background image

14

40 Gal. Water Heater: 

Align the reducer flue over top of 

baffle as shown in Figure 9 (NOTE: reducer flue must be 

installed on 40 gal. water heater above elevation 5,400 Ft. 

(1,646 m) from sea level).

40 & 50 Gal. Water Heaters: 

Align the legs of the draft 

hood with the slots provided. Insert the legs and secure 

the draft hood to the water heater’s top with the four 

screws provided as shown in Figure 9. Do not alter the 

draft hood in any way. If you are replacing an existing 

water heater, be sure to use the draft hood supplied with 

this water heater.

Vent Pipe Size                                                               

It is important that you follow the guidelines in these 

instructions for sizing a vent pipe system. If a transition 

to a larger vent size is required, the vent transition 

connection must be made at the draft hood outlet.

Vent Connectors                                                          

1.  Type B, Double wall, U.L. Listed Vent Pipe.
2.  Single wall Vent Pipe.
Maintain the manufacturer’s specified minimum clearance 

from combustible materials when using type B double wall 

vent pipe.
Vent connectors made of type B, double wall vent pipe 

material may pass through walls or partitions constructed 

of combustible material if the minimum listed clearance is 

maintained.
Maintain a six inch minimum clearance from all 

combustible materials when using single wall vent pipe.
IMPORTANT: Single wall vent pipe cannot be used for 

water heaters located in attics and may not pass through 

attic spaces, crawl spaces or any confined or inaccessible 

location. A single wall metal vent connector cannot pass 

through any interior wall.
When installing a vent connector, please note the following 

(See Figures 10-12):
• 

Install the vent connector avoiding unnecessary bends, 

which create resistance to the flow of vent gases.

• 

Install without dips or sags with an upward slope of at 

least 1/4-inch per foot.

• 

Joints must be fastened by sheet metal screws or other 

approved means. It must be supported to maintain 

clearances and prevent separation of joints and 

damage.

• 

The length of the vent connector cannot exceed 75% of 

the vertical vent height.

• 

The vent connector must be accessible for cleaning, 

inspection, and replacement.

• 

Vent connectors cannot pass through any ceiling, floor, 

firewall, or fire partition.

• 

It is recommended (but not mandatory) that a minimum 

12 inches of vertical vent pipe be installed on the draft 

hood prior to any elbow in the vent system.

IMPORTANT: Existing vent systems must be inspected for 

obstructions, corrosion, and proper installation.

Chimney Connection                                                  

IMPORTANT: Before connecting a vent to a chimney, 

make sure the chimney passageway is clear and free of 

obstructions. The chimney must be cleaned if previously 

used for venting solid fuel appliances or fireplaces. Also 

consult local and state codes for proper chimney sizing 

and application or, in the absence of local and state 

codes, the “National Fuel Gas Code”, ANSI Z223.1(NFPA 

54)-current edition.

• 

The connector must be installed above the extreme 

bottom of the chimney to prevent potentially blocking 

the flue gases.

• 

The connector must be firmly attached and sealed to 

prevent it from falling out.

• 

To aid in removing the connector, a thimble or slip joint 

may be used.

• 

The connector must not extend beyond the inner edge 

of the chimney as it may restrict the space between it 

and the opposite wall of the chimney (Figure 10).

Chimney Termination Vent System

Seal

 

Do Not Extend

Vent Beyond Edge

Of Chimney

Maintain

Clearance*

Support Strap

3 FT.

Minimum

2 FT. Minimum Above Any Object

Within 10 FT. Horizontally

Slope Up

1/4 Inch

Per Foot

Minimum

Vent

Connector

FIGURE 10.

Do not terminate the vent connector in a chimney that has 

not been certified for this purpose. Some local codes may 

prohibit the termination of vent connectors in a masonry 

chimney.

Vertical Exhaust Gas Vent                                          

Vertical exhaust gas vents must be installed with 

U.L. listed type B vent pipe according to the vent 

manufacturer’s instructions and the terms of its listing. 
It must be connected to the water heater’s draft hood by a 

listed vent connector or by directly originating at the draft 

hood opening.
Vertical gas vents must terminate with a listed cap or 

other roof assembly and be installed according to their 

manufacturer’s instructions.
Gas vents must be supported to prevent damage, joint 

separation, and maintain clearances to combustible 

materials (Figures 11 and 12).
IMPORTANT: This gas vent must be terminated in a 

vertical position to facilitate the removal of the burnt gases.
An unused chimney flue or masonry enclosure may be used 

as a passageway for the installation of a gas vent (Figure 12).
Common (combined) venting is allowable with vertical type 

B vent systems and lined masonry chimneys as long as 

proper draft for the water heater is established under all 

conditions of operation. CAUTION: DO NOT common vent 

this water heater with any power vented appliance.

Summary of Contents for 315456-004

Page 1: ...the fire department Installation and service must be performed by a qualified installer service agency or the gas supplier WARNING If the information in these instructions is not followed exactly a fi...

Page 2: ...lief Valve 16 17 T P Relief Valve and Pipe Installation 17 Combination Space Heating Potable Water System 17 18 Solar Installation 18 Electrical Connections and Wiring Diagram 18 Important Information...

Page 3: ...ty equivalent to a licensed tradesman in the fields of plumbing air supply venting and gas supply including a thorough understanding of the requirements of the National Fuel Gas Code as it relates to...

Page 4: ...s are available Breathing carbon monoxide can cause brain damage or death Always read and understand instruction manual Fire or Explosion Hazard Do not store or use gasoline or other flammable vapors...

Page 5: ...CODES IMPORTANT WHEN BRUSHING ON AN APPROVED NONCORROSIVE LEAK DETECTION SOLUTION DO NOT SPLASH SOLUTION ONTO ELECTRICAL CON NECTIONS SEE PAGE 27 M N A L B P D E Q F G DISCHARGE PIPE DO NOT CAP OR PLU...

Page 6: ...future users of this water heater will need it for future reference Service to the FVIR System should only be performed by a qualified technician Examples of a qualified technician include licensed pl...

Page 7: ...ignition sources have been extinguished Fire or Explosion Hazard WARNING Read instruction manual before installing using or servicing water heater Improper use may result in fire or explosion Maintain...

Page 8: ...ply wholesalers and retailers and detect and react to leakage in various ways Sensors mounted in the metal drain pan that trigger an alarm or turn off the incoming water to the water heater when water...

Page 9: ...PPLY WARNING Use a new CSA approved gas supply line Install a shut off valve Do not connect a natural gas water heater to an L P gas supply Do not connect an L P gas water heater to a natural gas supp...

Page 10: ...these instructions can result in death explosion or carbon monoxide poisoning Explosion Hazard Gas Pipe Capacity Table WARNING Explosion Hazard Gas leaks can not always be detected by smell Gas suppl...

Page 11: ...y a qualified technician using the installation instructions Examples of a qualified technican include gas technicians authorized gas company personel and authorized service persons Failure to so do c...

Page 12: ...for ventilation and combustion air supply openings consideration must be given to the blocking effect of protection louvers grilles and screens These devices can reduce airflow which in turn may requi...

Page 13: ...ing the manufacturer s instructions and local codes rules or regulations IMPORTANT If you lack the necessary skills required to properly install this venting system you should not proceed but get help...

Page 14: ...prior to any elbow in the vent system IMPORTANT Existing vent systems must be inspected for obstructions corrosion and proper installation Chimney Connection IMPORTANT Before connecting a vent to a c...

Page 15: ...he water heater and be easily accessible Know the location of this valve and how to shut off the water to the heater 6 A temperature and pressure relief valve must be installed in the opening marked T...

Page 16: ...or other chemicals must not be used Chemicals that may contaminate the potable water supply must not be added to the piping system Closed System Thermal Expansion As water is heated it expands thermal...

Page 17: ...ed into the T P valve discharge opening per the instructions manual 4 Locate the hot water outlet cold water inlet pipes to the water heater 5 Locate the slit running the length of a section of pipe i...

Page 18: ...tions for leaks Open the nearest hot water faucet and let it run for three 3 minutes to purge the water lines of air and sediment and to ensure complete filling of the tank The Electrical power may th...

Page 19: ...se review the following checklist and make any required installation upgrades or changes Questions Contact Residential Technical Assistance by referencing the phone number on the front of the Installa...

Page 20: ...performed 3 Set the ON OFF switch on the gas control to the OFF postition 2 6 This appliance is equipped with a device which automatically lights the burner DO NOT TRY TO LIGHT THE BURNER BY HAND This...

Page 21: ...code 8 page 31 FIGURE 17 SEQUENCE OF OPERATION System will verify pressure switch operation and start a 5 second pre purge then air intake fan will turn off Ignitor will start a 12 second warm up peri...

Page 22: ...hermostat see Figures 20 and 21 Using the lowest hot water temperature that meets your needs will also provide the most energy efficient operation of the water heater Never allow small children to use...

Page 23: ...the water heater cannot be used until the gas control valve thermostat is replaced by a qualified technician Contact your local dealer for service information losses and may satisfy your normal hot wa...

Page 24: ...s To drain the tank perform the following steps 1 Turn off the gas to the water heater at the manual gas shut off valve and turn off the electrical power to the gas control thermostat valve 2 Open a n...

Page 25: ...Manifold Burner Assembly 1 Turn off the gas supply to the water heater at the manual gas shut off valve This valve is typically located beside the water heater Note the position of the shut off valve...

Page 26: ...dirt it may be necessary to check the air intake chamber screen more frequently 2 Use a vacuum cleaner with a hose attachment to remove any dust or debris that may have accumulated on the screen FIGU...

Page 27: ...eater Refer to the section of Draining and Flushing section and follow the procedure 5 Disconnect the the flame sense hot surface igniter wire power supply transformer pressure switch fan and display...

Page 28: ...PERATURE REGULATION section BURNER FLAME YELLOW LAZY 1 Dirt in burner ports 2 Combustion air path restricted 3 Not enough dilution air for proper com bustion 4 Main burner line clogged 5 Obstruction i...

Page 29: ...MATION SOOTING 1 Insufficient secondary air 2 Low gas pressure 3 Water heater flue or vent system blocked 4 Thermostat not functioning properly 5 Heater installed in a confined area 6 Burner flame yel...

Page 30: ...ure supply and manifold gas pressures are within requirements in the installation manual Manifold gas pressure is non adjustable if pressure is off by more than 0 3 W C 75 Pa replace the lower control...

Page 31: ...power for 10 seconds and then back on If this error code will not clear and the ignitor resistance is within specifications replace the lower control 9 FV SENSE Flashing Flammable Vapor Sensor has det...

Page 32: ...control must be replaced 15 All Segments Flashing The self diagnostic check has detected one or both of the temperature adjustment buttons are stuck 1 Press and release each of the temperature adjustm...

Page 33: ...DURING TRIAL FOR IGNITION IGNITOR TURNS OFF YES NO IS FLAME SENSE LOST IS REQUEST FOR HEAT SATISFIED GAS VALVE OFF COMBUSTION FAN OFF AFTER POST PURGE DELAY GAS VALVE CLOSES LESS THAN 3 TRIES FOR IGN...

Page 34: ...w Retainer Clip 16 Manifold Door Gasket 17 Viewport Assembly 18 FV Sensor 19 Outer Door 20 Electrical Transformer 21 Pressure Switch REPAIR PARTS ILLUSTRATION LEGEND Special anode rod see Anode Rod Wa...

Page 35: ...assembly which contains the manifold tube gasket manifold door manifold component block with retainer clip and flame sense hot surface igniter assembly Natural Gas Item 15 Contains manifold component...

Page 36: ...36 NOTES...

Page 37: ...37 NOTES...

Page 38: ...38 NOTES...

Page 39: ...niques for residential water heaters bearing a rating plate which has not been altered defaced or removed except as required by the warrantor used in an open system or in a closed system with a proper...

Page 40: ...M DOES NOT CONSTITUTE PROOF OF PURCHASE OR PROOF OF INSTALLATION DISCLAIMERS NO EXPRESSED WARRANTY HAS BEEN OR WILL BE MADE ON BEHALF OF THE WARRANTOR WITH RESPECT TO THE MERCHANTABILITY OF THE HEATER...

Reviews: