Commissioning the field level
LM-CIRIA operating and commissioning manual 2.0 | 06. 2012 | en
85
61 Outputs
The LM-CIRIA control unit allows for outputs to be easily addressed and re-grouped and for their
addresses to be easily checked.
611 Addressing
Path: SERVICE MENU / EXTERNAL / ASSIGN ADDRESS / OUTPUTS
Figure 143:
OUTPUTS
settings level
–
Start point:
OUTPUTS
settings level
=
The room address (
ROOM
) is displayed in the header.
=
On/off key LED illuminates.
Note
•
If there are DALI operating devices in the system without a DALI short address, they will first be au-
tomatically assigned a DALI short address. This automatic addressing occurs before the addressing
described here and is displayed in the touchscreen header as DALI INIT. The automatic assignment
of the DALI short address may take several minutes depending on the number of DALI operating
devices.
1. Select
TYPE
to choose the building service type for the unaddressed output.
=
TYPE
illuminates.
2. Run your finger along the touchring until the desired setting appears.
3. Remove your finger from the touchring.
=
BUS ADDR.
illuminates.
=
An available bus address is displayed.
=
The output to be addressed responds (e.g. luminaire brightens to 100%).
=
The output's production number
(P:)
appears in the header.
4. Run your finger along the touchring until the desired bus address appears.
5. Select
GROUP
.
=
GROUP
illuminates.
6. Run your finger along the touchring until the desired group address appears.
7. Press the on/off key to save the settings.
=
The message
SAVED
briefly appears.
=
Room, group and bus addresses are saved for the output.
=
The next unaddressed output of the same building service type responds.
8. Select
NEXT
if you do not wish to address this output.