Pressure  value 

reading  max  or 
min  

Ensure  that  the  pressure  tubes  are  plugged  into 

the  correct  ports  on  the  pressure  sensor.  Ensure 
that  the  exterior  pressure  terminal  is  properly 
sealed 

 the  breach into  the  unit  should  be  filled 

with  the  supplied  foam,  or  with  silicone  if  the 
supplied foam is missing 

No 

pressure 

value 

If there is no differential pressure value displayed 
in the system summary, first use your voltmeter to 

check  that  there  is  a  DC  signal  of  ~5VDC  being 
sent to the controller from the Pressure sensor. If 
there is, check that the Smart Node is powered.  

 

75F TECHNICAL SUPPORT

 

 

If you need more information, please visit www.75f.io/support. Here 
installers will find instructional videos, installation guides, and more. 

You can also call 888.590.8995 x2 if you need technical support.  

Summary of Contents for A/DP2 Series

Page 1: ...olumn 75F solutions can regulate the pressure differential when the Pressure Sensor Package Solution is used in conjunction with a 75F Outside Air Optimization Package PRECAUTIONS Failure to wire devi...

Page 2: ...ackage pressure control is possible SPECIFICATIONS 75F Pressure Controller Supply Voltage 24VAC Input 0 10VDC Operating Environment 41 F 122 F Enclosure Rainproof type 3R non metallic enclosure A DP2...

Page 3: ...on the label pointing upward If the unit must be installed flat there may be a zero shift The shift can be corrected with the zero adjustment located inside the enclosure To adjust the zero both press...

Page 4: ...below Wiring the A DP2 Use 18 3AWG to run power from the 75F controller to the pressure sensor as shown in Fig 3 The power for the A DP2 is internally connected so that the controller will power the A...

Page 5: ...e Smart Node should read default room 1 Press the Right button on the Smart Node until Advertising is displayed 2 2 With the CCU Tablet within 20 of the Smart Node press Pair Pressure Sensor from Setu...

Page 6: ...w tab will appear titled Summary In the Summary tab look at the Pressure Sensor section and check that there are rational values being displayed for the differential pressure Typical differential pres...

Page 7: ...ied foam is missing No pressure value If there is no differential pressure value displayed in the system summary first use your voltmeter to check that there is a DC signal of 5VDC being sent to the c...

Reviews: