background image

30

VENTING SYSTEM

Examine the venting system every six months for obstructions
and/or deterioration of the vent piping.

Remove all soot or other obstructions from chimney which will
retard free draft.

REMOTE STORAGE TANK

TEMPERATURE CONTROL

The water temperature in the storage tank (if used) is controlled
by the storage tank temperature control.  The sensing element is
mounted in the hot water storage tank, see page 16.

A change in water temperature in the storage tank lower than the
tank temperature control setting will cause the sensor to activate
the circulating pump.  The pump then circulates the water through
the heater where the thermostat senses the drop in water
temperature and activates main burner operation of the appliance.
If the storage tank temperature control is out of calibration, replace
with new control.

 WARNING

SHOULD OVERHEATING OCCUR OR THE GAS SUPPLY FAIL
TO SHUT OFF, TURN OFF THE MANUAL GAS CONTROL VALVE
TO THE APPLIANCE.

RELIEF VALVE

At least once a year, the temperature and pressure relief valve
should be checked to ensure that it is in operating condition.  Lift
the lever at the top of the valve several times until the valve seats
properly and operates freely.

If the appliance installation includes other relief valves, such as
in “remote” storage tanks etc., check their relief valve operation
with the same frequency.

 WARNING

THE WATER PASSING OUT OF THE VALVE DURING THIS
CHECKING OPERATION MAY BE EXTREMELY HOT.  AVOID
CONTACT AND DISCHARGE SAFELY TO PREVENT WATER
DAMAGE.

If the temperature and pressure relief valve on the heater
discharges periodically or continuously, a problem exists.  This
may be due to unusually high water temperatures or pressures in
the system, or to a faulty relief valve.  Contact your dealer or a
qualified service technician to find the cause of the problem and
to correct it.  This may also be due to thermal expansion in a
closed water supply system.  Contact the water supplier or local
plumbing inspector on how to correct this situation.  

DO NOT

PLUG THE TEMPERATURE AND PRESSURE RELIEF VALVE.

 WARNING

SHOULD OVERHEATING OCCUR OR THE GAS SUPPLY FAIL
TO SHUT OFF, TURN OFF THE MANUAL GAS CONTROL VALVE
TO THE APPLIANCE.

HOT  WATER ODOR

On occasion, hot water may develop a strong odor.  If this occurs
drain the heater completely, flush thoroughly, and refill.  If the
problem persists, chlorination of the heater and replacement of

the factory installed magnesium anodes with aluminum anodes
may correct the condition.

Occasionally water softener companies recommend removal of
heater anodes for odor reasons.

 

CAUTION

Unauthorized removal of the anode(s) will void the warranty.  For
further information contact your dealer.

ANODE ROD INSPECTION

The heater tank is equipped with anode rods to provide corrosion
control.  At least once a year the anode rods should be checked
to determine if replacement is necessary.  Initially the anode rods
are approximately 7/8" (22mm) in diameter with a 1/8" (3mm)
diameter steel core wire running down the center of the anode
material.  THE ANODES SHOULD BE REPLACED when the 1/8"
(3mm) diameter core wire is visible as this means that the  anode
material has been expended in the control of corrosion.

For models with top inlet and outlet, it is recommended that,
before removing the inner cover for cleaning, inspection or
removal of inner parts, you obtain two new nipple collars, part
no. 74060.  The nipple collars on the heater will usually be
damaged when removed.  New pipe collars will insure that the
seal is such as to prevent leakage of flue products when properly
installed.

NOTE:

 

 Anode rod inspection may need to be made more

frequently in areas subject to acid rain that obtains their water
supply from surface water as the low pH will accelerate anode
activity.

CAUTION:

 

 Close cold water inlet valve serving heater and

open nearby hot water faucet to relieve the pressure in the
heater before attempting to remove anode(s) for inspection.

RECOMMENDED PROCEDURE FOR

PERIODIC REMOVAL OF LIME DEPOSITS
FROM TANK TYPE COMMERCIAL WATER

HEATERS

The amount of calcium carbonate (lime) released from water is in
direct proportion to water temperature and usage, see chart.  The
higher the water temperature or water usage, the more lime
deposits are dropped out of the water.  This is the lime scale
which forms in pipes, heaters and on cooking utensils.

Lime accumulation not only reduces the life of the equipment but
also reduces efficiency of the heater and increases fuel
consumption.

The usage of water softening equipment greatly reduces the
hardness of the water.  However, this equipment does not always
remove all of the hardness (lime).  For this reason it is
recommended that a regular schedule for deliming be
maintained.

The time between cleaning will vary from weeks to months
depending upon water conditions and usage.

Refer to A. O. Smith booklet, Form No. 4800, entitled “Why?
When and How” for detailed description on tank inspection and

Summary of Contents for BTR 120

Page 1: ...nnessee Waltz Parkway Ashland City TN 37015 Phone 800 527 1953 Fax 800 433 2515 www hotwater com CAUTION TEXT PRINTED OR OUTLINED IN RED CONTAINS INFORMATION RELATIVE TO YOUR SAFETY PLEASE READ THOROU...

Page 2: ...3 4 59 00 8 30 25 1 50 2 00 2 00 1 50 2 00 2 00 760 Lbs 874 Lbs 114 kW Hr 379 L 192 cm 12 cm 171 cm 148 cm 68 cm 58 cm 3 4 150 cm 20 cm 77 cm 1 50 2 00 2 00 1 50 2 00 2 00 345 Kg 396 Kg BTRC MODELS 1...

Page 3: ...1031 957 BTR 390 000 BTUH 100 Gal 80 1293 970 776 646 554 485 431 388 353 323 298 277 400 114 Kw Hr 379 L 4894 3671 2936 2447 2097 1835 1631 1468 1335 1224 1129 1049 TABLE 1D HEATER PERFORMANCE DATA B...

Page 4: ...ooting Guide 33 Operational Checklist 34 Limited Warranty 35 Page Page FOREWORD These designs comply with ANSI Z21 10 3 CSA 4 3 as an automatic circulating or automatic storage tank type water heater...

Page 5: ...explosive and heavier than air It collects first in the low areas making its odor difficult to detect at nose level If LP gas is present or even suspected do not attempt to find the cause yourself Go...

Page 6: ...or operation at altitudes other than that specified on the heater rating plate is not permitted The input reduction is primarily achieved by reducing the size of the main burner orifices To do this th...

Page 7: ...AUTOMATIC OPERATION and HOLD OPEN DAMPER For normal operation the switch should be in the AUTOMATIC OPERATION position If there is a problem with the damper the Service Switch can be placed in the HOL...

Page 8: ...g must be a continuous run no joints and retain the 6 16cm clearance unless an approved reducing thimble is used The National Sanitation Foundation also recommends circulation of 180 F 82 C water Wher...

Page 9: ...NAIR CONTAMINATIONTHATMAYBE HAZARDOUS TOLIFE SUCHACONDITIONOFTENWILLRESULTINAYELLOW LUMINOUSBURNERFLAME CAUSINGCARBONINGORSOOTING OF THE COMBUSTION CHAMBER BURNERS AND FLUE TUBES AND CREATESARISK OFAS...

Page 10: ...S OF FIRE AND ASPHYXIATION Heater must be protected from freezing downdrafts Remove all soot or other obstructions from the chimney that will retard a free draft Type B venting is recommended with the...

Page 11: ...BTR C 180 197 198 199 200 Input 180 000 190 000 199 000 Btuh Total Vent Height Feet Draft Hood 6 6 8 10 15 20 30 50 100 Input Btuh Rise Vent Connector Diameter in inches 180 000 1 Ft 8 8 8 8 8 7 7 7...

Page 12: ...10 10 10 8 8 8 Number of Combined Input Heaters in Thousands of Btuh Manifold Common Vent Diameter 2 610 14 14 12 12 12 10 10 10 3 915 16 16 16 14 14 12 12 12 4 1220 18 18 16 16 16 14 14 12 MODEL BTR...

Page 13: ...used in conjunction with this appliance shall also be installed with a properly sized rated and approved combination temperature ANSI and pressure ASME relief valve s WARNING THE PURPOSE OF RELIEF VA...

Page 14: ...AND CERTIFIED FOR GAS SERVICE BEFOREATTACHING THE GAS LINE BE SURE THATALL GAS PIPE IS CLEAN ON THE INSIDE TO TRAP ANY DIRT OR FOREIGN MATERIAL IN THE GAS SUPPLY LINE A DIRT LEG SOMETIMES CALLED SEDIM...

Page 15: ...SUPPLY PRESSURE TESTING EXCEEDING 1 2 PSIG 3 5 kPa GAS SUPPLY LINE MUSTBE CAPPED WHEN DISCONNECTED FROM THE HEATER FOR TEST PRESSURES OF 1 2 PSIG 3 5 kPa OR LESS THE APPLIANCE NEED NOT BE DISCONNECTED...

Page 16: ...ULD NOT EXCEED SAFE USE TEMPERATURE AT FIXTURES SEE WATER TEMPERATURE CONTROLWARNING ON PAGE 27 IF HIGHER PREHEAT TEMPERATURESARE NECESSARY TO OBTAINADEQUATE BOOSTER OUTPUT ADD AN ANTI SCALD VALVE FOR...

Page 17: ...MUST BE CLOSED ON DURING THERINSEOPERATIONANDOPEN OFF WHENDISHWASHER IS NOT OPERATING OR WHEN ON LONG STANDBY NOTE 2 INSTALL LINE TEMPERATURE CONTROL IN AN UNINSULATED TEE BEYOND THE DISHWASHING MACH...

Page 18: ...wn in the installation diagrams on the following pages are typical TWO TEMPERATURE TWO HEATERS ONE PRE HEATER ONE BOOSTER HEATER WITH OR WITHOUT BUILDING RECIRCULATION The discharge opening of the tem...

Page 19: ...OTE 3 ADJUST PLUG COCK SO THE SANITIZING LOOP FLOW RATE DOES NOT CAUSE UNNECESSARY TURBULENCE IN THE TANK PIPE RELIEF VALVE TO OPEN DRAIN INSTALL IN ACCORDANCE WITH LOCAL CODES CIRCULATING RETURN LINE...

Page 20: ...ERS WITH MIXING VALVE TWO PRE HEATERS WITH BOOSTER HEATER DANGER TEMPERATURE SETTING SHOULD NOT EXCEED SAFE USE TEMPERATURE AT FIXTURES SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 27 IF HIGHER PREHE...

Page 21: ...STER OUTPUT ADD AN ANTI SCALD VALVE FOR HOT WATER SUPPLIED TO FIXTURES PIPE RELIEF VALVE TO OPEN DRAIN WHEN USING AN A O SMITH T 140 200 350 OR 400 STORAGE TANK USE LOWER 3 4 OPENING FOR TANK TEMPERAT...

Page 22: ...OD A BTR MODELS BTRC MODELS 120 69 75 177cm 69 75 177cm 154 73 00 185cm 73 00 185cm 180 67 50 171cm 70 50 179cm 197 75 00 192cm 81 50 207cm 198 75 00 192cm N A 199 67 50 171cm 70 50 179cm 200 72 00 18...

Page 23: ...ete instructions MULTIPLE UNIT INSTALLATIONS For multiple unit installations contact A O Smith Water Products Company Technical Support Center at 1 800 527 1953 In Canada contact A O Smith Enterprises...

Page 24: ...AVOID RISK OF FIRE OR EXPLOSION PURGE DISCHARGE MUST NOT ENTER CONFINEDAREAS OR SPACES WHERE IGNITION CAN OCCUR THE AREA MUST BE WELL VENTILATED AND ALL SOURCES OF IGNITION MUSTBE INACTIVATED OR REMOV...

Page 25: ...25 FOR NATURAL GAS MODELS...

Page 26: ...26 FOR PROPANE GAS MODELS...

Page 27: ...e water temperature is controlled by a thermostat Fig 3 which has two sensing elements One sensor is located near the top of the tank and the other is near the center The thermostat is set in the lowe...

Page 28: ...MAINTENANCE CHECK THE PILOT At least once a year check the pilot burner fig 15 and the main burner fig 16 for proper operation Refer to the following pilot and main burner sections PILOT BURNER For a...

Page 29: ...pressure gauge or a manometer to the gauge port and refer to Table 5 for correct manifold pressure 2 Use this formula to clock the meter Be sure that other gas consuming appliances are not operating...

Page 30: ...he heater and replacement of the factory installed magnesium anodes with aluminum anodes may correct the condition Occasionally water softener companies recommend removal of heater anodes for odor rea...

Page 31: ...screws securing tank cleanout plate and remove plate 4 Remove lime scale or sediment using care not to damage the glass lining 5 Inspect cleanout plate gasket if new gasket is required replace with A...

Page 32: ...e replaced TROUBLESHOOTING IGNITION MODULE SYSTEM Before calling your service agent the following checklist should be examined to eliminate obvious problems from those requiring replacement or servici...

Page 33: ...Blown fuse or circuit breaker 5 Disconnect switch off 6 Harness not plugged into appliance receptacle A FLUE DAMPER OPEN OR OPENING Unit is calling for heat and damper disc should be in vertical posi...

Page 34: ...slower Call serviceman Check gas input If incorrect adjust gas pressure or replace main burner orifice Draft hood not installed or Call serviceman Install draft hood or baffles as one or more flue ba...

Page 35: ...e heater s and operational at all times The relief valve installed on the heater is not an acceptable method 4 SERVICE AND REPAIR EXPENSES Under the limited warranty the warrantor will provide only a...

Page 36: ...36 500 Tennessee Waltz Parkway Ashland City TN 37015 Phone 800 527 1953 Fax 800 433 2515 www hotwater com...

Reviews: