background image

Stand-Alone Modulating Damper
Controlled with Auto Changeover
Programmable Wireless Thermostat

W I R E L E S S   T H E R M O S T A T

WIRING INSTALLATION INSTRUCTION

Su

b

Zone

INSTALLATION

1.  Install Wireless SubZone Round, Rectangular or D-FUSER Damper into the supply air duct.  

     (Ref. Part # WST Round, WCD Rectangular WxH, WD-FUSER)

2.  Install a 24 volt, 40 VA transformer in accordance with local code requirements.  From the transformer - run 18/2 wire and 

     connect to SubZone control board terminals R and C.

3.  Install Discharge Air Sensor (TS) in the ductwork prior to the supply damper and run sensor wires to the SubZone control   

     board.  If wires need to be extended, 18 gauge thermostat wire may be used, not to exceed 100 ft. in length.

4.  Duct Air Temperature (TS) sensor wires are connected to the TS terminals of the SubZone control board.

Once the SubZone damper with controller has been installed go to Programming and Setup Instructions on the next page.

*

NOTE:

 An air proving switch (field supplied) must be used for reheat applications.  A field supplied relay may be required for VAV box 

applications.

FOR APPLICATIONS ASSISTANCE CALL 800 228 2966

VISIT OUR ON-LINE CATALOG AT ZONEXPRODUCTS.COM

NOTES:

     I.E. BASEBOARD OR RADIANT PANEL

PROVIDE MODULATING ZONEX ROUND OR RECTANGULAR DAMPER

or D-Fuser DESIGNED TO SUPPORT UP TO 1.75" S.P.
AUX CONTACTS USED TO CONTROL SUPPLEMENTAL HEAT SOURCE:

if ELECTRIC HEAT IS USED AN AIR PROVING SWITCH MUST BE INSTALLED

T-1

WIRELESS ZONE THERMOSTAT

R
C

TS

MC

RC

RO

24 VAC POWER INPUT
24 VAC POWER COMMON

DUCT TEMPERATURE SENSOR

24 V MOTOR COMMON

DAMPER RUN CLOSED SIGNAL

DAMPER RUN OPEN SIGNAL

AUX

OPTIONAL AUXILIARY HEAT

TERMINAL CONNECTIONS

CONTROLLER and ACTUATOR

DESCRIPTION

THERMOSTAT

T - 1

SUBZONE WIRELESS STAT

ZONEX SubZone

TS -1

DUCT TEMPERATURE SENSOR

TRANSFORMER

SYSTEM POWER 24 V - 40 VA

TR - 1

CONTROL BOARD

CB - 1

LAT SENSOR

SUBZONE CONTROLLER and ACTUATOR

C

C

R

R
RX

RX

TX

TX

MC

RO

RC

C

AUX

MC

RC

RO

DISCHARGE AIR

SUPPLY AIR DUCT

TS
TS

TS
TS

TS-1

TR-1

CB-1

ACTUATOR

COMMUNI

CA

TING 

D

A

MPER B

O

ARD

(OPTIONAL)

DUCT HEATER

INDEPENDENT

24V /40VA

TRANSFORMER

Содержание SubZone

Страница 1: ...mper will modulate open The SubZone system senses the duct temperature and compares it to the set point vs room temperature providing warm or cool air as required If the thermostat is not calling for heating or cooling the damper will modulate to 40 for ventilation The SubZone allows you to effectively control problem areas by controlling the existing air supply to the problem room or zone This ve...

Страница 2: ...t page NOTE An air proving switch field supplied must be used for reheat applications A field supplied relay may be required for VAV box applications FOR APPLICATIONS ASSISTANCE CALL 800 228 2966 VISIT OUR ON LINE CATALOG AT ZONEXPRODUCTS COM NOTES I E BASEBOARD OR RADIANT PANEL PROVIDE MODULATING ZONEX ROUND OR RECTANGULAR DAMPER or D Fuser DESIGNED TO SUPPORT UP TO 1 75 S P AUX CONTACTS USED TO CO...

Страница 3: ... and hold the AUTO on the SubZone Wireless Thermostat Hold button for 15 seconds when OFF icon appears release AUTO button The thermostat is now OFF Damper will fully close or go to minimum position ENERGY SAVING MODE When this menu item is selected display will go blank after 10 minutes to prolong and extend battery life SubZone is operating fully in this mode but display is blank To view display...

Страница 4: ...ns Once minutes are set press the NEXT button to select AM PM Press NEXT button to set Unoccupied Operations SET TIME OFF will be displayed when hour is highlighted use the UP DOWN buttons to select hour Press the NEXT button to set minutes using UP DOWN buttons Once minutes are set press the NEXT button to select AM PM using the UP DOWN button Press the NEXT button again to select Monday through ...

Страница 5: ...ace thermostat on sub base and turn set screw counter clockwise to fasten thermostat to sub base Reset time on the SubZone after battery replacement MOUNTING THE SUBZONE Once you have determined where you want to place the thermostat place the mounting plate in that spot and with a pencil mark where the drill holes will be Drill holes using a 1 8 drill bit Install screw anchors supplied with the t...

Отзывы: