INSTALLATION MANUAL
Страница 1: ...M 48 INSTALLATION MANUAL ...
Страница 2: ...Designed to EN54 Parts 2 4 It is available in sizes from 24 to 48 zones in 4 zone increments Automatically uses diode bases for line continuity Four common sounder circuits 400mA Each Serial Repeater Output Fire Fault Relays SELV F A R E Output which can be disabled Auxiliary supply 29 Volts 250 mA Zone Sounder Disablement facility One man test mode Sounder delay facility 3 amp power supply Is a l...
Страница 3: ...THE BATTERIES 5 FIELD DEVICE TERMINATION 10 5 1 TERMINATING THE DETECTION AND ALARM SOUNDER CIRCUITS 5 2 AUXILIARY INPUT AND OUTPUT TERMINATIONS 6 CONFIGURING THE PANEL 11 6 1 SOUNDER ACTIVATION DELAY 6 2 1 DECIDING TO SET A DELAY 6 2 2 TO SET A DELAY 6 2 3 DELAY INDICATION AND OVERRIDE 6 2 USING SOUNDER DELAY TO COMMON TIMER 7 ZONE DISABLEMENT 13 7 1 WHY USE ZONE DISABLEMENT 7 2 TO PROGRAM A ZONE...
Страница 4: ...t National Standards Contact the Fire Officer concerned with the property at an early stage in case he has any special requirements If in doubt read BS 5839 Pt 1 2002 Fire Detection and Alarm Systems for buildings Code of Practice for System Design Installation and Servicing available from the BSI or at your local reference library 1 5 EQUIPMENT GUARANTEE If this equipment is not fitted and commis...
Страница 5: ...on such as a conduit 2 2 MAINS WIRING RECOMMENDATIONS The Mains supply to the FACP is fixed wiring using Fire resisting 3 core cable Between 1 mm and 2 5mm or a suitable 3 conductor system fed from an isolating double pole switch fused spur fused at 5A IT SHOULD NOT BE CONNECTED THROUGH AN RCD This should be secure from unauthorised operation and be marked FIRE ALARM DO NOT SWITCH OFF The supply m...
Страница 6: ...ly with European Fire Alarm Panels For more specific device wiring information please refer to the device manufacturers own instructions The termination of each detection circuit must be as indicated on the main PCB See page 15 The Earthing of the cable screens should be as shown on page 9 2 4 SOUNDER CIRCUIT WIRING DIAGRAM SND SND SOUNDER SOUNDER SOUNDER SOUNDER 10K End of Line Resistor Note If n...
Страница 7: ...ored 24V nominal output This is a 24V 100mA output that activates in any fire condition and is used for driving local fire fighting equipment such as sprinkler systems magnetic door holders air conditioning shut off etc It is active until the panel is reset It can be disabled through the zone sounder disablement function which may be useful during maintenance tests if the panel is connected to a c...
Страница 8: ...he hole with a brass cable gland If any knockout is removed but subsequently not used it should be covered up The 230Va c Mains cable must be fed into the enclosure via one of the cable entries at the top right corner of the back box Refer to Connecting the Mains on Page 8 3 2 FIXING THE BACK BOX TO THE WALL Figure 2 Plan view inside the enclosure without PCBs Side view for surface flush installat...
Страница 9: ...ED WITH THE RUBBER GROMMETS PROVIDED It is advisable to apply power to the panel before connecting any devices to check for correct operation and to familiarise yourself with the fire alarm panels controls Although there are many sizes of suitable battery the sizes we usually recommend are 12V 7Ah The enclosure has been designed to hold this size battery To calculate the exact requirement use the ...
Страница 10: ...please refer to pages 4 and 5 FS FS FS FS FS FS ZONES 1 TO 8 BUILT IN ZONES 9 TO 16 BUILT IN ZONES 17 TO 24 BUILT IN ZONES 25 TO 32 BY ADD ON CARD ZONES 33 TO 40 BY ADD ON CARD ZONES 41 TO 48 BY ADD ON CARD BRASS GLANDS MAKE SURE ANY SPARE ENTRY HOLES ARE COVERED WITH THE RUBBER GROMMETS PROVIDED Figure 6 Detector and Sounder Circuit Connection 5 2 AUXILIARY INPUT AND OUTPUT TERMINATIONS Connect a...
Страница 11: ... alarm must be avoided It should be noted that the delay period will apply to ALL zones When an Alarm occurs on any zone it is processed as normal However the activation of the sounders is postponed until the delay period has expired thus allowing the cause of the Alarm to be investigated by the User If the alarm is false the alarm can be cancelled 6 2 2 TO SET A DELAY Open the panel door and set ...
Страница 12: ...elay period has expired After the delay period the Gen Disablement and Delay LEDs will extinguish the sounders will start Pressing the OVERRIDE SOUNDER DELAY switch will override the delay at any time and results in the sounders being turned on immediately If on investigation the panel was activated by a false alarm turn the keyswitch to Controls Enabled and press the reset button This will return...
Страница 13: ...oll through zones 24 48 then zone sounder 24 48 then common sounders then F A R E Continue to press scroll until the desired Zone or sounder is flashing 5 When an item has been disabled the DISABLEMENT LED will be lit The item that has been disabled will now flash 3 quick flashes then on This means that it has been disabled but is still the focus of the disablement select mode If scroll is pressed...
Страница 14: ...spended until the Alarm s from the other zones are investigated and then reset At this point zone retesting may resume 8 2 TO PROGRAMME ZONE IN TEST NOTE Only one zone can be programmed in test at any one time 1 Insert and turn control key to enabled position 2 Press FUNCTION button twice The General Zone test LED is now on flashing fast 3 Press Delay Override Silence Silence Delay Override The Ge...
Страница 15: ... A possible fault is a detector head badly seated in a base that is not making a good connection c A short circuit on a zone could be caused by the end of line capacitor being fitted backwards d Check that the detectors are compatible with this FACP Note that some makes of detector will require a series resistor or diode to be fitted to work properly There is usually a spare connector on the base ...
Страница 16: ...her equipment e g an oscilloscope to the panel can give an earth fault The voltage between battery Ve and earth should be 14 16 volts If it is not the voltage measured should indicate what is shorting to earth 9 5 SOUNDER FAULTS Check that the correct END of Line resistor has been fitted 10K brown black orange gold Check that all sounder fuses are OK FS4 FS5 FS7 FS8 150mA QB If working on an exist...
Страница 17: ... bells are connected to the common sounder circuit The required standby is 24 hours It will need to operate in alarm for hour Calculate the battery size required TALM 0 5 Hr IALM panel 0 270mA IALM 24 14 x 0 025 0 95A This typical bell current is 25 mA Most alarm Devices show their operating current TSBY 24 Hr IQP 0 150A IQZ 24 x 20 x 0 00006 0 0288A the quiescent current for a typical optical det...
Страница 18: ... to Zone 5 6 ZONE 6 Connect to Zone 6 7 ZONE 7 Connect to Zone 7 8 ZONE 8 Connect to Zone 8 9 SND 1 Connect to sounder circuit 1 sirens bells 10 SND 2 Connect to sounder circuit 2 sirens bells 11 SND 3 Connect to sounder circuit 3 sirens bells 12 SND 4 Connect to sounder circuit 4 sirens bells 13 FIRE RELAY NO CM NC Activates on fire including test mode 14 FAULT RELAY NO CM NC Activates on fault 1...
Страница 19: ...zones The ones in bank 1 will for zones 1 8 bank 2 will be for zones 9 16 bank 3 will be for zones 17 24 bank 4 will be for zones 25 32 bank 5 will for zones 33 40 and bank 6 will be for zones 41 48 11 2 FUSES FUSE NO DESCRIPTION RATING FS1 ZONE Zone Fuse 500mA time delay 5 x 20mm glass FS1 Charger Fuse 3 15A time delay 5 x 20mm glass FS2 Battery Fuse 3 15A time delay 5 x 20mm glass FS3 F A R E Fu...
Страница 20: ...urs ZONE VOLTAGE 21V DC NOMINAL 20 22 5V SOUNDER ALARM OUTPUTS 4 x 400mA 29V DC Nominal AUXILIARY FAULT OUTPUT 1 x RELAY SELV 1A MAX AUXILIARY FIRE OUTPUT 1 x RELAY SELV 1A MAX F A R E OUTPUT 1 X 100mA 29V DC NUMBER OF ZONES 24 28 32 36 40 44 48 MAXIMUM ZONE CAPACITY 32 DEVICES PER ZONE MAXIMUM ZONE RESISTANCE 70 ohms AUXILIARY SUPPLY 250mA 29 V dc NOMINAL SOUNDER ACTIVATION DELAY 0 9 MINUTES IN 1...
Страница 21: ...PREMIER M PLUS 48 INSTALLATION MANUAL Approved Document No GLT MAN 120 PAGE 21 Issue 1 2 Authorised GH Date 2 11 2007 ...
Страница 22: ...nal ZONAL SOUNDER CIRCUITS OPTIONAL 8 12 16 20 24 x 50mA 29V DC Nominal AUXILIARY FAULT OUTPUT 1 x RELAY SELV 1A MAX AUXILIARY FIRE OUTPUT 1 x RELAY SELV 1A MAX F A R E OUTPUT 1 X 100mA 29V DC NUMBER OF ZONES 24 28 32 36 40 44 48 MAXIMUM ZONE CAPACITY 32 DEVICES PER ZONE MAXIMUM ZONE RESISTANCE 70 ohms AUXILIARY SUPPLY 250mA 29 V dc NOMINAL SOUNDER ACTIVATION DELAY 0 9 MINUTES IN 1 MIN INCREMENTS ...