background image

Ref.No.

032011-1

 

               

Calculates and Displays Ventilation Rates   

               

Sample Method - Diffusion or flow through (50 ~200 ml/min)   

CO2 & Temperature Specification: 

CO2 Specification

 

Measurement Range 

0-3,000 ppm display 

Display Resolution 

1ppm at 0~1,000ppm; 5ppm at 1,001~2,000ppm; 10ppm at 2,001~3,000ppm 

Accuracy 

0~2,000ppm: ±70 ppm or ±5% of reading, whichever is greater;

 

over 2000ppm: +/-7%   

Repeatability 

±20 ppm @ 400ppm 

Temperature Dependence 

Typ. ±0.2% of reading per °C or ±2 ppm per °C, whichever is greater, referenced to 25°C 

Pressure Dependence 

0.13% of reading per mm Hg (Corrected via user input for altitude) 

Response Time 

About 2min for 63% of step change 

Warm-Up Time 

<60 seconds at 22°C 

Zone LED Display: 

Green:<800ppm; Yellow:800~1200ppm;Red: >1200ppm 

Temperature Specification: 
Temperature Range 

0°C to 50°C (32°F to 122°F) display 

Display Resolution 

0.1°C (0.1°F)                             

 

Display Options 

°C/°F  

Accuracy  

±1°C( ±2°F) When the fan blows to the device directly, the accuracy of temperature is + / -1.5 degC 

Response Time 

20-30 minutes (case must equalize with environment)

 

Operating Conditions: 
Operating Temperature 

0°C to 50°C (32°F to 122°F)

 

Humidity Range 

0 ~ 95% RH non-condensing

 

Storage Conditions: 
Storage Temperature 

-20°C to 60°C( -4°F to 140°F) 

Power Supply:   

Power Supply 

6 VDC from external AC/DC adapter which is included in package (Use specified AC adapter only) 

DC Output voltage   

6 VDC   

AC Input voltage & Frequency   

100 ~ 240 VAC      50 / 60 Hz 

 

Dimension 

 

 

                                                                                                                                                                                                           

Fault Codes & Troubleshooting Guide 

This section includes a list of Frequently Asked Questions for problems you may encounter with the ZG1163 CO2 Monitor. 

Fault Icon 

Description of the fault 

Suggested Actions 

 

The ambient temperature has exceeded the 
operating temperature range 0°C to 50°C (32°F 
to 122°F) 

This error will clear when the temperature returns to the range between 0°C to 
50°C (32°F to 122°F). 

 

 

EEPROM System Problem 

Please reconnect AC adapter to ZG1163 CO2 Monitor.   
If the “Err5, Err6” still appears, please contact the Service Department for further 
assistance. 

 

 

 

Radiant Innovation Inc.

  Http://www.ZyAura.com

 

1F, No.3, Industrial East 9

th

 Road, Science-Based Industrial Park, HsinChu, Taiwan 300.

 