VENT CONNECTIONS TO BLOWER ASSEMBLY

Figure 15 shows the typical vent connections.

FIGURE 15.

VENTING AND INSTALLATION

Plan the layout of the vent system from the vent termination to the water 
heater considering all of the 90° and 45° elbows plus the number of 
feet of pipe that would be needed to install the total vent system.  Note: 
The inlet connection to the blower requires a minimum 3" long x 3" 
Schedule 40 PVC pipe.  The water heater must be vented to the 
outdoors as described in these instructions. DO NOT connect this water 
heater to an existing vent or chimney. It must be vented separately 
from all other appliances. The 

fi

 ttings, other than the supplied Vent 

Termination should be equivalent to the following: PVC (Schedule 40, 
DWV, ASTM D-2665), CPVC (Schedule 40, DWV, ASTM F-438), ABS 
(Schedule 40 DWV, ASTM D-2661). 
The cement used should be as recommended by the vent 
pipe manufacturer. See the instructions in the “VENT PIPE 
PREPARATION” section of this manual for the proper method of 
cutting and cementing the PVC pipe and 

fi

 ttings. 

All vent gases must be completely vented to the outdoors of the 
structure (dwelling). When determining the installation location for 
a power direct vent water heater, snow accumulation and drifting 
should be considered in areas where applicable.
IMPORTANT: DO NOT common vent this water heater with any 
other appliance.

FIGURE 16.

Horizontal runs must be securely supported at 3 1/2 foot (1 m) 
intervals and vertical runs supported at 5 foot (1.5 m) intervals.

FIGURE 17.

VENTING THROUGH AN OUTSIDE WALL

A. All 75 Gallon Models

In the carton is supplied: 

1.  Two 3” inlet and outlet PVC Schedule 40 - 45° vent caps.

2.  One 3” CPVC Schedule 80 - 90° elbow; used to connect the 

outlet

 

vent pipe to the water heater when the 

outlet

 vent pipe is to be 

turned horizontally directly off the blower.

3.  One 5’ (1.5 m) section of 3” CPVC Schedule 40 

outlet

 vent pipe. 

(More may be required and must be purchased locally.)

Note: A 2-5/8" (66.675 mm) long section of CPVC pipe can be cut 
from the 5' (1.5 m) section of 3" CPVC Schedule 40 vent pipe.  
This is used to connect the 

outlet

 vent pipe elbow to the water 

heater when the 

outlet

 vent pipe is to be turned horizontally 

directly off the blower.

FIGURE 18.

Requirements:
1.  The water heater requires its own (separate) venting system.
2. 

Only

 3” CPVC Schedule 40 piping and 

fi

 ttings are acceptable 

materials on the 

fi

 rst 

fi

 ve feet of the 

outlet

 vent system.

3. 3” PVC, ABS, or CPVC Schedule 40 piping and 

fi

 ttings  are 

acceptable materials for the 

inlet

 vent system and for the 

outlet

 

vent system after the 

fi

 rst 

fi

 ve feet. 

Summary of Contents for ProMax GPDX-50

Page 1: ...MODELS NOT FOR USE IN MANUFACTURED MOBILE HOMES ALL TECHNICAL AND WARRANTY QUESTIONS SHOULD BE DIRECTED TO THE LOCAL DEALER FROM WHOM THE WATER HEATER WAS PURCHASED IF YOU ARE UNSUCCESSFUL PLEASE WRIT...

Page 2: ...some of the substances included in the act This product is certified to comply with a maximum weighted average of 0 25 lead content as required in some areas IMPORTANT DEFINITIONS Qualified Installer...

Page 3: ...3...

Page 4: ...location to ensure the water heater complies with the Locating the New Water Heater section in this manual 6 For California installation this water heater must be braced anchored or strapped to avoid...

Page 5: ...tally vented gas fueled heating appli ance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS INSPECTION The s...

Page 6: ...Relief Valve O Flue P Flue Baffle Assembly Q Insulation R Rating Plate S Gas Supply T Manual Gas Shut off Valve U Ground Joint Union V Sediment Trap Dirt Leg W Drain Valve X Gas Control Valve Thermos...

Page 7: ...an others These include the elderly children the infirm or physically mentally disabled If anyone using hot water in your home fits into one of these groups or if there is a local code or state law re...

Page 8: ...s and retailers and detect and react to leakage in various ways Sensors mounted in the metal drain pan that trigger an alarm or turn off the incoming water to the water heater when leakage is detected...

Page 9: ...to provide ventilation air can result in a fire or explosion and can cause DEATH SERIOUS BODILY INJURY OR PROPERTY DAMAGE FIGURE 5 If this water heater will be used in beauty shops barber shops cleani...

Page 10: ...he vent exhaust outlet and air inlet terminals shall terminate at least 18 45 7 cm above the roof surface see Figure 9 FIGURE 9 AIR FOR VENTILATION FOR APPLIANCES LOCATED IN CONFINED SPACES Air for ve...

Page 11: ...interfere with safe operation of the water heater Do not cover the outer door gas control valve thermostat temperature pressure relief valve or FV Sensor Do not let insulation around the gas water he...

Page 12: ...ermanently injure you upon contact Some people are more likely to be permanently injured by hot water than others These include the elderly children the infirm or physically mentally disabled If anyon...

Page 13: ...he valve must meet the requirements of local codes but not less than a combination temperature and pressure relief valve certified as indicated in the above paragraph The valve must be marked with a m...

Page 14: ...prevent dirt and foreign materials from entering the gas control valve thermostat A flexible gas connector or a ground joint union between the shut off valve and gas control valve thermostat to permit...

Page 15: ...er Water must flow from the hot water faucet before turning ON gas to the water heater To fill the water heater with water 1 Close the water heater drain valve by turning the handle to the right clock...

Page 16: ...0 120 Vac therefore a grounded outlet must be within reach of the six 6 foot 1 8 m flexible power cord supplied with the unit See Figure 2 The power cord supplied may be used only where local codes pe...

Page 17: ...rect vent water heater snow accumulation and drifting should be considered in areas where applicable IMPORTANT DO NOT common vent this water heater with any other appliance FIGURE 16 Horizontal runs m...

Page 18: ...d 50 Gallon 40 000 BTU HR Models In the carton is supplied 1 Two 3 inlet and outlet PVC Schedule 40 45 vent caps All other piping must be supplied by the supplier FIGURE 20 If making an immediate hori...

Page 19: ...eet 1 5 m of length required in the horizontal run See Figure 25 FIGURE 25 The 3 PVC ABS or CPVC Schedule 40 vent pipe can be run from the water heater through the wall or from the wall to the water h...

Page 20: ...et PVC Schedule 40 45 vent caps are supplied A 5 1 5 m section of 3 CPVC Schedule 40 outlet vent pipe is supplied with 75 gallon models and a 5 1 5 m section of 3 ABS Schedule 40 outlet vent pipe is s...

Page 21: ...r CPVC Components and ABS for ABS components Containers Metal or Glass to hold Primer and Cement Select the type of PVC ABS or CPVC materials to be used on the basis of their application with respect...

Page 22: ...if necessary Depth of entry Marking the depth of entry is a way to check if the pipe has reached the bottom of the fitting socket in Step F Measure the fitting depth and mark this distance on the pipe...

Page 23: ...23...

Page 24: ...le area is not available a cover should be installed over the thermostat to prevent tampering The water temperature setting was factory set at the lowest temperature Pressing the COOLER button decreas...

Page 25: ...f water grows there will be a corresponding increase in water pressure due to thermal expansion Thermal expansion can cause premature tank failure leakage This type of failure is not covered under the...

Page 26: ...ntact a qualified installer or service agency to replace a flooded water heater Do not attempt to repair the unit It must be replaced At least once a year a visual inspection should be made of the mai...

Page 27: ...h are visible ANODE ROD DEPLETION FIGURE 32B If the anode rod shows signs of either or both it should be replaced NOTE Whether re installing or replacing the anode rod check for any leaks and immediat...

Page 28: ...restart the heater as directed in this manual If the water heater is going to be shut down for an extended period the drain valve should be left open IMPORTANT Condensation may occur when refilling th...

Page 29: ...ief valve may be leaking at the tank fitting F Water from a drain valve may be due to the valve being slightly opened G The drain valve may be leaking at the tank fitting H Combustion products contain...

Page 30: ...6 26 FV Sensor 27 Gas Control Valve Thermostat 28 Pressure Switch Air 29 Flue Baffle Assembly 30 Baffle Adaptor Collar Assembly 31 Optional 3 PVCHorizontalVentKit rating plate located above the gas c...

Page 31: ...aximum number of elbows or maximum equivalent feet of vent or intake air pipe has not been exceeded per the installation instructions in the manual that came with the water heater 4 Ensure there are n...

Page 32: ...c check has detected the FV flammable vapor sensor is either open or shorted 1 Turn off power to the water heater Ensure all FV sensor wiring the ignitor assembly plug and the ignitor assembly socket...

Page 33: ...d gas clean burner head Combustion air path restricted Check intake venting arrangement for obstructions Not enough dilution air for proper combustion Check intake venting arrangement for obstructions...

Page 34: ...ith specifications of the heating component manufacturer This warranty gives you specific legal rights and you may have other rights which vary under the laws of each province If any provision of this...

Page 35: ...similar water heater or parts thereof which are manufactured or distributed by the warrantor Dealer replacements are made subject to in warranty validation by warrantor PROOF OF PURCHASE AND PROOF OF...

Page 36: ...Copyright 2012 A O Smith Corporation All rights reserved...

Reviews: