4B - W4005 BÜHLER ELEVATOR MONITORING SYSTEM R9.6 – 22 May 2020
Page
28
of
48
10.13
Settings Switches
The W4005NV46AI /B has all the adjustable settings available via the two switches on the PCB
–
SW1 is a
rotary switch and SW2 is a DIP switch. Please see Figure
for the location of the two switches.
Note:
The W4005NV46AI /B unit will only read the switch states during
power up
. If any changes to the
settings are needed, then the unit must be powered down, the switch states changed and then the
W4005NV46AI /B can be powered up again and the new settings will take effect.
10.13.1.
Rotary Switch (SW1)
SW1 rotary switch is used to configure the W4005NV46AI /B controller temperature alarm level. See Table
12 below.
Switch Position
Alarm ⁰
C
0
55
1
60 - Default
2
65
3
70
4
75
5
80
6
85
7
90
Table 12 – SW1 Temperature Alarm Levels
SW1 – Rotary Switch
SW2 – DIP Switch
Figure 18 – W4005N Switch Locations