4
Specifications
ZPDS-
208V60A-
HW-6L21-20
ZPDS-
208V60A-
HW-4L21-30
ZPDS-
480V60A-
HW-4L22-30
ZPDS-
480V60A-HW-
6L22-20
ZPDS-208V30A-
L21-4L21-20
ZPDS-208V30A-
L21-4L21-20-CR
Electrical
Rated Input
Voltage
[3ø Wye]
208V
208V
480V
480V
208V
208V
Input Rated
Max. Amp
[Amp]
60
60
60
60
30
30
Rated Input
Frequency
[Hz]
50-60
50-60
50-60
50-60
50-60
50-60
Full Load
[kVA]
17.2
17.2
39.9
39.9
8.64
8.64
Standard
Input Cords
4AWG-5/C-SOOW-600V-90C-UL/CSA
10AWG-5/C-SJTW-600V-105C-
UL/CSA
Input Cord
Terminations
Hardwire enclosure
Nema L21-30P
Outputs
(6) L21-20R (4) L21-30R (4) L22-30R
(6) L22-30R
(4) L21-20R
(4) L21-20R
(3) 5-20R Duplex
Internal
Overload
Protection
(18) Circuit
Breakers
per phase
(12) Circuit
Breakers
per phase
(12) Circuit
Breakers
per phase
(18) Circuit
Breakers
per phase
(12) Circuit
Breakers per
phase
(12) Circuit
Breakers per
phase
Physical
Dimensions
(HxWxD)
3.57” x 17.619” x 13.5” Note: width across brackets 19.17”
Weight
67 Lbs
TBD
Shipping
Dimensions
22” x 24” x 20”
Shipping
Weight
72 Lbs
TBD
Environmental
Elevation
Operating
0 to 10,000 ft.
Elevation
Storage
0 to 50,000 ft.
Operating
Temperature
-13°F to 149°F
Operating
Humidity
0
–
95% Non-condensing
Approvals
Safety
as appropriate
Note: All specifications are subject to change without notice.
Содержание Z-PDS Series
Страница 1: ...Version 2 3 October 2019 Zonit Power Distribution System Z PDS User Guide ...
Страница 2: ...Version 2 3 October 2019 Table of Contents ...
Страница 13: ...11 Note Examples are implemented via Zonit plug adapters where needed Output Branch Circuit Configurations ...
Страница 20: ...18 Copyright 2019 Zonit Structured Solutions LLC All Rights Reserved ...