3. The correct test instruments are:

CO

2

 indicator or 0

2

 analyzer

CO indicator

Stack thermometer

Draft gauge or inclined manometer

U-tube manometer or calibrated 0-10” and 0-35” w.c.
pressure gauge

Combination volt/ammeter.

Suggested safety device test procedures are:

A. While heater is operating, turn valve, main burner and pilot

gas line manual gas cocks to the OFF position.  Burner should
shutdown within 3-4 seconds and lockout on flame failure,
requiring reset of the flame safeguard device.

B. While heater is operating, lower the setting of each of (2)

operating thermostats (one at a time).  During this setting
change, the burner should shutdown when the called for
temperature is less than the temperature indicated on the
thermometer.  Restore the settings to original values and burner
should restart.

Should any of the above operating test fail, replace the involved
component.

MAINTENANCE

GENERAL

Water heater maintenance includes periodic tank flushing and
cleaning, and removal of lime scale.  The power burner should
be inspected and adjusted to maintain proper combustion.  Refer
to the following table. A periodic inspection of the venting system
should be made.  Where used, the water heating system
circulating pump should be oiled.

KEEP APPLIANCE AREA CLEAR AND FREE FROM
COMBUSTIBLE MATERIALS, GASOLINE AND OTHER
FLAMMABLE VAPORS AND LIQUIDS.

FLUSHING

1. Turn off the heater electrical disconnect switch.

• For convenience, the switch on the outside of the control
  compartment can be used.

2. Open the drain valve and allow water to flow until it runs clean.

3. Close the drain valve when finished flushing.

4. Turn on the heater electrical disconnect switch.

MAINTENANCE SCHEDULE

Component

Operation

Interval

Required

Flushing

Monthly

Sediment

Tank

Removal

Semi-Annually

Lime Scale

UN•LIME

®

Removal

As Required

Delimer

Relief Valve

Inspect

Semi-Annually

Power Burner

SAE No. 20

Motor(1)

Inspect

Quarterly

non-detergent

motor oil

Power Burner

Combustion

and Ignition

Inspection

Semi-Annually

test kit &

Device(2)

test

specifications

Main Burner

Check Flame

Annually

Flue Baffle

Pipe(3)

Cleaning

As Required

Wire Brush

Vent System

and Barometric

Inspect

Semi-Annually Draft Gauge

Damper

(1)  If furnished with oiling provisions
(2)  If flange gasket is damaged, it must be repaired.
(3) COF and COBT Only.

DRAINING

The heater must be drained if it is to be shut down or exposed to
freezing temperatures.  Maintenance and service procedures may
also require draining the heater.

1. Tun off the heater electrical disconnect switch.

2. Close the cold water inlet valve to heater.

3. Open a nearby hot water faucet to vent the system.

4. Open the heater drain valve.

5. If the heater is being drained for an extended shutdown, it is

suggested the drain valve be left open during this period.

•  Follow 

FILLING

 instructions when restoring hot water service

SEDIMENT REMOVAL

Waterborne impurities consist of fine particles of soil and sand
which settle out and form a layer of sediment on the bottom of the
tank.

For convenience, sediment removal and lime scale removal
should be performed at the same time.

LIME SCALE REMOVAL

The amount of calcium (lime) released from water is indirect
proportion to water temperature and usage. The higher the water
temperature or water usage, the more lime deposits are dropped
out of the water. This is the lime scale which forms in pipes, heaters
and on cooking utensils.

Summary of Contents for BTP-140

Page 1: ...tilate the room then call your gas supplier or service agent Keep area clear until a service agent has been called MODELS BTP 140 140 thru 600 2500 INCLUDING BTPD BTPN COF COBT COMMERCIAL GAS OIL AND...

Page 2: ...s Association Labortories 55 Scarsdale Road Don Mills Ontario Canada M3B 2R3 TABLE OF CONTENTS This manual is supplemented by the power burner manual All information including start up and maintenance...

Page 3: ...OW OF COMBUSTION AND VENTILATING AIR ADEQUATE AIR FOR COMBUSTION AND VENTILATION MUST BE PROVIDED FOR SAFE OPERATION LIQUID PETROLEUM MODELS Water heaters for propane or liquefied petroleum gas LPG ar...

Page 4: ...rsion from American Insurance Association 85 John Street New York NY 11038 Note Some gas utility companies derate the heating value of the supplied gas at high elevations Your authorized A O Smith Sta...

Page 5: ...T 18 Inches FRONT 18 Inches BACK 0 Inches Back 6 Inches TOP 5 Inches Top 12 Inches LEFT SIDE 0 Inches LEFT SIDE 6 Inches RIGHT SIDE 0 Inches RIGHT SIDE 6 Inches NOTE If a chimney connector is used the...

Page 6: ...RECIRCULATION OF FLUE GASES SUCH CONDITIONS CAUSE SOOTING OR RISKS OF FIRE AND ASPHYXIATION Heater must be protected from freezing downdrafts during shutdown periods Remove all soot or other obstruct...

Page 7: ...LOCATED IN FREEZING AREAS DO NOT THREAD OR CAP THE END OF THIS LINE RESTRICTED OR BLOCKED DISCHARGE WILL DEFEAT THE PURPOSE OF THE VALVE AND IS UNSAFE DISCHARGE LINE SHALL BE INSTALLED TOALLOW COMPLET...

Page 8: ...OM THE SUPPLY PRESSURE TEST BY CLOSING THE MANUAL GAS SHUTOFF VALVE BEFORE PLACING THE HEATER IN OPERATION CHECK FOR GAS LEAKAGE USE SOAP AND WATER SOLUTION OR OTHER MATERIAL ACCEPTABLE FOR THE PURPOS...

Page 9: ...9 TYPICAL WIRE DIAGRAM BTP 270 2 500 KBTUH COF 800 2 500 KBTUH COBT 400 2 500 KBTUH TYPICAL WIRE DIAGRAM BTP 140 255 KBTUH...

Page 10: ...10 TYPICAL WIRE DIAGRAM COF 140 720 KBTUH TYPICAL WIRE DIAGRAM COBT 140 300 KBTUH...

Page 11: ...te to ask the agent any questions which you may have regarding the units start up operation or maintenance A MAINTENANCE section is included at the rear of this manual Any service required should be p...

Page 12: ...finished flushing 4 Turn on the heater electrical disconnect switch MAINTENANCE SCHEDULE Component Operation Interval Required Flushing Monthly Sediment Tank Removal Semi Annually Lime Scale UN LIME...

Page 13: ...ined through your A O Smith dealer or distributor To clean heater through cleanout opening proceed as follows 1 Turn off water inlet valve the heater electrical disconnect switch and open drain valve...

Page 14: ...FIGURE 3 To test gate for operation gently tap gate and observe DO NOT OIL The red solid fuel tabs supplied with the draft regulator must be removed See instructions supplied with Draft Regulator TROU...

Page 15: ...et system it will not permit the expanded hot water volume to equalize pressure with the main The relief valve must release this water or the water heater or plumbing system will be damaged When such...

Page 16: ...ENSES Under the limited warranty the warrantor will provide only a replacement water heater or part thereof The owner is responsible for all other costs Such costs may include but are not limited to a...

Reviews: