12
12.
Reference
DIP Switches
Current Range
SW
1
2
Setting
Off
Off
100% (default)
Off
On
50%
On
Off
25%
On
On
12.5%
Pump Run Time Target
SW
3
4
5
Setting
Off
Off
Off
3 min
Off
Off
On
5 min (default)
Off
On
Off
8 min
Off
On
On
15 min
On
Off
Off
30 min
On
Off
On
1 h
On
On
Off
2 h
On
On
On
4 h
Alarm Relay Activates for …
SW
Setting
6
AIN (CT) Fault
7
Stop / Low Float
8
Start / High Float
9
Fail to Run (Low Current)
On = Activates for this condition. Default= Off,Off,Off,Off
Stop / Low Float Invert
SW
10
Setting
Off
Closed = Low (default)
On
Open = Low
Current Window (%)
SW
Setting
11
On: +16%
12
On: +8%
13
On: +4%
14
On: +2%
Default = Off,Off,Off,On.
Modes Default = Off,Off
SW
Setting
15
On: Disable Snore Stop
16
On: Disable Timer Start
Current % Display
PA
= PAUSING. Pump is Pausing.
CL
= CLEANING. Pumps is Stopped for a Cleaning flush.
Number = The measured current as a percentage of the
measured range (taking into account the Current Transformer
range configured using the DIP switches as per section 5.1).
Terminals
Power
24VAC
12-24VDC
DC+ / AC
1
DC- / AC (Earth)
2
Earth
3
Pump Run Relay
4
5
Alarm Relay
6
7
Pump Current
CT (4-20mA)
-
8
+
9
Digital Inputs
DIN Common
10
DIN 1: Start / High Float
11
DIN 2: Stop / Low Float
12
DIN 3: Up Pushbutton
13
DIN 4: Down Pushbutton
14
DIN 5: Set Pushbutton
15
DIN 8: Remote Config. Mode
18
No Connection
19-27
Do not use (AIN+ Loop Power)
28
Modbus RTU
(RS485)
A
29
B
30
Earth
31
No Connection
32-36
LED Indicators
Power
On
Power is Present
Flash
Unit starting up.
Run / Pause
On
Pump is Running
Pulse
Flash
Pump is Pausing and will start when
pause timer completes or high float
or start signal activates.
Fast
Flash
Pump Snoring. Pump will stop after
10 seconds of snoring
Slow
Flash
Pump Starting or running a cleaning
cycle.
Stop Input /
Low Float
On
Stop Input / Lo Float Active
Start Input /
High Float
On
Start Input / Hi Float Active
Alarm
Flash
Alarm Present & Alarm Relay Active
Fail to Run
On
Pump previously failed to run.
(Current Not detected when the
pump run relay is active.)
Fast
Flash
Pump is failing to run.
Hi Current
Fast
Flash
CT input too high
Pulse
Flash
CT input is above 100% of range.
Consider adjusting CT measuring
range or using a larger CT.
Lo Current
Fast
Flash
CT input too low.
Pulse Flash = Active for 0.25 secs every second.
Slow Flash = 1Hz Flash. Fast Flash = 2 Hz Flash.