Code and description
Cause
Measure
F04
(lock out error)
Ignition error
Three unsuccessful
ignition attempts.
No gas.
Make sure that the main gas supply valve
is open. If necessary, open the valve.
Make sure that the manual gas supply
valve, before the gas control valve, is
open. If necessary, open the valve.
Make sure that the gas supply pressure
to the gas control valve is correct, refer
to Gas supply pressure (see section
8.9.3).
•
•
•
Air in the gas pipes.
Bleed the air out of the gas pipe.
Make sure that the gas supply pressure
to the gas control valve is correct, refer
to Gas supply pressure (see section
8.9.3).
•
•
Defect in the hot surface igniter circuit.
Make sure that the hot surface igniter is
installed correctly.
Make sure that the wiring of the hot
surface igniter is not damaged.
Measure the resistance across the hot
surface igniter. This must be between the
36 and 72 Ohm (at room temperature).
Make sure that the hot surface igniter
lights up during ignition.
If necessary, replace the hot surface igniter.
•
•
•
•
Defect in the ionisation circuit.
Make sure that the flame probe is
installed correctly.
Make sure that the wiring of the flame
probe is not damaged.
Measure the ionisation current. This
current must be a minimum of 3 μA
(parameter
109
).
If necessary, replace the wiring and/or
flame probe.
•
•
•
Supply voltage too low.
Make sure that the measured voltage is
230 V
AC
(-15%, +10%).
Bent flame probe is in contact with
metal surface.
Make sure that the flame probe is not
bend.
If necessary, replace flame probe.
•
•
Ceramic part, of the flame probe, is
broken or cracked.
Make sure that the ceramic part of the
flame probe is not broken or cracked in
the vicinity of the burner.
If necessary, replace flame probe.
•
•
0312266_INNOVO_UKUK_V3.0, 2017-02-10
77
Summary of Contents for Innovo 12-160
Page 6: ...6...
Page 13: ...User part 0312266_INNOVO_UKUK_V3 0 2017 02 10 13...
Page 14: ...14...
Page 16: ...16 User part...
Page 18: ...18 User part...
Page 24: ...24 User part...
Page 27: ...Installation Maintenance and Service part 0312266_INNOVO_UKUK_V3 0 2017 02 10 27...
Page 28: ...28 User part...
Page 36: ...36 Installation Maintenance and Service part...
Page 43: ...Fig Venting systems 0312266_INNOVO_UKUK_V3 0 2017 02 10 43...
Page 58: ...58 Installation Maintenance and Service part...
Page 70: ...70 Installation Maintenance and Service part...
Page 83: ...0312266_INNOVO_UKUK_V3 0 2017 02 10 83...
Page 87: ...13 5 Declaration of conformity 0312266_INNOVO_UKUK_V3 0 2017 02 10 87...