14
Register
Address
Coil /
Discrete
Address
Read Only
(RO) or
Read/Write
(RW)
Description
22
RW
Disable Snore Stop.
23
RW
Disable (Pause) Timer Start.
3
-
-
Unused
4
-
-
Unused
5
-
RO
Discrete Status Values
LSB
65
RO
Low Float / Stop Input is active.
66
RO
High Float / Start Input is active.
67
RO
Pump Run Relay is On.
68
RO
Alarm Relay is On. (An alarm is active.)
69
RO
Remote Configuration Mode is active.
70
RO
Pump is Snoring.
71
RO
AIN 1 / CT Input is too high.
72
RO
AIN 1 / CT Input is too low.
73
RO
Pump has failed to run.
74
-
Unused
75
-
Unused
76
-
Unused
77
RO
Active Alarms
Alarm for Analog Input (CT Input) low is active.
78
RO
Alarm for Low Float Active.
79
RO
Alarm for High Float Active.
MSB
80
RO
Alarm for Pump Fails to Run. Pump Run Relay Active, but no current was detected.
6
-
-
Unused
7
-
-
Unused
8
-
-
Unused
9
-
RO
Pump Control State:
0: Initial State
1: Pump Pausing (waiting for Pause Timer to expire)
2: Pump Running
3: Low Level active (Pump Stopped)
4: High Level active (Pump Running)
5: Pump is pausing to flush pump.
6: Pump is starting (Pump not yet running.)
10
-
RO
Pump Current. Percentage with 1 decimal place. e.g. 125 = 12.5%
11
-
RO
Pump Stop Current (Snore Setpoint). . Percentage with 1 decimal place. E.g. 125 =
12.5%. Note: Read Only. See Register 23 for the actual setpoint.
12
-
RO
The Duration of this pump run:
Hours
13
-
RO
Minutes
14
-
RO
Seconds
15
-
RO
The Time remaining of the current Pause Timer:
Hours
16
-
RO
Minutes
17
-
RO
Seconds
18
-
RW
Settings / Configuration (Remote Configuration Mode Only.)
IMPORTANT: To save changes to these settings, set coil 4 (see above).
The Pump Run Time Target Setting:
… Hours
19
-
RW
… Minutes
20
-
RW
… Seconds