PREMIER M PLUS 48 INSTALLATION MANUAL.
Approved Document No: GLT.MAN-120
PAGE 12
Issue : 1.2 Authorised: GH Date: 2/11/2007
6.2.3 DELAY INDICATION AND OVERRIDE
If a delay is set, the fire panel will light the General Disablement LED and Sounder Delay LED to
indicate that the sounders are delayed. If an alarm occurs, the fire LEDs will light as usual, but the
sounders
will not start until the delay period has expired. After the delay period, the Gen Disablement
and Delay LEDs will extinguish & the sounders will start.
Pressing the
OVERRIDE SOUNDER DELAY
switch will override the delay at any time and results in
the sounders being turned on immediately.
If on investigation, the panel was activated by a false alarm, turn the keyswitch to Controls Enabled,
and press the reset button. This will return the system to normal, without the sounders being
activated. (Assuming the cause of the false alarm has been removed).
The delay can be removed by returning the rotary switch SW1 to position 0