7. MOST FREQUENT ERRORS
ERROR
INDICADOR
CAUSA
SOLUCIÓN
1
When the centre is powered
by 230 VAC, any led light up.
Lack of
voltage
Check that voltage reaches the
centre (230 VAC
10%).
2
The right red led flashes
quickly.
(Zoning type installation)
Sensor error
Connect the sound or leave the
resistance which is wired for
default.
3
5 min after switching the
centre on, the zone leds
flashes in all zones and all
grilles are closed.
Incorrect
configuration
Check thermostat configuration.
Antenna not receiving. Modify
position.
4
Some of the zone led flashes
and the damper in this zone
is closed.
Bad
communication
The zone is badly configured in the
thermostat SETUP.
Interference in the communication.
Modify thermostat location.
Thermostat battery low
5
When the damper should
open
close
(And vice versa).
Motors badly
connected
Check the motor connection.
Polarity (black -, red +)
6
One of the dampers does
not work.
Zone regulator
connection
Check the motor connection.
Polarity (black -, red +)
Check that the regulator is not
obstructed.
7
All of the dampers work
properly but the air
conditioning equipment does
not work.
Air conditioning
equipment badly
connected
Check the Sw1 configuration of the
control centre depending on the
machine type.
Check the equipment connection
to the board.
8
The equipment switches on
and of with the MASTER at a
standstill or some zones
close or open without any
signal from the thermostat.
Interference with
neighbouring
installations
Check that there are no two
thermostats
with
the
same
configuration.
Check whether there is some other
Zoning System with the same
series number installed in the
neighbouring households (0.03%
probability)
TECHNICAL CHARACTERISTICS:
Control board (receiver)
Power: 230 VAC, 50/60 Hz.
Power consumption: 4 VA
2 Relay outputs.
Maximum current load: 6 A .Cos
=1
Average scope: 50 m in free field. 20 m in the habitat.
External aiming antenna.
Size (mm): 105 x 90 x 60
Carrier frequency (ISM Band, as per I-ETS 300-220 standard):
434.33 MHz (Optional: 433.92 MHz)
Operating cycle <10%
Receiver. Class III
Protection level: IP 20
Electric shock insulation Clase II.
Operating temperature: 0 ºC a 55ºC.
Storage temperature:: -10 ºC a 60 ºC.
Thermostat (transmiter)
Power: 2 x 1.5 V LR06 AA batteries (supplied). Average
autonomy 1 year (or more).
Battery wear indicator.
Carrier frequency (ISM Band, as per I-ETS 300-220 standard):
434.33 MHz (Optional: 433.92 MHz)
Average scope: 50 m in free field. 20 m in the habitat.
Size (mm) (mm): 112 x 71 x 19.
Operating temperature: 0 ºC a 55ºC.
Storage temperature:: -10 ºC a 60 ºC..
Wall attachment using screws (supplied)
Protection level: IP 20
ECO mode (ordered temp. variation of
3ºC)
Hereby MADEL ATD decalres that the KSP (control board + thermostat) is in compliance with the essential requirements and other relevant provisions
of Directive 1999/5/CE.
http://www.madel.com/eng/pdf/Zoningconformidadksp.pdf