background image

39

OPERATING SEQUENCE

1.  The EMC modulation controller has four modes of operation: 

Initialization, Standby, Running/Modulation, and Service. The 

internal MCB  micros control these modes through a sequence 

of steps (or States) which are further described in the “UIM 

Operating Procedures” section.

2.  When power is applied to the system, it enters the initialization 

mode and the following automatic functions are performed:

 

•  A. O. Smith opening screen is displayed.

 

•  The system goes through a calibration indicated by the 

green running LED blinking and then staying on; next the 

red service LED and yellow standby LEDs come on, next 

the service and runnings LEDs blink ON and OFF.

 

•  Stored values are recalled from memory.

 

•  Configuration dipswitches are read.

 

•  Pending faults are recalled

 

•  Micros on all boards start running (indicated by a flashing 

Yellow LED near each micro)

 

•  Input sensors are read

3.  After  initialization  is  complete  (approximately  10  seconds)  

system turns green LED off and goes to standby mode (yellow 

“Standby” LED on), unless a previously stored fault has been 

recalled,  which  will  send  system  into  service  model  (red 

“Service” LED on). In standby mode display shows temperature 

screen and in fault mode current error screen is displayed.

4.  The  system  then  compares  the  temperature  read  from  the 

controlling probe (inlet or tank) to the setpoint temperature.  If 

the temperature is less than the operating setpoint minus the 

setpoint differential temperature and the enable/disable input 

is closed then a call for heat is established and the system 

shifts to the run mode (green “Running” LED turns on).

5.  The heating sequence begins by applying power to the pump.
6.  After a few seconds the blower is turned on for 30-second 

pre-purge period of combustion chamber.

7.  The  igniter is turned on.
8.  After the igniter has reached a minimum of 2.8 amps, the gas 

valve is energized to allow gas flow to burner.

9.  After an additional one second, the system checks status of the 

flame through the flame rod (sensor). If the flame is not verified 

within 4 seconds, the gas valve is immediately shut off followed 

by 15-second inter-purge period, then the system returns to 

step 7, if the “Trial for Ignition” dipswitch is set for three (3) tries. 

If the dipswitch is set for one (1) trial, the system will declare 

an error and boiler will require resetting the control. 

10.  Boiler  will  remain  running  until  set  point  is  satisfied.  Once 

satisfied, blower will continue for 15-second post purge period.

11.  Once set point has have been satisfied, the boiler pump will 

continue to run for the programmed post-circulate cycle.

12.  The  control  now  enters  the  idle  state  as  displayed  by  the 

“Standby”  LED.  The  control  will  continue  to  monitor  heat 

demand and state of other system devices. Upon a drop of 

water temperature below the set parameters, the control will 

return to step 5 and repeat the entire operating cycle. Note: 

Any fault detection, during standby or running modes, will halt 

the heating sequence and shift the system to the service mode 

where the detected fault will be displayed.

NOTE:  In  standby  and  running  modes  the  system  constantly 

monitors  the  signals  and  the  internal  operation  for  faults. Any 

detected fault will halt the heating sequence and shift the system 

to the service mode, where the detected fault will be displayed.

TEMPERATURE SETPOINTS (SYSTEM CONTROL ALGORITHM)

The boiler has a hysteresis type control, which means that it will 

begin  heating  the  water  when  the  temperature  sensed  by  the 

control  probe  (inlet  or  tank)  falls  below  the  operating  setpoint 

minus the differential setpoint. It will stop heating the water when 

the temperature rises to the operating setpoint. 

UIM OPERATING PROCEDURES

FIGURE 19.  UIM, USER INTERFACE MODULE

The UIM receives commands from user and displays operational 

information to user via an LCD (liquid crystal display) up to eleven 

LED’s, and five touch switches.  The LCD provides information 

to user by use of 10 menu-activated screens. Within each of the 

screens, helpful information can be displayed by pressing “Help” 

button. The LED’s visually inform user about the mode the system 

is in. The touch switches allow user to control operation of system. 

The operation of these parts is described in the following section:

UIM Screens:

On all screens a double vertical bar appears on right side of display 

each time a key is touched to indicate that a key has been activated. 

On several screens an indicator “>” appears on left side of display 

to indicate active line. The “Up/Down” keys are used to move the 

indicator to the desired line and the “Select” key is pressed to select 

the line. Also, on most of the screens, up/down arrows appear on 

the right side of the screen to indicate that there is additional lines 

either above or below the displayed four lines.

• 

Menu Screen:

  Displayed when the user presses the “Menu” key.  This screen 

is the selection point for the other 9 screens.

MCB - Three position Dipswitch SW2:

This dipswitch is similar to the FCB dipswitches described below, but with only three switches being used: the number of blower speeds 

(switch #3), Hi Gas option (switch #2) and a spare (switch #1).  Only the blower speed and Hi Gas options are the required selection, 

within the MCB, see Figure 17.

     Dipswitch Function

Dipswitch Position

     SW2 P1: Spare:

            NOT USED

        NOT USED

     SW2 P2: Hi Gas pressure switch:

            On = Yes

        Off = No

     SW2 P3: Number of Blower Speeds:

            NOT USED

        NOT USED

Example of Dipswitch configuration: 

No High Gas, 1 blower speed.

Summary of Contents for VB/VW 1500, 2000

Page 1: ...ur building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service mu...

Page 2: ...45 Venting Maintenance 46 Heat Exchanger Preventive Maintenance 46 Tube Cleaning Procedure 46 Replacement Parts 46 LIMITED WARRANTY 43 TABLE OF CONTENTS 2 safe installation use and service 3 APPROVAL...

Page 3: ...hazardous situation which if not avoided could result in property damage WARNING CAUTION CAUTION DANGER All safety messages will generally tell you about the type of hazard what can happen if you do...

Page 4: ...etup and instructions before lighting Failure to implement the proper setup will result in improper and inefficient operation of the appliance resulting in production of increased levels of carbon mon...

Page 5: ...hout water 4 Sooting If the boiler has been exposed to flooding it must be replaced LIQUEFIED PETROLEUM GAS MODELS Boilers for propane or liquefied petroleum gas LPG are different from natural gas mod...

Page 6: ...d trademark of Allegheny Ludlum Corporation The installation must conform to all instructions contained in this manual and the local code authority having jurisdiction These should be carefully follow...

Page 7: ...60hz and 30 amps TABLE 2 ROUGH IN DIMENSIONS Models VB VW 1500 VB VW 2000 Dimensions inches mm inches mm Flue Outlet Diameter 7 178 7 178 Air Intake Diameter 6 152 6 152 Water Inlet 2 5 inch NPT Water...

Page 8: ...Igniter is a device that ignites the main burner see Figure 3 When 120 VAC is applied to the igniter suf fi cient heat is generated to ignite the main burner Although improvements have been made to s...

Page 9: ...s to the gas valve during operation FLOW SWITCH The flow switch pictured in figure 6 activates when sufficient flow has been established Switch will not close when flow is restricted or is not present...

Page 10: ...Temperature Probe allows a boiler to sense the actual water temperature inside the storage tank or hydronic heating loop The boiler will modulate its firing rate in response to the actual system tempe...

Page 11: ...use type fusible plug cartridge or linkage T P relief valve should have a temperature rating of 210 F 99 C a pressure rating not exceeding lowest rated working pressure of any system compo nent and a...

Page 12: ...far as is practical close all building doors and windows and all doors between the space in which the appliances remaining connected to the common venting system are located and other spaces of the bu...

Page 13: ...zed louvers and grilles should be fixed in the open position FRESH AIR OPENINGS FOR CONFINED SPACES The following instructions should be used to calculate the size number and placement of openings pro...

Page 14: ...wo permanent vertical ducts one commencing within 12 inches 300 mm of the top and one commencing within 12 inches 300 mm of the bottom of the enclosure The vertical ducts should communicate directly w...

Page 15: ...into building or combustion air inlet to any other appliance 6 inches 15 cm for appliances up to 10 000 Btu hr 3 kW 12 inches 30 cm for appliances between 10 000 Btu hr 3 kW and 100 000 Btu hr 30kW 3...

Page 16: ...let into building or combustion air inlet to any other appliance 6 inches 15 cm for appliances up to 10 000 Btu hr 3 kW 12 inches 30 cm for appliances between 10 000 Btu hr 3 kW and 100 000 Btu hr 30...

Page 17: ...tion directly through an outside wall see Figure 11A 3 Horizontal Direct Vent using TWT to exhaust flue prod ucts and PVC piping to bring combus tion air to the boiler from the outside see Figures 12...

Page 18: ...um of 6 feet 2 0m separation between the air intake and the exhaust terminals HORIZONTAL INSTALLATION REQUIREMENTS 1 The vent system must terminate with a AL 29 4C Vent Through the Wall Termination TW...

Page 19: ...r parapet it must extend a minimum of 2 610mm above the wall or parapet Joints are not joined to show vent pipe orientation FIGURE 11 VERTICAL TERMINATION FIGURE 11A HORIZONTAL THROUGH THE WALL TERMIN...

Page 20: ...ED CARBON MONOXIDE DETECTORS Each carbon monoxide detector as required in accordance with the above provisions should comply with NFPA 720 and be ANSI UL 2034 listed and CSA certified SIGNAGE A metal...

Page 21: ...nt terminal NOTES If the exhaust vent terminal is within 10 3 0m of a wall or parapet it must extend a minimum of 2 610mm above the wall or parapet Joints are not joined to show vent pipe orientation...

Page 22: ...R PARAPET ON SIDEWALL VENT INSTALLATION REFER TO 11A and 12 FOR SPACING SPECIFICATIONS FOR EXHAUST AND AIR INTAKE PIPE INSTALLATIONS CLEARANCES SUPPORT ETC REFER TO FIGURES 11 AND 11A VERTICAL AIR INT...

Page 23: ...expansion tank as shown in Figure 13 The sizing of the expansion tank for a closed system is very important and is directly related to the total water volume of the system Refer to Systems and Equipme...

Page 24: ...ee support phone number on the back of this manual to order the Quad Thermistor Probe On domestic hot water applications the Remote Temperature Probe or the optional Quad Thermistor Probe must be inst...

Page 25: ...ugh improper testing of gas lines or emergency malfunction of supply system the gas valves must be checked for safe operation Make sure that the outside vents on supply regulators and the safety vent...

Page 26: ...the three voltage tests below Refer to Figure 12D for these tests Confirm RMS voltage between H and GND 108 VAC minimum 132 VAC maximum N and H 108 VAC minimum 132 VAC maximum N and GND 1 VAC maximum...

Page 27: ...8 000 12 636 000 11 700 000 11 232 000 10 452 000 9 360 000 8 580 000 7 800 000 7 176 000 kW 10 508 7 219 5 848 4 980 4 432 4 021 3 701 3 427 3 290 3 061 2 741 2 513 2 284 2 102 Table 7 Suggested Pipe...

Page 28: ...NE BOILER PRIMARY SECONDARY HYDRONIC PIPING SYSTEM LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP REMOTE TEMPERATURE PROBE DRAIN FULL PORT BALL VALVE TEMPERATURE GAGE...

Page 29: ...NK RECOVERY SYSTEM ONE TEMPERATURE LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP REMOTE TEMPERATURE PROBE DRAIN FULL PORT BALL VALVE TEMPERATURE GAGE WATER FLOW SWITC...

Page 30: ...STORAGE TANK RECOVERY SYSTEM ONE TEMPERATURE LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP REMOTE TEMPERATURE PROBE DRAIN FULL PORT BALL VALVE TEMPERATURE GAGE WATER...

Page 31: ...DB F7 3 AMP FUSE PDB F3 7 5 AMP FUSE MCB II F1 24VDC GENERATION MCB II R K6 RELAY COIL MCB II MR HIGH LIMIT FLOW SWITCH LWCO SWITCH OPTIONAL LOW GAS SWITCH HIGH GAS SWITCH OPTIONAL EXTERNAL ENABLE OPT...

Page 32: ...ed 7 Must be ON low gas switch always used 8 Spare n a 9 Spare n a 10 Spare n a MCB II DETAIL B DIP SWITCH SW2 FUNCTIONS ON IS POS ITION AWAY FR OM BOAR D S E DGE 1 Spare not used 2 High gas switch ON...

Page 33: ...AL LEGEND 120VAC WIRING LOW VOLTAGE WIRING CAT 5 COMM CABLE AVAILABLE OPTION NOTE1 IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE APPLIANCE MUST BE REPLACED REPLACE WITH EQUIVALNET GAUGE WIRE INSULA...

Page 34: ...essure Close bypass valve and permit pressure to be established by the pressure reducing valve 2 Vent all high points in system to purge system of air Provisions should be made to permit manual ventin...

Page 35: ...make further adjustments on the outlet and bypass valves until the desired inlet and outlet water temperatures are reached MANIFOLD PRESSURE CONNECTIONS Take the manifold pressure refer to Table 1 by...

Page 36: ...36 LIGHTING AND OPERATING INSTRUCTIONS...

Page 37: ...fully adjust the low fire gas setting to achieve the CO2 level prescribed in above reference table Note The rotation of the Low Fire adjustment is opposite of the High Fire as follows Clockwise rotati...

Page 38: ...t will operate with the voltage and current level provided Pump MCB 120VAC required on systems that do not have an external pump Provides electrical power to directly operate a pump or the coil of an...

Page 39: ...idle state as displayed by the Standby LED The control will continue to monitor heat demand and state of other system devices Upon a drop of water temperature below the set parameters the control will...

Page 40: ...when the fault state is exited Hard Fault State See Fault Description section for list of soft and Auto Reset faults The pump remains on for the selected post circulate time to cycle the hot water ou...

Page 41: ...soft lockout condition will occur and burner will be shut off This fault condition is automatically cleared when temperature drops below high limit setpoint minus high limit differential AUTO HIGH LI...

Page 42: ...nwards in screens to reach a desired item and to change setpoints and user settings They have an auto increment decrement feature for some of the configurations and values When you first press one of...

Page 43: ...the MCB and reading the resistance across the two active pinsontheconnectoratthe end of the probe cable The value should be approximately 0 ohms when the temperature of the probe is less than 220 F L...

Page 44: ...ction of the servo pressure regulator Replace the valve and add a gas filter in front of the new valve preventative maintenance This is a pre mix burner system The flame is not supposed to be directly...

Page 45: ...to move at this point FOR DIRECT VENT UNITS It is necessary to loosen and slide the rubber coupling on the blower adaptor in order to move the blower 4 Loosen the seven bolts on the blower adapter at...

Page 46: ...xist As the water is heated these tend to drop out depositing as scale or lime This scale must be removed before the heat exchanger tubes become blocked DELIMING The amount of calcium carbonate lime r...

Page 47: ...his boiler under state or provincial law are limited to one 1 year duration for the boiler or any of its parts Some states and provinces do not allow limitations on how long an implied warranty lasts...

Page 48: ...48 500 Tennessee Waltz Parkway Ashland City TN 37015 Technical Support 800 527 1953 Parts 800 433 2545 Fax 800 644 9306 www hotwater com...

Reviews: