2iB SC10 Installation And User Manual Download Page 12

 

12 
 

12.

 

Reference 

DIP Switches 

Current Range

 

SW 

Setting 

 

Off 

Off 

100% (default) 

 

Off 

On 

50% 

 

On 

Off 

25% 

 

On 

On 

12.5% 

 

Pump Run Time Target

 

SW 

Setting 

 

Off 

Off 

Off 

3 min 

 

Off 

Off 

On 

5 min (default)  

 

Off 

On 

Off 

8 min 

 

Off 

On 

On 

15 min 

 

On 

Off 

Off 

30 min 

 

On 

Off 

On 

1 h 

 

On 

On 

Off 

2 h 

 

On 

On 

On 

4 h 

 

Alarm Relay Activates for …

 

SW 

Setting 

AIN (CT) Fault 

Stop / Low Float 

Start / High Float 

Fail to Run (Low Current) 

On = Activates for this condition. Default= Off,Off,Off,Off

 

 

Stop / Low Float Invert 

SW 

10 

Setting 

 

Off 

Closed = Low (default) 

 

On 

Open = Low 

 

Current Window (%) 

SW 

Setting 

11 

On: +16% 

12 

On: +8% 

13 

On: +4% 

14 

On: +2% 

Default = Off,Off,Off,On. 

 

Modes                                                      Default = Off,Off 

SW 

Setting 

15 

On: Disable Snore Stop 

16 

On: Disable Timer Start 

Current % Display 

PA

 = PAUSING.  Pump is Pausing. 

CL

 = CLEANING. Pumps is Stopped for a Cleaning flush. 

Number = The measured current as a percentage of the 
measured range (taking into account the Current Transformer 
range configured using the DIP switches as per section 5.1). 

Terminals 

Power 
24VAC 
12-24VDC 

DC+ / AC 

DC- / AC (Earth) 

Earth 

Pump Run Relay 

Alarm Relay 

Pump Current 
CT (4-20mA) 

Digital Inputs 

DIN Common 

10 

DIN 1: Start / High Float 

11 

DIN 2: Stop / Low Float 

12 

DIN 3: Up Pushbutton 

13 

DIN 4: Down Pushbutton 

14 

DIN 5: Set Pushbutton 

15 

DIN 8: Remote Config. Mode 

18 

No Connection 

19-27 

Do not use (AIN+ Loop Power) 

28 

Modbus RTU 
(RS485) 

29 

30 

Earth 

31 

No Connection 

32-36 

 

LED Indicators 

Power 

On 

Power is Present 

Flash 

Unit starting up. 

Run / Pause 

On 

Pump is Running 

Pulse 
Flash 

Pump is Pausing and will start when 
pause timer completes or high float 
or start signal activates. 

Fast 
Flash 

Pump Snoring.  Pump will stop after 
10 seconds of snoring 

Slow 
Flash 

Pump Starting or running a cleaning 
cycle. 

Stop Input / 
Low Float 

On 

Stop Input / Lo Float Active 

Start Input / 
High Float 

On 

Start Input / Hi Float Active 

Alarm 

Flash 

Alarm Present & Alarm Relay Active 

Fail to Run 

On 

Pump previously failed to run. 
(Current Not detected when the 
pump run relay is active.) 

Fast 
Flash 

Pump is failing to run. 

Hi Current 

Fast 
Flash 

CT input too high 

Pulse 
Flash 

CT input is above 100% of range.  
Consider adjusting CT measuring 
range or using a larger CT. 

Lo Current 

Fast 
Flash 

CT input too low. 

Pulse Flash = Active for 0.25 secs every second. 
Slow Flash = 1Hz Flash.  Fast Flash = 2 Hz Flash. 

Summary of Contents for SC10

Page 1: ...SC10 Single Pump Controller Installation and User Manual ...

Page 2: ...ations To ensure accuracy and reliability screened twisted pair cable is to be used for connection of the Current Transducer for measuring the pump motor current 3 2 Remote Snoring Setup Controls for Operator Safety The Stop Current Setpoint can be set and adjusted using pushbuttons on the front of the pump starter control panel This enables the pump setup commissioning and setpoint adjustment to ...

Page 3: ...elps clear the impellor and the suction strainer of debris reducing the chance of blockage and cavitation as well as increasing the flow rate and efficiency Start up of the SC10 The SC10 will normally start the pump 30 Seconds after start up The pump will run until a stop condition is reach snoring is detected or the stop low float is activated This pump start will not occur if the stop low float ...

Page 4: ...CT In the circumstance that this isn t achievable there are four current range dip switch selections available 100 50 25 and 12 5 that increases the current percentage display providing full scale set point ranging setting i e if you have a 0 100 CT with a 50 Amp full load current the output is only 4mA to 12mA and the percentage of current displayed will only be 50 by switching dip switch 2 50 on...

Page 5: ...6 7 8 9 on front of SC10 CT Fault diagnostic monitoring of CT Sump Low Sump High Failed to Run pump called to run no current detected 5 5 Stop Low Level Switch Invert If a low level switch is used then the switch contact status needs to be set to normally open or closed Ref DIP Switch 10 on front of SC10 Tip If both the High and Low Level Switches are the same and their contacts close when the flo...

Page 6: ...int Adjustment An additional adjustment method is by using the up and down buttons independently By pushing the up or down button it will adjust the stop current threshold to the user s desired value as a percentage of CT current Note This settings is non volatile It is stored through power cycles of the SC10 6 Display and LED Indication 6 1 Current Display PA PAUSING Pump is Pausing CL CLEANING P...

Page 7: ...nected to terminals 7 and 9 Ensure installed 4 20mA CT is correct range for installed load The pump stops although it is not snoring Ensure the inhibit low float input is not activated Stop current setpoint requires adjustment as it is set too high Adjust the stop current setpoint to a lower value If using the Set functionality during commissioning then adjust the Current Window to a lower value T...

Page 8: ...ides 24VDC drive for CT Operating Temp 0 55 degrees Celsius Run Relay Contact Rating 5 A 48 VAC Resistive 1 5 A 48 VAC Pilot duty AC12 Alarm Contact Rating 5 A 48 VAC Resistive 1 5 A 48 VAC Pilot duty AC12 Dimensions W 106 5mm x H 90 50 mm x D 59mm Material PC ABS Mounting 35mm Din rail mounted Weight 300 g Certification EN 61000 6 3 2007 A1 AC FCC Part 15B 90 5mm ...

Page 9: ...9 9 SC10 Connections See section 12 Reference for terminal identification Figure 1 SC10 Front Panel Figure 2 Connections ...

Page 10: ...el PanelStart Remote Start Start Inputs Stop Inputs 5 Overload Reset Remote Set Point Up Remote Set Point Down Remote Threshold Set DIN Common O L 2 Emergency Stop 2 3 4 5 6 7 8 9 10 11 K1 Pump Run DIN 1 DIN 2 DIN 3 DIN 4 DIN 5 4 20mA 4 20mA 1 6 12 13 14 15 16 17 18 19 20 21 24 VAC A 24 VAC N 22 23 24 25 26 27 28 29 31 32 33 34 35 36 37 38 Ref Line 8 Ref Line 7 Ref Line 23 OL Ref Line 11 24 VAC A ...

Page 11: ...nts in a few different ways Rated Current FLC Amps CT Rating Amps SC10 Current Range At Rated Current SC10 will Display Range DIP Switches SW 1 SW 2 An Example Optimal setup for an 8kW Pump Based on 11 1 above Option 1 As above 8 6 20 100 off off 30 30 of the range really is a bit low It would be best to adjust the range to increase the measurement Option 2 Change the Range Setting on the SC10 8 6...

Page 12: ... Run Relay 4 5 Alarm Relay 6 7 Pump Current CT 4 20mA 8 9 Digital Inputs DIN Common 10 DIN 1 Start High Float 11 DIN 2 Stop Low Float 12 DIN 3 Up Pushbutton 13 DIN 4 Down Pushbutton 14 DIN 5 Set Pushbutton 15 DIN 8 Remote Config Mode 18 No Connection 19 27 Do not use AIN Loop Power 28 Modbus RTU RS485 A 29 B 30 Earth 31 No Connection 32 36 LED Indicators Power On Power is Present Flash Unit starti...

Page 13: ...ses will be ignored Addressing Modbus addresses are indexed from 1 in the following table The address in the Modbus packet is 1 less than that address There is inconsistency between Modbus implementations about whether the addresses start from 0 or 1 so if you are not reading the value that you expect then consider reading the previous or next address Register Address Coil Discrete Address Read On...

Page 14: ...p Fails to Run Pump Run Relay Active but no current was detected 6 Unused 7 Unused 8 Unused 9 RO Pump Control State 0 Initial State 1 Pump Pausing waiting for Pause Timer to expire 2 Pump Running 3 Low Level active Pump Stopped 4 High Level active Pump Running 5 Pump is pausing to flush pump 6 Pump is starting Pump not yet running 10 RO Pump Current Percentage with 1 decimal place e g 125 12 5 11 ...

Page 15: ...llowing conditions are met 1 Redistributions of source code must retain the above copyright notice this list of conditions and the following disclaimer 2 Redistributions in binary form must reproduce the above copyright notice this list of conditions and the following disclaimer in the documentation and or other materials provided with the distribution 3 The name of the author may not be used to e...

Page 16: ...B Pty Ltd 4 Barkala St Wellington Point QLD Australia Tel 61 7 3822 1005 Fax 61 7 3822 1008 support 2ib com au www 2ib com au 2018 2IB Pty Ltd All Rights Reserved SC10 Installation and User Manual V20180709 ...

Reviews: