www.75f.io       888.590.8995 x2

 

low pressure port and run the other end to the exterior pickup port. 

Cut  to  length  and  push  the  tubing  to  the  barbed  connector  on  the 
pickup port. Using the leftover length of tubing, connect to the high-
pressure port on the A/DP2 and run the length to the interior pickup 
port. 

  

|

 

PAIRING 

 

Pair the Pressure controller

 as a Pressure sensor in System Devices. 

Once power is supplied to the system, the Smart Node should read 
default room.

  

1.

 

Press the Right button on the Smart Node until “Advertising” 

is displayed. 

2.

 

 

 

 

 

2. 

With  the  CCU  Tablet  within  20’  of  the  Smart  Node  press  “Pair 

Pressure  Sensor”  from  Setup  >  Settings  >  System  Devices  > 

Pressure.  
 

3. When the Bluetooth pairing process is complete on the Tablet the 

Pressure  Smart  Node  will  read  only  “Pressure”  until  the  CM  and 

Tablet are reconnected. Now pair other modules or snap the Tablet 

back  onto  the  CM.  The  Pressure  Smart  Node  will  begin 
communicating over the 900Mhz channel. Once communicating over 
long range the Pressure Smart Node will display relevant information.  

 

Fig. 5

 

Summary of Contents for A/DP2 Series

Page 1: ...olumn 75F solutions can regulate the pressure differential when the Pressure Sensor Package Solution is used in conjunction with a 75F Outside Air Optimization Package PRECAUTIONS Failure to wire devi...

Page 2: ...ackage pressure control is possible SPECIFICATIONS 75F Pressure Controller Supply Voltage 24VAC Input 0 10VDC Operating Environment 41 F 122 F Enclosure Rainproof type 3R non metallic enclosure A DP2...

Page 3: ...on the label pointing upward If the unit must be installed flat there may be a zero shift The shift can be corrected with the zero adjustment located inside the enclosure To adjust the zero both press...

Page 4: ...below Wiring the A DP2 Use 18 3AWG to run power from the 75F controller to the pressure sensor as shown in Fig 3 The power for the A DP2 is internally connected so that the controller will power the A...

Page 5: ...e Smart Node should read default room 1 Press the Right button on the Smart Node until Advertising is displayed 2 2 With the CCU Tablet within 20 of the Smart Node press Pair Pressure Sensor from Setu...

Page 6: ...w tab will appear titled Summary In the Summary tab look at the Pressure Sensor section and check that there are rational values being displayed for the differential pressure Typical differential pres...

Page 7: ...ied foam is missing No pressure value If there is no differential pressure value displayed in the system summary first use your voltmeter to check that there is a DC signal of 5VDC being sent to the c...