background image

Su

b

Zone

W I R E L E S S   T H E R M O S T A T

Stand-Alone or Floating Zone

Modulating Damper Controlled with Auto Changeover Programmable

SUBZONE OVERVIEW

The system is designed for over-conditioned areas and prevents over-heating and over-cooling of individual or 

stand alone zones.  The SubZone is a battery powered auto changeover programmable thermostat that 

communicates via an RF wireless signal to a damper control module located on a fully modulating round or 

rectangular damper or D-Fuser.  

 

Auto changeover operation allows the SubZone thermostat to change from a cooling to a heating thermostat 

automatically.  A duct sensor is included and installed upstream of the damper to determine the temperature 

in the duct.  If the SubZone thermostat is calling for cooling and cool air is available in the duct the damper 

will modulate open.  A heating call will close the damper.  If the sensor determines warm air is available in the 

duct and the thermostat is calling for heat the damper will modulate open.  The SubZone system senses the 

duct temperature and compares it to the set point vs. room temperature providing warm or cool air as 

required.  If the thermostat is not calling for heating or cooling the damper will modulate to 40% for 

ventilation.

 

The SubZone allows you to effectively control problem areas by controlling the existing air supply to the 

problem room or zone.  This versatile problem solver is also designed to control supplemental or 

auxiliary heating devices.

Zonex auto changeover programmable thermostat is designed to control and modulate a stand alone diffuser or damper.  

Zonex offers 600 unique sizes of round and rectangular dampers for your commercial applications.

SubZone

 solves the problem of over-heated and 

over-cooled

 rooms for your customers

S

UB

Z

ONE

 FEATURES

Auto Changeover 7-day Programmable
Control Fully Modulating Dampers
Display Duct Temp at the Stat
Adjustable Aux or Reheat Operation
F or C Temperature Operation
Single Set Point for Easy End User Operation

Wireless
Setpoint lock
Auto / Off switch
Non volatile memory retains stored 

    set points, date, and schedules
Slave capability – up to 3 dampers per stat

(800) 228-2966  

|

  zonexproducts.com 

Содержание SubZone

Страница 1: ...mper will modulate open The SubZone system senses the duct temperature and compares it to the set point vs room temperature providing warm or cool air as required If the thermostat is not calling for heating or cooling the damper will modulate to 40 for ventilation The SubZone allows you to effectively control problem areas by controlling the existing air supply to the problem room or zone This ve...

Страница 2: ...t page NOTE An air proving switch field supplied must be used for reheat applications A field supplied relay may be required for VAV box applications FOR APPLICATIONS ASSISTANCE CALL 800 228 2966 VISIT OUR ON LINE CATALOG AT ZONEXPRODUCTS COM NOTES I E BASEBOARD OR RADIANT PANEL PROVIDE MODULATING ZONEX ROUND OR RECTANGULAR DAMPER or D Fuser DESIGNED TO SUPPORT UP TO 1 75 S P AUX CONTACTS USED TO CO...

Страница 3: ... and hold the AUTO on the SubZone Wireless Thermostat Hold button for 15 seconds when OFF icon appears release AUTO button The thermostat is now OFF Damper will fully close or go to minimum position ENERGY SAVING MODE When this menu item is selected display will go blank after 10 minutes to prolong and extend battery life SubZone is operating fully in this mode but display is blank To view display...

Страница 4: ...ns Once minutes are set press the NEXT button to select AM PM Press NEXT button to set Unoccupied Operations SET TIME OFF will be displayed when hour is highlighted use the UP DOWN buttons to select hour Press the NEXT button to set minutes using UP DOWN buttons Once minutes are set press the NEXT button to select AM PM using the UP DOWN button Press the NEXT button again to select Monday through ...

Страница 5: ...ace thermostat on sub base and turn set screw counter clockwise to fasten thermostat to sub base Reset time on the SubZone after battery replacement MOUNTING THE SUBZONE Once you have determined where you want to place the thermostat place the mounting plate in that spot and with a pencil mark where the drill holes will be Drill holes using a 1 8 drill bit Install screw anchors supplied with the t...

Отзывы: