Turn  power  off.  18AWG  T-stat  wire  is  recommended.

 

Follow  the 

wiring  diagram  to  wire  the  Smart  Node  and  the  A/DP2  Pressure 
Sensor. 

 

Powering the controller. Use 18/2AWG to run power from the 24VAC 
transformer to the 75F Smart Node as shown below. 

Wiring the A/DP2. Use 18/3AWG to run power from the 75F controller 
to the pressure sensor as shown in Fig.3. The power for the A/DP2 is 

internally  connected  so  that  the  controller  will  power  the  A/DP2 
pressure differential sensor

.

 

 

Low  Pressure  Port  connects  to  outside  and  High  Pressure 
Port  connects  to  inside. 

Using  a  length  of  ¼”

  O.D.

,  0.170”ID 

polyethylene tubing. Push one end over the brass fitting on the A/DP2 

Pickup 

Port

Exterior

Pickup 

Port

Interior

Fig.4

 

Summary of Contents for A/DP2 Series

Page 1: ...olumn 75F solutions can regulate the pressure differential when the Pressure Sensor Package Solution is used in conjunction with a 75F Outside Air Optimization Package PRECAUTIONS Failure to wire devi...

Page 2: ...ackage pressure control is possible SPECIFICATIONS 75F Pressure Controller Supply Voltage 24VAC Input 0 10VDC Operating Environment 41 F 122 F Enclosure Rainproof type 3R non metallic enclosure A DP2...

Page 3: ...on the label pointing upward If the unit must be installed flat there may be a zero shift The shift can be corrected with the zero adjustment located inside the enclosure To adjust the zero both press...

Page 4: ...below Wiring the A DP2 Use 18 3AWG to run power from the 75F controller to the pressure sensor as shown in Fig 3 The power for the A DP2 is internally connected so that the controller will power the A...

Page 5: ...e Smart Node should read default room 1 Press the Right button on the Smart Node until Advertising is displayed 2 2 With the CCU Tablet within 20 of the Smart Node press Pair Pressure Sensor from Setu...

Page 6: ...w tab will appear titled Summary In the Summary tab look at the Pressure Sensor section and check that there are rational values being displayed for the differential pressure Typical differential pres...

Page 7: ...ied foam is missing No pressure value If there is no differential pressure value displayed in the system summary first use your voltmeter to check that there is a DC signal of 5VDC being sent to the c...