background image

27

3.  Insert the manifold/burner assembly into the burner 

compartment making sure that the tip of the manifold 
tube engages in the slot of the bracket inside the 
combustion chamber (Figure 29). 

4.  Inspect the door gasket and make sure there is no 

fiberglass insulation between the gasket and the 
combustion chamber.

5.  Replace the two screws, which secure the manifold/

burner assembly door to the combustion chamber 
and tighten securely. Once the manifold/burner 
assembly door is tightened, visually inspect the door 
gasket between the manifold/burner assembly door 
and the combustion chamber for spaces or gaps that 
would prevent a seal. IMPORTANT: Do not operate 
the water heater if the door gasket does not create a 
seal between the manifold door and the combustion 
chamber.

6.  During the following procedure, do not cross-thread 

or apply any thread sealant to any of the fittings listed 

below.  First, reconnect the manifold tubing to the gas 
control valve/thermostat.

7.  Reconnect the flame sense/hot surface igniter wire to 

the gas control valve/thermostat (Figure 24).

8.  Turn gas supply on and refer to the Lighting 

Instructions.

9.  With the burner lit, check the gas control valve/

thermostat supply line, two piece wire connector, and 

manifold tube connections for leaks. Check for leaks by 

brushing on an approved noncorrosive leak detection 

solution. 

IMPORTANT: Do Not splash solution onto 

the electrical connections. 

Bubbles forming indicate 

a leak. Correct any leak found. All leaks must be fixed 
immediately.

10.  Replace the outer door (see item K page 5).

Door Gasket

Viewport

Manifold Tab

Slot

Burner

FIGURE 29.

Removing and Replacing the Gas Control 
Valve/Thermostat                                                             

IMPORTANT: Use only factory authorized replacement 

parts.

Removing the Gas Control Valve/Thermostat:

1.  Set the gas control valve/thermostat to its lowest setting 

by first depressing the COOLER      and HOTTER      

buttons together and hold for 1 second. Then press the 

COOLER      button until the lowest setting appears 

(Figure 21).

2.  Unplug the electrical transformer from the wall outlet.

3.  Turn off the gas supply to the water heater at the 

manual gas shut-off valve. This valve is typically located 

beside the water heater. Note the position of the shut-

off valve in the open/on position then proceed to turn it 

off (Figure 3).

4.  Drain the water heater. Refer to the section of 

“Draining and Flushing” section and follow the 

procedure.

5.  Disconnect the the flame sense/hot surface igniter 

wire, power supply transformer, pressure switch/

fan and display connector wires from the thermostat 

(Figure 24). Disconnect the manifould tube at the 

thermostat (Figure 24).

6.  Refer to “Gas Piping” section (Figure 3) and disconnect 

the ground joint union in the gas piping. Disconnect the 

remaining pipe from the gas control valve/thermostat.

7.  To remove the gas control valve/thermostat, thread a 

correctly sized pipe into the inlet and use it to turn the gas 

control valve/thermostat (counterclockwise.) Do not use 

pipe wrench or equivalent to grip body.  Damage may 

result, causing leaks. Do not insert any sharp objects into 

the inlet or outlet connections. Damage to the gas control 

valve/thermostat may result.

Replacing the Gas Valve:

1.   To replace the gas control valve/thermostat, 

reassemble in reverse order. When replacing the gas 

control valve/ thermostat, thread a correctly sized 

pipe into the inlet and use it to turn the gas valve 

(clockwise.) DO NOT OVER TIGHTEN or damage may 

result. NOTE: Use an approved 

TEFLON

®

 tape or pipe 

compound only on the threaded section of the gas 

control valve/thermostat that screws into the tank. 

2.   Reconnect the gas piping to the gas control valve/

thermostat. NOTE: Use an approved Teflon tape or 

pipe compound on the gas piping connections.

3.   Reconnect the manifold tube, flame sense/hot surface 

igniter wire, power supply transformer, pressure switch/

fan and display connector wires (Figure 24).

4.   Fill the tank completely with water. NOTE: To purge the 

lines of any excess air, keep the hot water faucet open 

for 3 minutes after a constant flow of water is obtained.

5.  Turn on the gas supply and test the gas supply 

connections by brushing on an approved noncorrosive 

leak detection solution. 

IMPORTANT: Do Not splash 

solution onto the electrical connections. 

Bubbles 

forming indicate a leak. Correct any leak found.

6.   Check the operation of the burner by following the 

lighting instructions on the front of the water heater. 

With the burner lit, check the gas control valve/

thermostat supply line, manifold tube connections for 

leaks. 

7.  Verify proper operation and then replace the outer door.
8.  If additional information is required, contact Residential 

Technical Assistance by referencing the phone number on 

the water heater or on the front cover of this manual.

TEFLON

®

 is a registered trademark of E.I. Du Pont De Nemours and Company

Summary of Contents for 315456-004

Page 1: ...the fire department Installation and service must be performed by a qualified installer service agency or the gas supplier WARNING If the information in these instructions is not followed exactly a fi...

Page 2: ...lief Valve 16 17 T P Relief Valve and Pipe Installation 17 Combination Space Heating Potable Water System 17 18 Solar Installation 18 Electrical Connections and Wiring Diagram 18 Important Information...

Page 3: ...ty equivalent to a licensed tradesman in the fields of plumbing air supply venting and gas supply including a thorough understanding of the requirements of the National Fuel Gas Code as it relates to...

Page 4: ...s are available Breathing carbon monoxide can cause brain damage or death Always read and understand instruction manual Fire or Explosion Hazard Do not store or use gasoline or other flammable vapors...

Page 5: ...CODES IMPORTANT WHEN BRUSHING ON AN APPROVED NONCORROSIVE LEAK DETECTION SOLUTION DO NOT SPLASH SOLUTION ONTO ELECTRICAL CON NECTIONS SEE PAGE 27 M N A L B P D E Q F G DISCHARGE PIPE DO NOT CAP OR PLU...

Page 6: ...future users of this water heater will need it for future reference Service to the FVIR System should only be performed by a qualified technician Examples of a qualified technician include licensed pl...

Page 7: ...ignition sources have been extinguished Fire or Explosion Hazard WARNING Read instruction manual before installing using or servicing water heater Improper use may result in fire or explosion Maintain...

Page 8: ...ply wholesalers and retailers and detect and react to leakage in various ways Sensors mounted in the metal drain pan that trigger an alarm or turn off the incoming water to the water heater when water...

Page 9: ...PPLY WARNING Use a new CSA approved gas supply line Install a shut off valve Do not connect a natural gas water heater to an L P gas supply Do not connect an L P gas water heater to a natural gas supp...

Page 10: ...these instructions can result in death explosion or carbon monoxide poisoning Explosion Hazard Gas Pipe Capacity Table WARNING Explosion Hazard Gas leaks can not always be detected by smell Gas suppl...

Page 11: ...y a qualified technician using the installation instructions Examples of a qualified technican include gas technicians authorized gas company personel and authorized service persons Failure to so do c...

Page 12: ...for ventilation and combustion air supply openings consideration must be given to the blocking effect of protection louvers grilles and screens These devices can reduce airflow which in turn may requi...

Page 13: ...ing the manufacturer s instructions and local codes rules or regulations IMPORTANT If you lack the necessary skills required to properly install this venting system you should not proceed but get help...

Page 14: ...prior to any elbow in the vent system IMPORTANT Existing vent systems must be inspected for obstructions corrosion and proper installation Chimney Connection IMPORTANT Before connecting a vent to a c...

Page 15: ...he water heater and be easily accessible Know the location of this valve and how to shut off the water to the heater 6 A temperature and pressure relief valve must be installed in the opening marked T...

Page 16: ...or other chemicals must not be used Chemicals that may contaminate the potable water supply must not be added to the piping system Closed System Thermal Expansion As water is heated it expands thermal...

Page 17: ...ed into the T P valve discharge opening per the instructions manual 4 Locate the hot water outlet cold water inlet pipes to the water heater 5 Locate the slit running the length of a section of pipe i...

Page 18: ...tions for leaks Open the nearest hot water faucet and let it run for three 3 minutes to purge the water lines of air and sediment and to ensure complete filling of the tank The Electrical power may th...

Page 19: ...se review the following checklist and make any required installation upgrades or changes Questions Contact Residential Technical Assistance by referencing the phone number on the front of the Installa...

Page 20: ...performed 3 Set the ON OFF switch on the gas control to the OFF postition 2 6 This appliance is equipped with a device which automatically lights the burner DO NOT TRY TO LIGHT THE BURNER BY HAND This...

Page 21: ...code 8 page 31 FIGURE 17 SEQUENCE OF OPERATION System will verify pressure switch operation and start a 5 second pre purge then air intake fan will turn off Ignitor will start a 12 second warm up peri...

Page 22: ...hermostat see Figures 20 and 21 Using the lowest hot water temperature that meets your needs will also provide the most energy efficient operation of the water heater Never allow small children to use...

Page 23: ...the water heater cannot be used until the gas control valve thermostat is replaced by a qualified technician Contact your local dealer for service information losses and may satisfy your normal hot wa...

Page 24: ...s To drain the tank perform the following steps 1 Turn off the gas to the water heater at the manual gas shut off valve and turn off the electrical power to the gas control thermostat valve 2 Open a n...

Page 25: ...Manifold Burner Assembly 1 Turn off the gas supply to the water heater at the manual gas shut off valve This valve is typically located beside the water heater Note the position of the shut off valve...

Page 26: ...dirt it may be necessary to check the air intake chamber screen more frequently 2 Use a vacuum cleaner with a hose attachment to remove any dust or debris that may have accumulated on the screen FIGU...

Page 27: ...eater Refer to the section of Draining and Flushing section and follow the procedure 5 Disconnect the the flame sense hot surface igniter wire power supply transformer pressure switch fan and display...

Page 28: ...PERATURE REGULATION section BURNER FLAME YELLOW LAZY 1 Dirt in burner ports 2 Combustion air path restricted 3 Not enough dilution air for proper com bustion 4 Main burner line clogged 5 Obstruction i...

Page 29: ...MATION SOOTING 1 Insufficient secondary air 2 Low gas pressure 3 Water heater flue or vent system blocked 4 Thermostat not functioning properly 5 Heater installed in a confined area 6 Burner flame yel...

Page 30: ...ure supply and manifold gas pressures are within requirements in the installation manual Manifold gas pressure is non adjustable if pressure is off by more than 0 3 W C 75 Pa replace the lower control...

Page 31: ...power for 10 seconds and then back on If this error code will not clear and the ignitor resistance is within specifications replace the lower control 9 FV SENSE Flashing Flammable Vapor Sensor has det...

Page 32: ...control must be replaced 15 All Segments Flashing The self diagnostic check has detected one or both of the temperature adjustment buttons are stuck 1 Press and release each of the temperature adjustm...

Page 33: ...DURING TRIAL FOR IGNITION IGNITOR TURNS OFF YES NO IS FLAME SENSE LOST IS REQUEST FOR HEAT SATISFIED GAS VALVE OFF COMBUSTION FAN OFF AFTER POST PURGE DELAY GAS VALVE CLOSES LESS THAN 3 TRIES FOR IGN...

Page 34: ...w Retainer Clip 16 Manifold Door Gasket 17 Viewport Assembly 18 FV Sensor 19 Outer Door 20 Electrical Transformer 21 Pressure Switch REPAIR PARTS ILLUSTRATION LEGEND Special anode rod see Anode Rod Wa...

Page 35: ...assembly which contains the manifold tube gasket manifold door manifold component block with retainer clip and flame sense hot surface igniter assembly Natural Gas Item 15 Contains manifold component...

Page 36: ...36 NOTES...

Page 37: ...37 NOTES...

Page 38: ...38 NOTES...

Page 39: ...niques for residential water heaters bearing a rating plate which has not been altered defaced or removed except as required by the warrantor used in an open system or in a closed system with a proper...

Page 40: ...M DOES NOT CONSTITUTE PROOF OF PURCHASE OR PROOF OF INSTALLATION DISCLAIMERS NO EXPRESSED WARRANTY HAS BEEN OR WILL BE MADE ON BEHALF OF THE WARRANTOR WITH RESPECT TO THE MERCHANTABILITY OF THE HEATER...

Reviews: