Parameter
Description
Unit/Value
Adjustable
Range
Default
116
Status burner
Initialization
Reset
Stand-by
Pre-purge (1)
Pre-Purge (2)
Pre-Ignition
Ignition
Flame check
Burn
Post-Burn
Post-Purge (1)
Post-Purge (2)
Blocking
Lockout
Warning
Burner Boot
No
0
- Initialization
1
- Reset
2
- Stand-by
3
- Pre-purge
(part 1)
4
- Pre-Purge
(part 2)
5
- Pre Ignition
6
- Ignition
7
- Flame check
8
- Burn
9
- Post Burn
10
- Post Purge (part 1)
11
- Post Purge (part 2)
12
- Blocking
13
- Lockout
14
- Warning
15
- Burner Boot
-
117
Actual error number
#
No
C02
…
S13
---
- no error
-
120
Time left till service reminder
appears on display
Months
Days
No
≥ 1 Month =
01
-
36
< 1 Month =
01d
-
31d
12
201
Test cycle
dIS
FAn
Lo
Ign
Hi
rEg
Yes
dIS
- leave test cycle
FAn
- pre-purge on ignition
speed
Lo
- burn on partial load
Ign
- burn on ignition speed
Hi
- burn on full load
rEg
- t.b.d.
dIS
202
Turn the power anode warning
on or off.
Off
ON
Yes
Off
- power anodes deactivated
ON
- power anodes activated
ON
203
Minimum fan speed
×10 rpm
No
0
…
990
-
204
Ignition fan speed
×10 rpm
No
0
…
990
-
205
Maximum fan speed
×10 rpm
No
0
…
990
-
207
Maximum setpoint
ºC
No
40
…
85
70
208
Minimum load
%
Yes
0
…
50
0
and
1
= minimum load
50
= 50% between minimum
load and maximum load
0
211
Service reminder
Off
ON
rst
Yes
Off
- service reminder off
ON
- service reminder on
rst
- reset service reminder
ON
212
Setting service interval
Months
Yes
0
…
36
12
270
Last lock-out error
#
No
C02
…
S14
---
- no error
-
271
Interval between last lock-out
and read-out.
Minutes
Hours
Days
Weeks
No
00n
...
59n
= 0 till 59 minutes
01h
...
23h
= 1 till 23 hours
01d
...
06d
= 1 till 6 days
01
...
63
= 1 till 63 weeks
-
272
Last blocking error
#
No
C02
…
S14
---
- no error
-
60
Installation, Maintenance and Service part
Summary of Contents for Innovo 12-160
Page 6: ...6...
Page 13: ...User part 0312266_INNOVO_UKUK_V3 0 2017 02 10 13...
Page 14: ...14...
Page 16: ...16 User part...
Page 18: ...18 User part...
Page 24: ...24 User part...
Page 27: ...Installation Maintenance and Service part 0312266_INNOVO_UKUK_V3 0 2017 02 10 27...
Page 28: ...28 User part...
Page 36: ...36 Installation Maintenance and Service part...
Page 43: ...Fig Venting systems 0312266_INNOVO_UKUK_V3 0 2017 02 10 43...
Page 58: ...58 Installation Maintenance and Service part...
Page 70: ...70 Installation Maintenance and Service part...
Page 83: ...0312266_INNOVO_UKUK_V3 0 2017 02 10 83...
Page 87: ...13 5 Declaration of conformity 0312266_INNOVO_UKUK_V3 0 2017 02 10 87...