45

Any safety devices including low water cutoffs used in conjunction 

with this boiler should receive periodic (every six months) inspection 

to assure proper operation.  A low water cutoff device of the float 

type should be flushed every six months.  Periodic checks, at least 

twice a year, should be made for water leaks.

More frequent inspections may be necessary depending on water 

conditions.

The boiler-mounted gas and electrical controls have been designed 

to give both dependable service and long life.  However, malfunction 

can  occur,  as  with  any  piece  of  equipment.    It  is  therefore 

recommended that all components be checked periodically by a 

qualified serviceman for proper operation.

RELIEF VALVE

The safety relief valve should be opened at least twice a year 

to check its working condition.  This will aid in assuring proper 

pressure relief protection.  Lift the lever at the top of the valve 

several times until the valve seats properly and operates freely.

BLOWER COMPARTMENT

The blower compartment should be cleaned annually to remove 

any dirt and lint that may have accumulated in the compartment or 

on the blower and motor.  Buildups of dirt and lint on the blower 

and motor can create excessive loads on the motor resulting 

in  higher  that  normal  operating  temperatures  and  possible 

shortened service life.

BURNER MAINTENANCE

Qualified servicers should follow this procedure when the boiler’s 

burner needs cleaning.

1.  Turn off the electrical power to the boiler and close the main 

manual gas shutoff valve(s). Allow the boiler parts to cool before 

disassembly.

2.  Loosen the flange and separate the gas train from the manifold 

assembly.

3.  Separate the burner from the blower adapter by first removing 

the four (4) bolts and subsequently, the blower gas kets. The 

blower should be free to move at this point.

  FOR DIRECT VENT UNITS: It is necessary to loosen and 

slide the rubber coupling on the blower adaptor in order to 

move the blower.

4.  Loosen the seven bolts on the blower adapter at the base and 

move the burner ground wire (Green) aside.

5.  Lift the blower adapter and remove the manifold assembly up 

from the 6 studs located on the cover plate and remove the 

burner gasket.  

6.  Remove any loose foreign material such as dust or lint with a 

vacuum. Check all ports for blockage.  Dislodge any foreign 

material causing blockage. Remove any soot or carbon deposits 

with a rag making sure to remove any lint  left on the burner by 

vacuuming again.

7.  Reverse the steps to reassemble the unit.

8.  Restore electrical power and gas supply to the boiler.

  •  Put the boiler back in operation by following the Lighting and 

Operating instructions in this manual.

  •  Check for gas leaks and proper boiler and vent operation.

CONDENSATE REMOVAL SYSTEM

Due to the highly efficient operation of this unit, condensate is 

formed during operation and must be removed by the conden-

sate drain systems. Inspect the condensate drains and tubes 

at least once a month and insure they will allow the free flow of 

condensate at all times. The system must be inspected more 

frequently in cold weather if the drain system is located in an 

area, such as along the floor, where freezing tempera tures are 

likely to occur. The conden sate drain system must be protected 

against freezing. Contact a qualified service agent to inspect 

and correct the condition if freezing of the conden sate lines 

is a problem.

The transparent drain lines and condensate drain on the bottom 

of the vent collector should be visually inspected at one month 

intervals for blockage, particularly in the areas of the loops in the 

lines which trap a small amount of conden sate, and the exit point 

of the vent collector drain.  Conden sate in portions of the line other 

than the loop area indicates a blockage in the drain line.  Flush the 

Summary of Contents for VB/VW 1500, 2000

Page 1: ...ur building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service mu...

Page 2: ...45 Venting Maintenance 46 Heat Exchanger Preventive Maintenance 46 Tube Cleaning Procedure 46 Replacement Parts 46 LIMITED WARRANTY 43 TABLE OF CONTENTS 2 safe installation use and service 3 APPROVAL...

Page 3: ...hazardous situation which if not avoided could result in property damage WARNING CAUTION CAUTION DANGER All safety messages will generally tell you about the type of hazard what can happen if you do...

Page 4: ...etup and instructions before lighting Failure to implement the proper setup will result in improper and inefficient operation of the appliance resulting in production of increased levels of carbon mon...

Page 5: ...hout water 4 Sooting If the boiler has been exposed to flooding it must be replaced LIQUEFIED PETROLEUM GAS MODELS Boilers for propane or liquefied petroleum gas LPG are different from natural gas mod...

Page 6: ...d trademark of Allegheny Ludlum Corporation The installation must conform to all instructions contained in this manual and the local code authority having jurisdiction These should be carefully follow...

Page 7: ...60hz and 30 amps TABLE 2 ROUGH IN DIMENSIONS Models VB VW 1500 VB VW 2000 Dimensions inches mm inches mm Flue Outlet Diameter 7 178 7 178 Air Intake Diameter 6 152 6 152 Water Inlet 2 5 inch NPT Water...

Page 8: ...Igniter is a device that ignites the main burner see Figure 3 When 120 VAC is applied to the igniter suf fi cient heat is generated to ignite the main burner Although improvements have been made to s...

Page 9: ...s to the gas valve during operation FLOW SWITCH The flow switch pictured in figure 6 activates when sufficient flow has been established Switch will not close when flow is restricted or is not present...

Page 10: ...Temperature Probe allows a boiler to sense the actual water temperature inside the storage tank or hydronic heating loop The boiler will modulate its firing rate in response to the actual system tempe...

Page 11: ...use type fusible plug cartridge or linkage T P relief valve should have a temperature rating of 210 F 99 C a pressure rating not exceeding lowest rated working pressure of any system compo nent and a...

Page 12: ...far as is practical close all building doors and windows and all doors between the space in which the appliances remaining connected to the common venting system are located and other spaces of the bu...

Page 13: ...zed louvers and grilles should be fixed in the open position FRESH AIR OPENINGS FOR CONFINED SPACES The following instructions should be used to calculate the size number and placement of openings pro...

Page 14: ...wo permanent vertical ducts one commencing within 12 inches 300 mm of the top and one commencing within 12 inches 300 mm of the bottom of the enclosure The vertical ducts should communicate directly w...

Page 15: ...into building or combustion air inlet to any other appliance 6 inches 15 cm for appliances up to 10 000 Btu hr 3 kW 12 inches 30 cm for appliances between 10 000 Btu hr 3 kW and 100 000 Btu hr 30kW 3...

Page 16: ...let into building or combustion air inlet to any other appliance 6 inches 15 cm for appliances up to 10 000 Btu hr 3 kW 12 inches 30 cm for appliances between 10 000 Btu hr 3 kW and 100 000 Btu hr 30...

Page 17: ...tion directly through an outside wall see Figure 11A 3 Horizontal Direct Vent using TWT to exhaust flue prod ucts and PVC piping to bring combus tion air to the boiler from the outside see Figures 12...

Page 18: ...um of 6 feet 2 0m separation between the air intake and the exhaust terminals HORIZONTAL INSTALLATION REQUIREMENTS 1 The vent system must terminate with a AL 29 4C Vent Through the Wall Termination TW...

Page 19: ...r parapet it must extend a minimum of 2 610mm above the wall or parapet Joints are not joined to show vent pipe orientation FIGURE 11 VERTICAL TERMINATION FIGURE 11A HORIZONTAL THROUGH THE WALL TERMIN...

Page 20: ...ED CARBON MONOXIDE DETECTORS Each carbon monoxide detector as required in accordance with the above provisions should comply with NFPA 720 and be ANSI UL 2034 listed and CSA certified SIGNAGE A metal...

Page 21: ...nt terminal NOTES If the exhaust vent terminal is within 10 3 0m of a wall or parapet it must extend a minimum of 2 610mm above the wall or parapet Joints are not joined to show vent pipe orientation...

Page 22: ...R PARAPET ON SIDEWALL VENT INSTALLATION REFER TO 11A and 12 FOR SPACING SPECIFICATIONS FOR EXHAUST AND AIR INTAKE PIPE INSTALLATIONS CLEARANCES SUPPORT ETC REFER TO FIGURES 11 AND 11A VERTICAL AIR INT...

Page 23: ...expansion tank as shown in Figure 13 The sizing of the expansion tank for a closed system is very important and is directly related to the total water volume of the system Refer to Systems and Equipme...

Page 24: ...ee support phone number on the back of this manual to order the Quad Thermistor Probe On domestic hot water applications the Remote Temperature Probe or the optional Quad Thermistor Probe must be inst...

Page 25: ...ugh improper testing of gas lines or emergency malfunction of supply system the gas valves must be checked for safe operation Make sure that the outside vents on supply regulators and the safety vent...

Page 26: ...the three voltage tests below Refer to Figure 12D for these tests Confirm RMS voltage between H and GND 108 VAC minimum 132 VAC maximum N and H 108 VAC minimum 132 VAC maximum N and GND 1 VAC maximum...

Page 27: ...8 000 12 636 000 11 700 000 11 232 000 10 452 000 9 360 000 8 580 000 7 800 000 7 176 000 kW 10 508 7 219 5 848 4 980 4 432 4 021 3 701 3 427 3 290 3 061 2 741 2 513 2 284 2 102 Table 7 Suggested Pipe...

Page 28: ...NE BOILER PRIMARY SECONDARY HYDRONIC PIPING SYSTEM LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP REMOTE TEMPERATURE PROBE DRAIN FULL PORT BALL VALVE TEMPERATURE GAGE...

Page 29: ...NK RECOVERY SYSTEM ONE TEMPERATURE LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP REMOTE TEMPERATURE PROBE DRAIN FULL PORT BALL VALVE TEMPERATURE GAGE WATER FLOW SWITC...

Page 30: ...STORAGE TANK RECOVERY SYSTEM ONE TEMPERATURE LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP REMOTE TEMPERATURE PROBE DRAIN FULL PORT BALL VALVE TEMPERATURE GAGE WATER...

Page 31: ...DB F7 3 AMP FUSE PDB F3 7 5 AMP FUSE MCB II F1 24VDC GENERATION MCB II R K6 RELAY COIL MCB II MR HIGH LIMIT FLOW SWITCH LWCO SWITCH OPTIONAL LOW GAS SWITCH HIGH GAS SWITCH OPTIONAL EXTERNAL ENABLE OPT...

Page 32: ...ed 7 Must be ON low gas switch always used 8 Spare n a 9 Spare n a 10 Spare n a MCB II DETAIL B DIP SWITCH SW2 FUNCTIONS ON IS POS ITION AWAY FR OM BOAR D S E DGE 1 Spare not used 2 High gas switch ON...

Page 33: ...AL LEGEND 120VAC WIRING LOW VOLTAGE WIRING CAT 5 COMM CABLE AVAILABLE OPTION NOTE1 IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE APPLIANCE MUST BE REPLACED REPLACE WITH EQUIVALNET GAUGE WIRE INSULA...

Page 34: ...essure Close bypass valve and permit pressure to be established by the pressure reducing valve 2 Vent all high points in system to purge system of air Provisions should be made to permit manual ventin...

Page 35: ...make further adjustments on the outlet and bypass valves until the desired inlet and outlet water temperatures are reached MANIFOLD PRESSURE CONNECTIONS Take the manifold pressure refer to Table 1 by...

Page 36: ...36 LIGHTING AND OPERATING INSTRUCTIONS...

Page 37: ...fully adjust the low fire gas setting to achieve the CO2 level prescribed in above reference table Note The rotation of the Low Fire adjustment is opposite of the High Fire as follows Clockwise rotati...

Page 38: ...t will operate with the voltage and current level provided Pump MCB 120VAC required on systems that do not have an external pump Provides electrical power to directly operate a pump or the coil of an...

Page 39: ...idle state as displayed by the Standby LED The control will continue to monitor heat demand and state of other system devices Upon a drop of water temperature below the set parameters the control will...

Page 40: ...when the fault state is exited Hard Fault State See Fault Description section for list of soft and Auto Reset faults The pump remains on for the selected post circulate time to cycle the hot water ou...

Page 41: ...soft lockout condition will occur and burner will be shut off This fault condition is automatically cleared when temperature drops below high limit setpoint minus high limit differential AUTO HIGH LI...

Page 42: ...nwards in screens to reach a desired item and to change setpoints and user settings They have an auto increment decrement feature for some of the configurations and values When you first press one of...

Page 43: ...the MCB and reading the resistance across the two active pinsontheconnectoratthe end of the probe cable The value should be approximately 0 ohms when the temperature of the probe is less than 220 F L...

Page 44: ...ction of the servo pressure regulator Replace the valve and add a gas filter in front of the new valve preventative maintenance This is a pre mix burner system The flame is not supposed to be directly...

Page 45: ...to move at this point FOR DIRECT VENT UNITS It is necessary to loosen and slide the rubber coupling on the blower adaptor in order to move the blower 4 Loosen the seven bolts on the blower adapter at...

Page 46: ...xist As the water is heated these tend to drop out depositing as scale or lime This scale must be removed before the heat exchanger tubes become blocked DELIMING The amount of calcium carbonate lime r...

Page 47: ...his boiler under state or provincial law are limited to one 1 year duration for the boiler or any of its parts Some states and provinces do not allow limitations on how long an implied warranty lasts...

Page 48: ...48 500 Tennessee Waltz Parkway Ashland City TN 37015 Technical Support 800 527 1953 Parts 800 433 2545 Fax 800 644 9306 www hotwater com...

Reviews: