Problem

Corrective Action

“Status – Good” posted in plumbSMART and faucet actuation 

event data not appearing in plumbSMART (< 2 hours) or 

“Device Not Communicating” warning or severe alert posted in 

plumbSMART for all devices (> 3 hours)

Step 1

Verify gateway Status LED flashes twice every 2 seconds.  If LED 

is OFF or ON solid, power cycle the gateway and wait for no 

more than 5 minutes for unit to initialize and connect.

Step 2

After initialization is finished, LORA LED should turn ON solid 

within an additional minute.

Step 3 

If LORA LED does not turn ON solid and ethernet cable 

connected, contact facility IT administrator to modify port rules 

to allow Zurn gateway to access the internet via local router.  

If gateway model is ETH/LTE, visually verify SIM card is installed 

in designated slot on the side of gateway.  If unit has a SIM card, 

then disconnect ethernet cable and power cycle the gateway 

and wait for unit to initialize and connect.  LORA LED should 

turn ON solid after initialization.

Step 4

If problem still present, move gateway closer to LoRa monitors 

and/or verify gateway mounting, orientation and connections 

comply with requirements listed in Zurn Gateway Installation 

Guide.

Contact Zurn Customer Service at 1.855.ONE.ZURN 

(1.855.663.9876) for assistance with additional troubleshooting 

steps.

Trouble Shooting: Gateway

For further assistance with troubleshooting, visit https://plumbsmart.zurn.com/app/training

Содержание AquaSense Camaya Z6953-XL-W2

Страница 1: ... of the product for his intended use and the purchaser assumes all risk and liability whatever in connection therewith Where permitted by law the implied warranty of merchantability is expressly excluded If the products sold hereunder are consumer products the implied warranty of merchantability is limited to a period of three years and shall be limited solely to the replacement of the defective g...

Страница 2: ...ce to radio communications However there is no guarantee that interference will not occur in a particular installation If this equipment does cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the following measures Reorient or relocate the receiving ante...

Страница 3: ...nd finish Operating Water Pressure 10 125 psi Operational Water Temperature 33 F to 140 F 1 C to 60 C Aerator 0 5 GPM Vandal Resistant Standard Important Safety Information Installer is responsible for ensuring the product is installed and conforms to all plumbing codes and ordinances Do not convert or modify this Zurn product yourself All warranties will be voided Water supply lines must be sized...

Страница 4: ... Gasket Aerator and Key Electronics Box with Solenoid Filter Spout Assembly Required Tools Batteries Batteries AquaSense Package Contents Adjustable Wrench Optional Smooth Jawed Wrench Phillips Head Screwdriver 3 32 M3 Allen Wrenches Filter Shank Mounting Kit Base Gasket Electronics Box with Solenoid Valve Hydrogenerator Y Cable Y Cable ...

Страница 5: ...and or internal control and mixing valve 1 Carefully screw aerator into spout using included tool Take care to not pinch blue o ring 3 Ensure that slot in plastic washer is facing forward Sensor cable should pass through the front of the plastic mounting washer Spout Installation Instructions Z6953 XL W2 Z6956 XL W2 Cover Plate Installation Instructions 1 For faucets with CP4 or CP8 suffix Pass se...

Страница 6: ...lied batteries Close lid and tighten lid screw 4 Connect sensor inline connector to electronics module and hydrogenerator Do not connect cable to the monitor at this step Use AA Lithium Batteries or AAAlkaline batteries but do not mix Lithium with Alkaline Monitor Electronic Module Installation Instructions 3 Connect the hydrogenerator A downstream of electronics module B and filter C to bottom of...

Страница 7: ...mildly warm soapy water and then wipe the device dry with a clean soft towel or cloth Upon cleaning other areas of the restroom be sure the sensor lenses are protected from other cleaning chemicals solvents to prevent potential damages to the sensor and or electronics Care and Cleaning Instructions 6 Tighten electronics module assembly to shank and connect water line s 5 Open battery module using ...

Страница 8: ...ctions Thick walls and reflective surfaces such as metal weaken the signal between the gateway and other devices The LoRa antenna is an omni directional antenna but for best results mount the device so the LoRa antenna is in a vertical position near the top of a wall We recommend conducting a site survey to test the signal strength in different locations before you mount the device Step 4 Mounting...

Страница 9: ...sitivity is configured during pack out but the mode can be changed upon installation to optimize the performance within the sink Sensor sensitivity and sensor detection Modes A B may be tried for various lighting conditions sink materials and shape Switch 7 controls the sensitivity On default is normal sensitivity for most sinks providing max range Off set the sensor to a lower sensitivity level f...

Страница 10: ... enough time to calibrate prior to a user or target trying to initiate activa tion Disconnect the sensor and electronic box cables and wait for 30 seconds Reconnect the cables but allow for another 30 seconds before placing hands or a target within the sensor range You should hear a click of the solenoid once calibration is complete Check if protective film was removed from lens Water does not sto...

Страница 11: ...R sensor and Faucet actuator electronics Restore proper electrical connection as needed Step 2 Test activate the faucet If problem persists see Faucet Troubleshooting section in this guide for other steps Status Good posted in plumbSMART and faucet actuates but usage event data not appearing in plumbSMART Charts Step 1 Verify gateway is powered and LoRa Status LED is ON If not apply power per Zurn...

Страница 12: ...acility IT administrator to modify port rules to allow Zurn gateway to access the internet via local router If gateway model is ETH LTE visually verify SIM card is installed in designated slot on the side of gateway If unit has a SIM card then disconnect ethernet cable and power cycle the gateway and wait for unit to initialize and connect LORA LED should turn ON solid after initialization Step 4 ...

Страница 13: ...ect fixture model Verify product image and model number from plumbSMART product page Details tab against model number cited on product literature and packaging If incorrect contact Zurn Custom Service at 1 855 ONE ZURN 1 855 663 9876 for assistance High Daily Faucet Activate Rate posted in plumbSMART Step 1 Verify faucet is not falsely triggering See Faucet Troubleshooting section for appropriate ...

Страница 14: ...To service solenoid use Phillips head screw driver to remove the screws on both sides of the electronics box With screws removed the electronics box can slide off and allow access to the solenoid for service Accessing the Solenoid ...

Страница 15: ...pplied Adapter 3 8 Copper Tube By Others For use with MV Option Mixing Valve Filter and Mixing Valve Installation Control Box Attach adapter or Braided Hose SSH here with MV and TMV 1 options SSH suffix option P6900 12BC Filter Need to hold at pointed area by suitable wrench or by hand while applying torque to the supply hose nut Do not over torque the nut ...

Страница 16: ...it Item 3 P6900 43 Hydrogenerator Assembly Item 4 P6900 HYD Electronics Box with Solenoid Item 5 P6950 XL B L Sensor Inline Connector Item 6 P6950 XL DC Description Product No Smart Connected Faucet Retrofit Kit Item 7 P6900 RK W2 8 Cast Cover Plate w Gasket Item 8 P6900 CP8 4 Cast Cover Plate w Gasket Item 9 P6900 CP4 Single Stainless Supply Hose XL Item 10 P6900 SH XL Stainless Supply Hoses XL I...

Отзывы: