background image

20

B.  Deburring

  Use a knife, plastic pipe deburring tool, or 

fi

 le to remove burrs 

from the end of small diameter pipe.  Be sure to remove all burrs 
from around the inside as well as the outside of the pipe.  A slight 
chamfer (bevel) of about 10°-15° should be added to the end to 
permit easier insertion of the pipe into the end of the 

fi

 tting.  Failure 

to chamfer the edge of the pipe may remove cement from the 

fi

 tting 

socket, causing the joint to leak.

STEP B

C. Test dry 

fi

 t of the joint

 Tapered 

fi

 tting sockets are designed so that an interfaced 

fi

 t should 

occur when the pipe is inserted about 1/3 to 2/3 of the way into 
the socket. Occasionally, when pipe 

fi

 tting dimensions are at the 

tolerance extremes, it will be possible to fully insert dry pipe to the 
bottom of the 

fi

 tting socket.  When this happens, a suf

fi

 cient quantity 

of cement must be applied to the joint to 

fi

 ll the gap between the 

pipe and 

fi

 tting.  The gap must be 

fi

 lled to obtain a strong, leak-free 

joint.

D.  Inspection, cleaning, priming

  Visually inspect the inside of the pipe and 

fi

 tting sockets and 

remove all dirt, grease or moisture with a clean dry rag. If wiping 
fails to clean the surfaces, a chemical cleaner must be used.  
Check for possible damage such as splits or cracks and replace 
if necessary.

 

Depth-of-entry

 

Marking the depth of entry is a way to check if the pipe has reached 
the bottom of the 

fi

 tting socket in Step F.  Measure the 

fi

 tting depth 

and mark this distance on the pipe O.D. You may want to add 
several inches to the distance and make a second mark as the 
primer and cement will most likely destroy your 

fi

 rst one.

  Apply primer to the surface of the pipe and 

fi

 tting socket with a 

natural bristle brush. This process softens and prepares the PVC 
or CPVC for the solvent cementing step.  Move quickly and without 
hesitation to the cementing procedure while the surfaces are still 
wet with primer.

E.  Application of solvent cement

 

•  Apply the solvent cement evenly and quickly around the outside 

of the pipe at a width a little greater than the depth of the 

fi

 tting 

socket.

 

•  Apply a light coat of cement evenly around the inside of the  

fi

 tting socket.  Avoid puddling.

 

•  Apply a second coat of cement to the pipe end.

                   

STEP E

F. Joint assembly

 

Working quickly, insert the pipe into the 

fi

 tting socket bottom and 

give the pipe or 

fi

 tting a 1/4 turn to evenly distribute the cement. 

Do not continue to rotate the pipe after it has hit the bottom of the 

fi

 tting socket. A good joint will have suf

fi

 cient cement to make a 

bead all the way around the outside of the 

fi

 tting hub. The 

fi

 tting 

will have a tendency to slide back while the cement is still wet so 
hold the joint together for about 15 seconds.

                             

STEP F

G. Cleanup and joint movement

 

Remove all excess cement from around the pipe and 

fi

 tting with a 

dry cotton rag. This must be done while the cement is still soft.

 

The joint should not be disturbed immediately after the cementing 
procedure, and suf

fi

 cient time should be allowed for proper curing of 

the joint. Exact drying time is dif

fi

 cult to predict because it depends 

on variables such as temperature, humidity and cement integrity. 
For more speci

fi

 c information, you should contact your solvent 

cement manufacturer.

                                

STEP G

Summary of Contents for ProMax Power-Vent 185237-004

Page 1: ...ECHNICAL AND WARRANTY QUESTIONS SHOULD BE DIRECTED TO THE LOCAL DEALER FROM WHOM THE WATER HEATER WAS PURCHASED IF YOU ARE UNSUCCESSFUL PLEASE WRITE TO THE COMPANY LISTED ON THE RATING PLATE ON THE WA...

Page 2: ...T DEFINITIONS Qualified Installer A qualified installer must have ability equivalent to a licensed tradesman in the fields of plumbing air supply venting and gas supply including a thorough understand...

Page 3: ...3 GENERAL SAFETY...

Page 4: ...fety rules the water heater will not operate properly It could cause DEATH SERIOUS BODILY INJURY AND OR PROPERTY DAMAGE This manual contains instructions for the installation operation and maintenance...

Page 5: ...tally vented gas fueled heating appli ance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS INSPECTION The s...

Page 6: ...in Valve X Gas Control Valve Y Drain Pan Z Air Intake Screen Base Pan AA Inner Door B B Outer Door CC HSI Burner Assembly D D Air Intake Screen Blower Assembly E E FV Sensor Bracket Assembly 40K 50K M...

Page 7: ...than others These include the elderly children the infirm or physically mentally handicapped If anyone using hot water in your home fits into one of these groups or if there is a local code or state l...

Page 8: ...er an alarm or turn off the incoming water to the water heater when leakage is detected Sensors mounted in the drain pan that turn off the water supply to the entire home when water is detected in the...

Page 9: ...xceeds the National Appliance Energy Conversation Act standards with respect to insulation and standby loss requirements making an insulation blanket unnecessary Should you choose to apply an insulati...

Page 10: ...ors through vertical ducts each opening shall have a minimum free area of 1 square inch per 4 000 Btu per hour 5 5 cm2 kW of total input rating of all equipment in the enclosure see Figure 8 3 When co...

Page 11: ...res higher than required for domestic water purposes a tempering valve must be installed Please refer to Figure 2 for suggested piping arrangement CLOSED WATER SYSTEMS Water supply systems may because...

Page 12: ...ctly into the fitting of the water heater designed for the relief valve Position the valve downward and provide tubing so that any discharge will exit only within 6 inches 15 2 cm above or at any dist...

Page 13: ...er heater Use a soapy water solution not a match or open flame Rinse off soapy solution and wipe dry When installed at elevations above 7 700 feet 2 347 meters input rating should be reduced at the ra...

Page 14: ...is still mounted securely and the air intake screen of the blower assembly is installed in the dilution air opening Also make sure the drain port of the rubber boot vent adapter is capped off Lastly m...

Page 15: ...this water heater to an existing vent or chimney It must be vented separately from all other appliances Nonmetallic vent may be used if it has Heat Deflection Temperature HDT 66 psi or 455 kPa of at l...

Page 16: ...llations will have water condensate in the vent piping If this occurs then adequate means of draining and disposing of the condensate needs to be made by the installer CONDENSATE Condensate formation...

Page 17: ...building The manufacturer also recommends that the vent termination should not be installed closer than 18 45 7 cm from an inside corner of an L shaped structure and not be less than 1 foot 0 31 m abo...

Page 18: ...lied for decorative purposes only and is not a requirement for the vent termination if not needed by the installer VERTICAL VENT THROUGH ROOF This unit is approved for venting through the roof with th...

Page 19: ...15 2 cm and above PRIMER It is recommended that Tetrahydrofuran THF be used to prepare the surfaces of pipe and fittings for solvent welding Do not use water rags gasoline or any other substitutes fo...

Page 20: ...he distance and make a second mark as the primer and cement will most likely destroy your first one Apply primer to the surface of the pipe and fitting socket with a natural bristle brush This process...

Page 21: ...21...

Page 22: ...If a suitable area is not available a cover should be installed over the thermostat to prevent tampering The water temperature setting was factory set at the lowest temperature Pressing the COOLER bu...

Page 23: ...expansion Contact a local plumbing service agency to have a thermal expansion tank installed STRANGE SOUNDS Possible noises due to expansion and contraction of some metal parts during periods of heat...

Page 24: ...Viewport on the Inner Door see Figure 1 The main burner should provide complete combustion of gas ignite rapidly give reasonably quiet operation and cause no excessive flame lifting from the burner po...

Page 25: ...ils to completely reset and continues to release water immediately close the cold water inlet to the water heater follow the draining instructions and replace the temperature pressure relief valve wit...

Page 26: ...he tank Droplets form and drip onto the burner or run on the floor This is common at the time of start up after installation and when incoming water is cold I Water in the water heater bottom or on th...

Page 27: ...odels only 26B FV Sensor Bracket 55K 62 5K models only 27 Nipple with Heat Trap 28 Secondary Anode with Heat Trap Not Shown Optional Now that you have purchased this water heater should a need ever ex...

Page 28: ...INES TROUBLESHOOTING GUIDELINES TROUBLE SHOOTING Please check guidelines below For your safety water heater service should be performed only by a qualified service technician Read the GENERAL SAFETY I...

Page 29: ...29...

Page 30: ...be utilized by a qualified service agent When calling for service notify the service agent that this is a Flammable Vapor Ignition Resistant Product TROUBLESHOOTING GUIDELINES TROUBLESHOOTING GUIDELI...

Page 31: ...t any operation of it in a modified form or any attempt to repair tank leaks or parts will void this warranty SERVICE AND LABOR RESPONSIBILITY UNDER THIS LIMITED WARRANTY THE WARRANTOR WILL PROVIDE ON...

Page 32: ...32...

Reviews: