OPERATING INSTRUCTION

OPERATION

Pressing any button on the SubZone Wireless Thermostat 

will wake up controller providing current information about 

system operations.

Using the Up and Down button, select your required 

setpoint:  

UP

 - Increases set point, additionally this button is used to 

configure time and date, set schedule.

DOWN

 - Decreases set point, additionally this button is used 

to configure time and date, set schedule.

Confirm “AUTO” icon appears above the third button on the 

thermostat to maintain zone comfort based on thermostat 

set point, room temperature and duct temperature.

FUNCTION BUTTONS

AUTO

 - Configures controller for AUTO mode or OFF mode

DUCT

 - Pressing this button displays supply air temperature

MENU

 - Accesses system configuration functions

OCCUPIED AND UNOCCUPIED 

OPERATIONS

When in the Occupied mode, the SubZone will work in 

normal operation.

When in the Unoccupied Mode, the SubZone thermostat will 

power down, screen display will go blank to conserve 

battery life and damper will go to ventilation mode, 40% 

open.  When it comes out of Unoccupied Mode to Occupied 

Mode at established setup time it will resume normal 

operation.

To wake the SubZone thermostat when in Unoccupied 

Mode, press any button to override.

TURN OFF SUBZONE

To turn SubZone Wireless Thermostat “OFF”, press and hold 

the AUTO on the SubZone Wireless Thermostat.  Hold 

button for 15 seconds, when “OFF” icon appears, release 

AUTO button.  The thermostat is now “OFF” Damper will 

fully close or go to minimum position.

ENERGY SAVING MODE

When this menu item is selected display will go blank after 

10 minutes to prolong and extend battery life.  SubZone is 

operating fully in this mode but display is blank.  To view 

display, press any button.

The SubZone Wireless Thermostat communicates with SubZone Damper Controller every minute or each time the thermostat 

buttons are pushed, transmitting information between the SubZone Damper Controller and the SubZone Wireless 

Thermostat.  System logic dictates system mode of operation.  When duct temperature is 3 degrees or more below room 

displayed temperature on SubZone Wireless Thermostat, the mode is set as Cool.  When duct temperature is 7 degrees or 

greater than room temperature as displayed on SubZone Wireless Thermostat, then mode is set for Heat.  If duct temperature 

is neither 3 degrees below nor 7 degrees above room temperature displayed on SubZone Wireless Thermostat, then mode is 

set for Vent.

UP

DOWN

SET POINT

DAMPER CONTROL BOARD

RED LED - 

Damper Runs 

CLOSED

GREEN LED - 

Damper Runs 

OPEN

YELLOW LED - 

AUX/HEAT 

is energized

BLUE LED - 

 

POWER & COMMUNICATION with the stat

 when flashing

 

SET CLOCK

SET SCHEDULE

SYNCHRONIZE DAMPER

SET STAT ID

CALIBRATE

SET AUX HEAT

TEMP FORMAT

ENERGY SAVING MODE

C

C

R

R
RX

RX

TX

TX

MC

RO

RC

C

AUX

TS

TS

SYNC

BUTTON

SYNC ID BUTTON

Содержание SubZone

Страница 1: ...mper will modulate open The SubZone system senses the duct temperature and compares it to the set point vs room temperature providing warm or cool air as required If the thermostat is not calling for heating or cooling the damper will modulate to 40 for ventilation The SubZone allows you to effectively control problem areas by controlling the existing air supply to the problem room or zone This ve...

Страница 2: ...t page NOTE An air proving switch field supplied must be used for reheat applications A field supplied relay may be required for VAV box applications FOR APPLICATIONS ASSISTANCE CALL 800 228 2966 VISIT OUR ON LINE CATALOG AT ZONEXPRODUCTS COM NOTES I E BASEBOARD OR RADIANT PANEL PROVIDE MODULATING ZONEX ROUND OR RECTANGULAR DAMPER or D Fuser DESIGNED TO SUPPORT UP TO 1 75 S P AUX CONTACTS USED TO CO...

Страница 3: ... and hold the AUTO on the SubZone Wireless Thermostat Hold button for 15 seconds when OFF icon appears release AUTO button The thermostat is now OFF Damper will fully close or go to minimum position ENERGY SAVING MODE When this menu item is selected display will go blank after 10 minutes to prolong and extend battery life SubZone is operating fully in this mode but display is blank To view display...

Страница 4: ...ns Once minutes are set press the NEXT button to select AM PM Press NEXT button to set Unoccupied Operations SET TIME OFF will be displayed when hour is highlighted use the UP DOWN buttons to select hour Press the NEXT button to set minutes using UP DOWN buttons Once minutes are set press the NEXT button to select AM PM using the UP DOWN button Press the NEXT button again to select Monday through ...

Страница 5: ...ace thermostat on sub base and turn set screw counter clockwise to fasten thermostat to sub base Reset time on the SubZone after battery replacement MOUNTING THE SUBZONE Once you have determined where you want to place the thermostat place the mounting plate in that spot and with a pencil mark where the drill holes will be Drill holes using a 1 8 drill bit Install screw anchors supplied with the t...

Отзывы: