Instruction manual BFM
27
is
3.9
Air supply and flue
3.9.1
Introduction
Warning
The installation should be carried out by an authorised installation engineer,
in compliance with general and local regulations
(1.3 "Regulations")
.
The BFM 30, 50 and 80 differ from the BFM 100 and 120 in how the air supply
and chimney flue are connected.
3.9.2
Installing chimney flue components for BFM 30, 50, 80
The BFM-appliances are approved for installation types C13 and C33. The
instruction manual describes these types. For a more detailed explanation,
please contact your supplier or the manufacturer.
Note
We prescribe the use of a concentric roof or wall flue terminal, exclusively of
a type approved for the appliance.
You must fulfil the following requirements:
•
The maximum permissible length of chimney pipe (A+B+C) is 7 metres.
•
The maximum permissible number of 45° or 90° bends is 2.
•
If you are using a horizontal pipe, you must mount it with a minimum run-off
of 5 mm per running metre of pipe towards the appliance!
•
Make sure that the chimney discharges into an area approved for this type
of appliance.
Summary of Contents for BFM - 100
Page 1: ......
Page 2: ......
Page 4: ...4 Instruction manual BFM gis ...
Page 10: ...Introduction 10 Instruction manual BFM 1 gis ...
Page 16: ...Working principle of the appliance 16 Instruction manual BFM 2 gis ...
Page 42: ...Conversion to a different gas category 42 Instruction manual BFM 4 is ...
Page 48: ...Draining 48 Instruction manual BFM 6 gis ...
Page 52: ...Status of the appliance 52 Instruction manual BFM 8 gis ...
Page 54: ...Starting and running 54 Instruction manual BFM 9 gis ...
Page 56: ...Shutting down 56 Instruction manual BFM 10 gis ...
Page 62: ...is Instruction manual BFM 62 ...
Page 72: ...Electrical diagram 72 Instruction manual BFM 14 is ...
Page 74: ...0306 723 4 0 UK Index Instruction manual BFM ...