PREMIER M PLUS 48 INSTALLATION MANUAL.
Approved Document No: GLT.MAN-120
PAGE 22
Issue : 1.2 Authorised: GH Date: 2/11/2007
12. PANEL SPECIFICATIONS
12.1 ENCLOSURE SPECIFICATIONS
DESCRIPTION VALUE
ENCLOSURE SIZE
480 x 395 x 100 mm
TOP CABLE ENTRIES
20 x 19mm DIA GROMMETED ENTRIES
BOTTOM CABLE ENTRIES
10 x 19mm KNOCKOUT ENTRIES
REAR CABLE ENTRIES
2 SNAP OUTS, 60 x 20mm
12.2 ELECTRICAL SPECIFICATIONS
ELECTRICAL DESCRIPTION
VALUE
MAINS VOLTAGE
230V AC +/- 10% @ 50/60 Hz
BATTERY VOLTAGE
24V DC (2 X 12V SLA BATTERY)
SYSTEM VOLTAGE
24V DC NOMINAL (18 – 32 V)
SYSTEM VOLTAGE RIPPLE
2V PK-PK MAX
CHARGER SIZE
UP TO 7AH in 24 Hours
ZONE VOLTAGE
21V DC NOMINAL (20 - 22.5V)
SOUNDER ALARM OUTPUTS
4 x 150mA @ 29V DC (Nominal)
ZONAL SOUNDER CIRCUITS (OPTIONAL)
8/12/16/20/24 x 50mA @ 29V DC (Nominal)
AUXILIARY FAULT OUTPUT
1 x RELAY SELV (1A MAX)
AUXILIARY FIRE OUTPUT
1 x RELAY SELV (1A MAX)
F.A.R.E. OUTPUT
1 X 100mA @ 29V DC
NUMBER OF ZONES
24/28/32/36/40/44/48
MAXIMUM ZONE CAPACITY
32 DEVICES PER ZONE
MAXIMUM ZONE RESISTANCE
70 ohms
AUXILIARY SUPPLY
250mA @ 29 V dc (NOMINAL)
SOUNDER ACTIVATION DELAY
0-9 MINUTES -IN 1 MIN INCREMENTS
ZONE END OF LINE DEVICE
100uF CAPACITOR (- STRIPE TO ZONE -VE)
SOUNDER END OF LINE DEVICE
10 K RESISTOR
CHARGER VOLTAGE
28.4V @ 25
o
C (NO BATTERY CONNECTED)
CHARGER SHORT CIRCUIT PROTECTION
Batteries less than 20V
TOTAL PSU OUTPUT
3 Amp
MAXIMUM CHARGING CURRENT
600mA
PANEL LOAD FOR BATTERY
CALCULATIONS
VALUE
PANEL CURRENT IN MAINS FAIL (NO ZONE
SOUNDERS)
150mA (125 mA with buzzer silenced)
PANEL CURRENT IN MAINS FAIL (WITH ZONE
SOUNDERS)
175mA (150 mA with buzzer silenced)
PANEL CURRENT IN ALARM
270mA