14
MENU 2 – Setting function of signalling relays
– Basic setting of the signalling relays is SZ 1 % and SO 99 % of stroke.
– In case different setting is required, it can be changed after shifting the actuator to required position by means of
push-button C or O.
– Using push-button P, perform basic setting SZ 1 % and SO 99 % of stroke.
MENU 3 – Setting of blocking of torque in end-limit positions
– Shortly press P to select the set value of blocking time 0 – 20 s
(0 – 20 blinking of LED2)
and keep pressing push-
-button P to store the parameter to memory.
– Keep pressing push-button C to store actual position for blocking torque on the side Closed to memory.
– Keep pressing push-button O to store actual position for blocking torque on the side Open to memory.
MENU 4 – Setting transducer characteristics
– Shortly press P to select the value 4 – 20 mA – 1x blinking of LED2 or 20 – 4 mA – 2x blinking of LED2, and keep
pressing push-button P to store the parameter to memory.
Other menus only serve for board setting in version Control
MENU 5 – Setting control signal in 3P regulation
– Shortly press P to select value 4 – 20 mA
- 1x blinking of LED2,
or 20 – 4 mA
- 2x blinking of LED2,
or 0 – 20 mA
- 3x blinking of LED2,
or 20 – 0 mA
- 4x blinking of LED2
and keep pressing push-button P to store the parameter to memory.
MENU 6 – Setting insensitivity in three-position regulation
– Shortly press P to select value 1 – 10 %
(1 – 10x blinking of LED2)
and keep pressing push-button P to store
the parameter to memory.
MENU 7 – Response in case of losing control signal in three-position regulation
– Shortly press P to select value OPEN
- 1x blinking of LED2,
or CLOSE
- 2x blinking of LED2,
or STOP
- 3x blinking of LED2,
and keep pressing push-button P to store the parameter to memory.
MENU 8 – Way of switching off in end-limit positions in 3P regulation
– Shortly press P to select value TORQUE
- 1x blinking of LED2,
or PO
- 2x blinking of LED2,
or PZ
- 3x blinking of LED2,
PO + PZ - 4x blinking of LED2,
And keep pressing push-button P to store the parameter to memory.
PROCEDURE of SETTING PARAMETERs by PROGRAM DMS2
– Before starting the actuator, it is necessary to set some parameters of the system by means of program
DMS2 on PC.
– For safety reasons, the system is delivered in the state of induced error of Calibration when the functions are
limited in order to reduce the risk of damaging the actuator by wrong wiring. In controlling the actuator from program
DMS2, its run is stopped when any torque is induced.