FINESSE
|
VCF
AIR CURTAINS
LUFTSCHLEIER
58
HAUPTTEILE
Aufhängungen
Anschluss Wasserheizelement ¾“
Stecker Stromversorgungskabel
Stromversorgungsanschlüsse und Position der
Sicherungen
Buchse für Steuerungsmodul
Vordere Einlassabdeckung
Auslassgitter
MAIN PARTS
Suspension holders
Water coil connection ¾“
Power supply cable plug
Power supply connectors and fusse location
Control modul socket
Inlet face cover
Outlet grid
4
5
4. DIMENSIONS
594,6
299,3
304,1
25
596,5
638,5
25
0
A
B
C
5. TECHNICAL PARAMETERS
*The distance at which the average velocity of the air current flow drops to 2m/s.For optimal conditions and maximum
performance of the equipment.
** Acoustic pressure at a distance of 3 m from the curtain.
*** With water temperature gradient of 90º/70° C and temperature of suctioned air at +18°C
Type
Spacing of installation
holes A [mm]
Width B [mm]
Width of cover C
(mm)
VCF-x-100-x-...
1085
1124,1
1166,1
VCF-x-150-x-...
1585
1624,1
1666,1
VCF-x-200-x-...
2085
2124,1
2166,1
VCF-x-250-x-...
2465
2504,1
2546,1
Type
Max.
height
doors
[mm]
Air
output
[m3/h]
Noise*
[dB(A)]
Heater
output
[kW]
Heater
power
supply
[V/A]
Fan power
supply
[V/A]
Weight
[kg]
VCF-B-100-E-...
VCF-B-150-E-...
VCF-B-200-E-...
VCF-B-250-E-...
VCF-B-100-V-...
VCF-B-150-V-...
VCF-B-200-V-...
VCF-B-250-V-...
2250
3230
4360
5300
2140
3100
4280
5140
57,9
60,2
61,2
62,8
57,5
59,6
61
62,5
9,61
15,48
20,15
25,73
24,77**
38,77**
52,61**
62,29**
400/15,50
400/25,21
400/31,38
400/41,16
-
-
-
-
230/2,20
230/3,30
230/4,44
230/5,41
230/2,24
230/3,33
230/4,34
230/5,43
39,5
54,5
71
85
41
56
73
87
4
Air curtain dimensions
Abmessungen des Luftschleiers
4
5
3. MAIN PARTS
1
2
3
4
5
6
7
Suspension holders
Water coil connection ¾“
Power supply cable plug
Power supply connectors and fusse location
Control modul socket
Inlet face cover
Outlet grid
1
4
5
7
2
6
3
Summary of Contents for BASIC Series
Page 1: ...AIR CURTAINS LUFTSCHLEIER 19...
Page 82: ...INDESSE VCIN AIR CURTAINS LUFTSCHLEIER...
Page 97: ...INTRODUCTION VORWORT...