ZURN AquaSense AV ZER Series Скачать руководство пользователя страница 4

FV237   Rev. E   11/9/11
Page 4

Before the supply water is turned on, be sure all stop valves to
the flush valves are closed off tight.  The stop valves can be
opened and closed by using the adjusting screw located at the
center of the stop valve cap 

(T)

 , behind the adjusting screw

cover if already installed.  Stop valve adjustments can only be
made by using the adjusting screw.  

It is not necessary to

remove the stop valve cap when making adjustments.  If for
any reason it becomes necessary to remove the stop valve
cap, be certain the water is shut off at the main supply valve.

10.) 

The ZER flush valves are preset for fixture volume as marked

on the valve cartons.  The valve does not require regulation for
variation in water pressure within its operating range.  To set
the flush valve for proper operation, gradually adjust the stop
valve open, using the adjusting screw, while actuating the valve
until the rate of water flow into the fixture is not excessive, yet is
sufficient to adequately evacuate the waste.  The final setting for
urinals should be such that the fixture will not overflow when the
valve is actuated in succession.  The stop cap screw cover
should be replaced after final adjustments have been made.

APPENDIX A

TO CHANGE ACTIVATION DISTANCE FOR
THE OBJECT LOCK SENSOR

1. Remove battery compartment tray as shown in Step 6.
2. Remove cover and sensor adjustor tool as shown in Step 6.
3. Replace battery compartment in E-Z Flush to activate unit.
4. Press sensor range reset button (the yellow L.E.D. will flash
continuously when it has an object in view for the 10-minute
reset period).
5. Stand at desired activation distance.
6. Use sensor adjustor tool and turn 

Distance Adjustment

Screw 

all the way down and then turn slowly up until 

yellow

L.E.D. 

begins to flash.

7. Ensure Object Lock Sensor is not detecting stall door or wall
by closing door, stepping out of sensor path and making sure

yellow L.E.D. 

is not flashing. If sensor locks onto door or wall,

unit will not flush properly. Shorten activation distance.
8. Remove battery compartment, replace sensor adjustor tool
and cover. Replace battery compartment tray to reactivate E-Z
Flush unit.
9. After 10-minute start-up sequence, the 

yellow L.E.D. 

will flash

only 3 times when a user is in view (after a 5-second delay).

9.) 

When all flush valves are connected to the fixtures and

water pressure is available, it is recommended that the supply
piping be flushed to remove dirt, pipe chips, etc., from system.

Use the following procedure to flush out the supply piping:
A. Remove the main valve body cover .

(O)

B. Remove the working parts from the flush valve 

(P)

 and 

(Q)

(shown in 9b).
C. Replace the plastic cover 

(P)

 and main body cover 

(O)

 with-

out reinstalling the working parts.
D. Open the stop valve by using the stop adjusting screw and
flush out all debris from pipe and connections.
E. Shut stop, open cover, reinstall the working parts, replace
both covers and tighten.
This procedure should also be repeated when the system is
drained for seasonal use, as occurs in athletic fields, recre-
ation parks, etc.

9a

10

9b

Working Parts

New RetroFlush
Diaphragm Kit

T

O

P

Q

Содержание AquaSense AV ZER Series

Страница 1: ...abor charges or any loss injury or damages whatsoever including incidental or consequential damages The sole and exclusive remedy shall be limited to the replacement of the defective goods Before installation and use the purchasershalldeterminethesuitabilityoftheproductforhisintendeduseandthepurchaserassumesallriskandliability whateverinconnectiontherewith Where permitted by law the implied warran...

Страница 2: ...hread sealing compounds should be used on male NPT threads only 2 Prior to inserting the flush valve tailpiece B into stop valve be certain that the O ring seal C is located in O ring seal groove at the end of the tailpiece and the locking nut D and locking snap ring E are located as shown Care should be taken not to damage the O ring when inserting the tailpiece into the stop valve If lubrication...

Страница 3: ...om the E Z Flush unit Load batteries into compartment tray note position of batteries in tray and reinstall battery tray into the E Z Flush unit Secure tray with battery compartment wrench The last three turns of the wrench will activate the E Z Flush unit The E Z Flush System is now operational Your E Z Flush unit comes preset from the factory If special circumstances require adjustment of the ac...

Страница 4: ... unit 4 Press sensor range reset button the yellow L E D will flash continuously when it has an object in view for the 10 minute reset period 5 Stand at desired activation distance 6 Use sensor adjustor tool and turn Distance Adjustment Screw all the way down and then turn slowly up until yellow L E D begins to flash 7 Ensure Object Lock Sensor is not detecting stall door or wall by closing door s...

Страница 5: ...ed Object Lock Sensor range set too close to E Z Flush batteries are dead or water supply is turned off Dirt or debris preventing dia phragm from functioning properly Batteries are dead SOLUTION Remove item covering sensor or adjust Object Lock Sensor activation distance See Appendix B Adjusting the E Z Flush Yellow L E D light will flash only 3 times acknowledging a user is in view after the 10 m...

Страница 6: ...WS Full Flow Closet Kit 4 5 gal flush P6000 ECA FF Ultra Low Flush Urinal Kit 0 125 gal flush P6000 EUA ULF Extra Water Saver Urinal Kit 0 5 gal flush P6000 EUA EWS Low Consumption Urinal Kit 1 0 gal flush P6000 EUA WS1 Water Saving Urinal Kit 1 5 gal flush P6000 EUA WS Full Flush Urinal Kit 3 0 gal flush P6000 EUA FF Repair Parts Inside Parts Product No Urinal Relief Valve Item 12 P6000 EU13 Clos...