  Ductwork is the same cross-sectional area as the 

openings.

Vent Pipe System

Check for proper drafting at the water heater draft hood. 

Refer to the “Checking the Draft” section of this manual for 

the test procedure. If the procedure shows insufficient draft 

is present, please check the following.

  Draft hood properly installed.

  Vent connectors securely fastened with screws and 

supported properly to maintain six inch clearance.

  Vent connector made of approved material and sized 

correctly.

  Vent pipe system installed according to all local and 

state codes or, in the absence of local and state codes, 

the “National Fuel Gas Code”, ANSI Z223.1(NFPA 

54)-current edition.

  Flue baffle properly positioned in the flue tube.

  Check the vent system for restrictions/obstructions 

and check the vent termination height.  Refer to the 

“Combustion Air and Ventilation” section of this water 

heater manual for specific requirements.

 

Recheck for sufficient combustion air supply.

Water System Piping

  Temperature and pressure relief valve properly installed 

with a discharge line run to an open drain and protected 

from freezing.

  All piping properly installed and free of leaks.

  Heater completely filled with water.

  Closed system pressure build-up devices installed.

  Mixing valve (when applicable) installed per 

manufacturer’s instructions (See Water Temperature 

Regulation section).

Gas Supply and Piping

  Gas type is the same as that listed on the water heater 

rating plate.

  Gas line equipped with shut-off valve, union, and  drip 

leg.

  Use pipe joint compound or teflon tape marked as being 

resistant to the action of petroleum gases.

  Adequate pipe size and approved pipe material.

  An approved noncorrosive leak detection solution used 

to check all connections and fittings for possible gas 

leaks. Correct any leak found.

Electrical Supply

  Water heater to be located as close as possible to a 

120

VAC

 

outlet (extension cord is 

not

 allowed).

  Electrical supply installed according to all local and 

state codes or, in the absence of local and state codes, 

the “National Electrical Code”, ANSI/NFPS 70 current 

edition.

IMPORTANT INFORMATION ABOUT THIS WATER HEATER

This gas water heater was manufactured to voluntary safety standards to reduce the likelihood of a flammable vapor 

ignition incident. The new technology used in meeting these standards makes this product more sensitive to installation 

errors. Please review the following checklist and make any required installation upgrades or changes.  

Questions? Contact Residential Technical Assistance by referencing the phone number on the front of the Installation 

Instructions and Use & Care Guide.

Installation Checklist                                                  

Water Heater Location

Water heater location is important and can affect system 

performance. Please check the following:

  Installation area free of corrosive elements and 

flammable materials.

  Centrally located with the water piping system (For new 

installations). Located as close to the gas piping, vent 

pipe system and 120VAC outlet as possible.

  Located indoors and in a vertical position. Protected 

from freezing temperatures.

  Proper clearances from combustible surfaces 

maintained and not installed directly on a carpeted floor.

  Provisions made to protect the area from water damage. 

Metal drain pan installed and piped to an adequate 

drain.

  Sufficient room to service the water heater. See 

Clearances and Accessibility section of this manual.

  Water heater not located near an air moving device.

  Is the installed environment dirty (excessive amounts 

of lint, dirt, dust, etc.)?  If so, the air intake chamber 

louvers located on the side of the water heater 

will need to be cleaned periodically.  Refer to the 

maintenance section of your water heater’s manual 

for information on cleaning the “Air Intake Chamber 

Louvers”. 

Combustion Air Supply and Ventilation

Check for sufficient combustion air supply.  Insufficient air 

for the combustion of gas will result in a inferior burner 

flame “yellow-lazy”, thereby allowing smoking and carbon 

formation (sooting) to build up in the combustion chamber.
Is the water heater installed in a closet or other small, 

enclosed space? If so:

  Are there openings for make-up air to enter and exit 

the room/area? 

 

Are the openings of sufficient size?  Remember, if 

there are other gas-fired or air-consuming appliances 

in the same room, you need more make-up air.  Refer 

to the Location Requirements section of this water 

heater manual for specific requirements.

Fresh air not taken from areas that contain negative 

pressure producing devices such as exhaust fans, dryers, 

fireplaces, etc.

   Is there a furnace/air handler in the same room space 

as the water heater?  If so, has a return air duct system 

been attached that exits the room? If so, check for 

leaks on the air duct system. If no air duct system is 

present, correct immediately by contacting a local 

Heating, Ventilation, Air-Conditioning & Refrigeration 

(HVAC-R) authorized service provider. 

  Fresh air supply free of corrosive elements and 

flammable vapors.

Summary of Contents for 315456-004

Page 1: ...the fire department Installation and service must be performed by a qualified installer service agency or the gas supplier WARNING If the information in these instructions is not followed exactly a fi...

Page 2: ...lief Valve 16 17 T P Relief Valve and Pipe Installation 17 Combination Space Heating Potable Water System 17 18 Solar Installation 18 Electrical Connections and Wiring Diagram 18 Important Information...

Page 3: ...ty equivalent to a licensed tradesman in the fields of plumbing air supply venting and gas supply including a thorough understanding of the requirements of the National Fuel Gas Code as it relates to...

Page 4: ...s are available Breathing carbon monoxide can cause brain damage or death Always read and understand instruction manual Fire or Explosion Hazard Do not store or use gasoline or other flammable vapors...

Page 5: ...CODES IMPORTANT WHEN BRUSHING ON AN APPROVED NONCORROSIVE LEAK DETECTION SOLUTION DO NOT SPLASH SOLUTION ONTO ELECTRICAL CON NECTIONS SEE PAGE 27 M N A L B P D E Q F G DISCHARGE PIPE DO NOT CAP OR PLU...

Page 6: ...future users of this water heater will need it for future reference Service to the FVIR System should only be performed by a qualified technician Examples of a qualified technician include licensed pl...

Page 7: ...ignition sources have been extinguished Fire or Explosion Hazard WARNING Read instruction manual before installing using or servicing water heater Improper use may result in fire or explosion Maintain...

Page 8: ...ply wholesalers and retailers and detect and react to leakage in various ways Sensors mounted in the metal drain pan that trigger an alarm or turn off the incoming water to the water heater when water...

Page 9: ...PPLY WARNING Use a new CSA approved gas supply line Install a shut off valve Do not connect a natural gas water heater to an L P gas supply Do not connect an L P gas water heater to a natural gas supp...

Page 10: ...these instructions can result in death explosion or carbon monoxide poisoning Explosion Hazard Gas Pipe Capacity Table WARNING Explosion Hazard Gas leaks can not always be detected by smell Gas suppl...

Page 11: ...y a qualified technician using the installation instructions Examples of a qualified technican include gas technicians authorized gas company personel and authorized service persons Failure to so do c...

Page 12: ...for ventilation and combustion air supply openings consideration must be given to the blocking effect of protection louvers grilles and screens These devices can reduce airflow which in turn may requi...

Page 13: ...ing the manufacturer s instructions and local codes rules or regulations IMPORTANT If you lack the necessary skills required to properly install this venting system you should not proceed but get help...

Page 14: ...prior to any elbow in the vent system IMPORTANT Existing vent systems must be inspected for obstructions corrosion and proper installation Chimney Connection IMPORTANT Before connecting a vent to a c...

Page 15: ...he water heater and be easily accessible Know the location of this valve and how to shut off the water to the heater 6 A temperature and pressure relief valve must be installed in the opening marked T...

Page 16: ...or other chemicals must not be used Chemicals that may contaminate the potable water supply must not be added to the piping system Closed System Thermal Expansion As water is heated it expands thermal...

Page 17: ...ed into the T P valve discharge opening per the instructions manual 4 Locate the hot water outlet cold water inlet pipes to the water heater 5 Locate the slit running the length of a section of pipe i...

Page 18: ...tions for leaks Open the nearest hot water faucet and let it run for three 3 minutes to purge the water lines of air and sediment and to ensure complete filling of the tank The Electrical power may th...

Page 19: ...se review the following checklist and make any required installation upgrades or changes Questions Contact Residential Technical Assistance by referencing the phone number on the front of the Installa...

Page 20: ...performed 3 Set the ON OFF switch on the gas control to the OFF postition 2 6 This appliance is equipped with a device which automatically lights the burner DO NOT TRY TO LIGHT THE BURNER BY HAND This...

Page 21: ...code 8 page 31 FIGURE 17 SEQUENCE OF OPERATION System will verify pressure switch operation and start a 5 second pre purge then air intake fan will turn off Ignitor will start a 12 second warm up peri...

Page 22: ...hermostat see Figures 20 and 21 Using the lowest hot water temperature that meets your needs will also provide the most energy efficient operation of the water heater Never allow small children to use...

Page 23: ...the water heater cannot be used until the gas control valve thermostat is replaced by a qualified technician Contact your local dealer for service information losses and may satisfy your normal hot wa...

Page 24: ...s To drain the tank perform the following steps 1 Turn off the gas to the water heater at the manual gas shut off valve and turn off the electrical power to the gas control thermostat valve 2 Open a n...

Page 25: ...Manifold Burner Assembly 1 Turn off the gas supply to the water heater at the manual gas shut off valve This valve is typically located beside the water heater Note the position of the shut off valve...

Page 26: ...dirt it may be necessary to check the air intake chamber screen more frequently 2 Use a vacuum cleaner with a hose attachment to remove any dust or debris that may have accumulated on the screen FIGU...

Page 27: ...eater Refer to the section of Draining and Flushing section and follow the procedure 5 Disconnect the the flame sense hot surface igniter wire power supply transformer pressure switch fan and display...

Page 28: ...PERATURE REGULATION section BURNER FLAME YELLOW LAZY 1 Dirt in burner ports 2 Combustion air path restricted 3 Not enough dilution air for proper com bustion 4 Main burner line clogged 5 Obstruction i...

Page 29: ...MATION SOOTING 1 Insufficient secondary air 2 Low gas pressure 3 Water heater flue or vent system blocked 4 Thermostat not functioning properly 5 Heater installed in a confined area 6 Burner flame yel...

Page 30: ...ure supply and manifold gas pressures are within requirements in the installation manual Manifold gas pressure is non adjustable if pressure is off by more than 0 3 W C 75 Pa replace the lower control...

Page 31: ...power for 10 seconds and then back on If this error code will not clear and the ignitor resistance is within specifications replace the lower control 9 FV SENSE Flashing Flammable Vapor Sensor has det...

Page 32: ...control must be replaced 15 All Segments Flashing The self diagnostic check has detected one or both of the temperature adjustment buttons are stuck 1 Press and release each of the temperature adjustm...

Page 33: ...DURING TRIAL FOR IGNITION IGNITOR TURNS OFF YES NO IS FLAME SENSE LOST IS REQUEST FOR HEAT SATISFIED GAS VALVE OFF COMBUSTION FAN OFF AFTER POST PURGE DELAY GAS VALVE CLOSES LESS THAN 3 TRIES FOR IGN...

Page 34: ...w Retainer Clip 16 Manifold Door Gasket 17 Viewport Assembly 18 FV Sensor 19 Outer Door 20 Electrical Transformer 21 Pressure Switch REPAIR PARTS ILLUSTRATION LEGEND Special anode rod see Anode Rod Wa...

Page 35: ...assembly which contains the manifold tube gasket manifold door manifold component block with retainer clip and flame sense hot surface igniter assembly Natural Gas Item 15 Contains manifold component...

Page 36: ...36 NOTES...

Page 37: ...37 NOTES...

Page 38: ...38 NOTES...

Page 39: ...niques for residential water heaters bearing a rating plate which has not been altered defaced or removed except as required by the warrantor used in an open system or in a closed system with a proper...

Page 40: ...M DOES NOT CONSTITUTE PROOF OF PURCHASE OR PROOF OF INSTALLATION DISCLAIMERS NO EXPRESSED WARRANTY HAS BEEN OR WILL BE MADE ON BEHALF OF THE WARRANTOR WITH RESPECT TO THE MERCHANTABILITY OF THE HEATER...

Reviews: