9. REMOVING FAULTS
ATTENTION!
● Before starting maintenance and repair work,
the unit must be disconnected from the power
source and the supply voltage must be locked,
service switch must be in the position 0 (off).
● Do not start repairs, if you are not sure or un
-
familar with the exact procedure. Contact an
authorized service technician!!!
TECHNICAL DATA
● A fault is usually indicated by a message on the
display, see the table below.
Description
Unit's be-
haviour
Likely problem
Solution
4 – Supply fan
error
Unit is not
working
Overheated fan or defect on
thermal contact of inlet fan
Determine the cause of the overheating (defecti-
ve bearing, short-circuit...) or replace the motor.
5 – Exhaust fan
error
Unit is not
working
Overheated fan or defect on
thermal contact of inlet fan
Determine the cause of the overheating (defecti-
ve bearing, short-circuit...) or replace the motor.
6 – Inlet filter
clogged
Unit is venti-
lating
Clogged filter
Check the condition of the filter, or replace it. If
the unit does not have a pressure sensor for the
filter, RESET the clogged filter according to the
manual.
7 – Exhaust
filter clogged
Unit is venti-
lating
Clogged filter
Check the condition of the filter, or replace it. If
the unit does not have a pressure sensor for the
filter, RESET the clogged filter according to the
manual.
8 - Failure in
preheating 1
Unit is venti-
lating
Overheated electric ex-
changer or damaged sensor
Open the exchanger ther-
mostat.
Check that air can flow freely through the unit,
electric heat exchanger is not cooling sufficient
-
ly. Check the safety thermostat on the electric
preheating for damages.
9 - Failure in
exchanger 1
Unit is venti-
lating
Overheated electric ex-
changer or damaged sensor
Open the exchanger ther-
mostat.
Check that air can flow freely through the unit,
electric heat exchanger is not cooling sufficient
-
ly. Check the safety thermostat on the electric
reheating for damages.
10 - Failure in
exchanger 2
Unit is venti-
lating
Overheated electric ex-
changer or damaged sensor
Open the exchanger ther-
mostat.
Check that air can flow freely through the unit,
electric heat exchanger is not cooling sufficient
-
ly. Check the safety thermostat on the electric
reheating for damages.
11 - Failure in
preheating 1
Unit is venti-
lating
Overheated electric ex-
changer or damaged sensor
Open the exchanger ther-
mostat.
Check that air can flow freely through the unit,
electric heat exchanger is not cooling sufficient
-
ly. Check the safety thermostat on the electric
preheating for damages.