background image

Page 7

Pro-120 controller instructions

at the controller to fall so low that the controller
detects a fault condition and the relay will switch off.

On the 24v versions, use of wire that is too long
(and/or too thin) will cause loss of power but will not
harm the controller although the decoupling
capacitor (see ‘features’ diagram above) may heat
up. Heat will shorten the operating life of capacitors.

Crimp Contacts

You must use fully insulated crimps: the power
connections are close to each other and uninsulated
crimps may short out and cause damage. Best of all
use ‘F type’ crimps with vinyl covers. 4QD can
supply these pre-crimped only as they require a
special crimp tool.

8.02

Motor wiring

This is not quite so critical as battery wiring: too
long and/or too thin wire will cause a loss of
performance, it will get and will waste battery power
but will not damage the controller. However, wire
which is too thick will do no harm either so we
recommend the same wire for the motor as for the
battery.

8.03

Circuit breaker

A fuse or circuit breaker may be fitted if required.
The main advantage is that it will enable the battery
or motor to be disconnected in the event of an
emergency or for security. A circuit breaker will not
protect the drive in the event of a fault: MOSFETs
fail far faster than a circuit breaker can operate.

This may be fitted in the battery lead as shown: take
care not to increase the wiring length too much.
Also, certain types of breaker can have the same
effect as increased battery lead length. A breaker in
the motor may therefore be best: it will enable you to
quickly disconnect the motor in an emergency. Also
with the motor disconnected, freewheeling becomes
possible. It is also possible to get a battery isolator
switch - these are normally fitted to lorries, buses
and boats to isolate the battery in an emergency - but
this is not required as the Pro-120 has a power relay
which effectively disconnects the battery (except for
a small bleed resistor).

8.04

Battery condition meter.

This should connect between Pins B and F (white
and green on the diagram). White is connected via
the ignition switch to battery positive and green is
always connected via the wiring to the battery
negative.

9 Controls

The mating connector supplied is
suitable only for the correct size of wire.
Acceptable wire sizes are: 

stranded 0.22-0.25mm²
24 AWG (7/32 AWG)

It is an Insulation Displacement
Connector (IDC): 

Do not strip the insulation from the
wires, simply push them into the top part
of the open connector, from the front
(visible in the diagram) and squeeze it
closed in a vice or with suitable parallel
action pliers. As you do so, the tines of the contacts
bite through the insulation to make contact with the
conductors.

You can re-open a closed connector by gently
moving the tabs at the sides of the top cover outward
to disengage the latches while lifting the cover
slightly, one side at a time.

Wire which is too thin will not make good contact. 

Wire which is too thick will damage the tines which
may short to each other

Solid wire will quickly break with use.

Under no circumstances should you solder to the
connector or the circuit board.

A

B

C

D

E

F

Closed

Open

D red:       Max speed (about 7v when ign on)
E blue:      Wiper (0 to Max Speed,  as pot is varied)
F green:    0v (Min speed)

C black:    Reverse (0v = forward, >5v = reverse)

A yellow:  +24v  (V Batt) to Ignition
B white:    Ignition

A B C D E F

1

1

Summary of Contents for Pro-120 Series

Page 1: ...vailable either for 24v operation or for 12v operation Models can also be supplied for 36v and 48v The voltage is marked on the relays Make sure this are correct as 24v relays will not operate from 12...

Page 2: ...and electromagnetic brake driver Many of these features can be disabled if so required The simplest configuration is shown in section 7 However because of the features and versatility of our controll...

Page 3: ...raking may have difficulty in operating as it has to overcharge the battery A similar problem exists if the battery is disconnected or the wiring faulty There are several options as to how the control...

Page 4: ...Reverse Gain Accel MST RAT Decel Expansion connector HPLO Thermal sensor Trickle resistor UVP Brake drive transistor Battery Controls Parking brake Motor Motor Battery A B C D F E A B C RB1 RB2 Revers...

Page 5: ...er won t cause damage unless the unit is connected to the battery when electrolytic corrosion will occur See also section 15 Supply voltage 12v or 24v or 36v or 48v different models Supply current 30m...

Page 6: ...tery connectors the controller feeds current back the battery during braking and if a battery connector falls off when braking this regenerated current can pump up the voltage on the dud battery conne...

Page 7: ...ckly disconnect the motor in an emergency Also with the motor disconnected freewheeling becomes possible It is also possible to get a battery isolator switch these are normally fitted to lorries buses...

Page 8: ...nternal capacitor charging through a bleed resistor before the ignition switch is closed Beware of opening the switch when the motor is running the motor will brake to a halt more or less quickly depe...

Page 9: ...onnections diagram page 7 For variable cutback you could fit a variable resistor Or you could use a switch to enable disable the feature The level at which it works is controlled by the value of the e...

Page 10: ...deceleration rates These are user adjustable and to get best performance from your machine you should adjust them Acceleration ramp This is shown as Accel on the Features diagram It is present to make...

Page 11: ...ink disconnected they will be independent The two motors will perform identically but with independent current limits If two motors are used off one single 200 amp controller then the full 200 amps cu...

Page 12: ...extra holes in the base swarf could get into the controller and this will invalidate any warranty 13 Heat Heatsinking The long time current the controller can give is limited by the build up of heat i...

Page 13: ...Page 13 Pro 120 controller instructions 113 9 181 166 121 118 0 0 3 15 47 8 73 2 A A B B B B 50 60 5 C 126 C...

Page 14: ...ssion capacitor a ceramic type of 10n value is ideal If the motor does not include this you are advised to fit one across the brushes as close as possible to the motor body The controller will work wi...

Page 15: ...amage to the controller is there is an external wiring fault There are three special sections of track which should blow if a major fault occurs in the controls or the brake connected to the 6 pin and...

Page 16: ...the drive MOSFETs cause their drive resistors to burn up a sure sign the MOSFET has failed Relay drop out A flat battery or wiring which is too thin can cause excessive voltage drop If the supply volt...

Reviews: