www.75f.io       888.590.8995 x2

 

 

|

 

CONFIGURATION | CONFIRMATION

 

 
Once paired, ensure that the sensor is reading accurately. To do this 
you will go to the Central Control Unit (CCU), or the 75F installer app 
on your iPhone or Android device to look at the  pressure value. On 
the CCU go to the Zones tab and see the Pressure reading in 

“W.C. 

Check that the value is not maxed out in either direction, +0.25wc or 
-0.25wc.  
 
To look at the summary page on the CCU tap on the 75F logo in the 
upper left 4 times and a new tab will appear titled Summary. 
 
In the Summary tab look at the Pressure  Sensor section and  check 
that  there  are  rational  values  being  displayed  for  the  differential 
pressure. Typical differential pressure values under static conditions 
should  be  0.0 

inches’

  water  column,  +/-  0.05  is  acceptable  under 

static  conditions.  If  there  are  no  values,  check  that  the  Pressure 
Sensor Controller is paired correctly, and check that the connections 
to the sensor are color coded correctly and are firmly plugged in to 
their  terminals.  Hide  the  Summary  tab  again  by  pressing  the  logo 
until it disappears.  

|

 

TROUBLESHOOTING  

No display 

No power to controller. Check voltage to controller 
is 24V. 

PROBLEM 

SOLUTION 

Fig. 6

 

Summary of Contents for A/DP2 Series

Page 1: ...olumn 75F solutions can regulate the pressure differential when the Pressure Sensor Package Solution is used in conjunction with a 75F Outside Air Optimization Package PRECAUTIONS Failure to wire devi...

Page 2: ...ackage pressure control is possible SPECIFICATIONS 75F Pressure Controller Supply Voltage 24VAC Input 0 10VDC Operating Environment 41 F 122 F Enclosure Rainproof type 3R non metallic enclosure A DP2...

Page 3: ...on the label pointing upward If the unit must be installed flat there may be a zero shift The shift can be corrected with the zero adjustment located inside the enclosure To adjust the zero both press...

Page 4: ...below Wiring the A DP2 Use 18 3AWG to run power from the 75F controller to the pressure sensor as shown in Fig 3 The power for the A DP2 is internally connected so that the controller will power the A...

Page 5: ...e Smart Node should read default room 1 Press the Right button on the Smart Node until Advertising is displayed 2 2 With the CCU Tablet within 20 of the Smart Node press Pair Pressure Sensor from Setu...

Page 6: ...w tab will appear titled Summary In the Summary tab look at the Pressure Sensor section and check that there are rational values being displayed for the differential pressure Typical differential pres...

Page 7: ...ied foam is missing No pressure value If there is no differential pressure value displayed in the system summary first use your voltmeter to check that there is a DC signal of 5VDC being sent to the c...

Reviews: