The Static Pressure Controller controls a standard medium pressure round damper (STMPD) or the heavy duty rectangular damper (STCD)
by maintaining constant static pressure in the duct downstream of the bypass takeoff.  As the zone dampers close, the static pressure increases.
When this happens, the static pressure controller opens the bypass damper to bring the static pressure back to the setpoint.

STATIC PRESSURE CONTROLLER DESCRIPTION

A:

Mounting tabs.

B:

Supply air barb.

C:

Reference air, “LOW”, barb.

D: Diaphragm must be 

mounted vertically.

E:

Pressure adjusting screw.

F:

Normally closed, N/C, terminal.

G:

Normally open, N/O, terminal.

H:  Common, COM, terminal.

STATIC PRESSURE CONTROLLER INSTALLATION

a) Select location for pressure sensor tube. Location should be in sup-

ply duct, downstream of bypass takeoff, upstream of any zone
dampers and perpendicular to the air flow.  

b) Drill 5/16” hole at selected location for pressure sensor tube.
c) Mount Static Pressure Controller near the drilled hole with the

diaphragm of the sensor vertical. The controller must be mounted
on a stable, non vibrating surface.

d) Attach 5/16” pressure sensor tube, supplied, to the barb of the

Static Pressure Controller located closest to the mounting tabs.
The other barb, labeled “LOW”, is left open if the Controller
is in the conditioned building. If the Controller is located outside
the  building, another tube, not provided, must be connected
between the “LOW” barb and a location inside the building.

e) Remove the terminal cover and wire as shown in the wiring

diagram.

f)

Reattach terminal cover.  Installation is complete. Proceed to Static
Pressure Controller Setup.

STATIC PRESSURE CONTROLLER SETUP

Note:

24V ac may be read on both terminals (RO & RC to MC) due to

voltage bleeding thru the motor windings. Disconnect the RO or RC wire
to determine which wire is energizing the motor.

a) Ensure all dampers are open and blower is running on high speed.

The DigiTract 

controller should have the green blower LED 

on

and

all of the red damper LEDs 

off

.

b) Verify bypass damper is 

Closed

.

Bypass dampers using a square
motor have a grey release lever on the bottom/side of the damper
(near motor) to manually open or close the damper.

c) At 101ASPC Static Pressure Controller, remove the 

NO

wire from the

micro switch. Connect A/C voltmeter (or test light) to 

COM

and 

NC

terminals of static pressure controller. 

Zero V ac

(no light) should

be present, ensuring a connection is made between 

COM

and 

NC

. If

24V ac is present (light on), turn adjustment screw on 101ASPC
Static Pressure Controller clockwise (

CW

) until connection is made

and 0V ac (no light) is obtained. Do Not Overtighten Adjusting Screw.

d) Verify bypass damper is 

Closed

. Slowly back out adjusting screw

(

CCW

) until 24V ac (light on) is present ensuring no connection

between 

COM

and 

NC

. STOP. Slowly turn adjusting screw in (

CW

)

until 0V ac (no light) is present. STOP. Bypass damper should be on
verge of opening but still closed with all zone dampers open and the
blower fan on high speed.

e) If the bypass damper sizing and duct design are correct, this

completes the bypass damper setup. Connect all wires and proceed
to Bypass Checkout.

BYPASS CHECKOUT FOR STATIC 
PRESSURE CONTROLLER

a) Make a cool call at the zone thermostat of the smallest (damper size)

zone.

b) Verify all zone dampers are closed except for calling zone.  
c) Verify noise at zone register is not excessive. Adjust static pressure

controller CCW to lower noise (airflow) or CW to increase airflow
until too noisy.

STOPS

AIRFLOW

 BYPASS DAMPER

MOTOR 

WINDOW

AIRFLOW

STATIC 

PRESSURE 

SENSOR

1

AIR

CONDITIONER

C
O

I

L

Insert the tube into the side of the duct, approximately 

3”.  Make sure the tube is perpendicular to the air flow.

1

A

B

C

E

F

G

H

D

BYPASS DAMPER – STATIC PRESSURE CONTROLLER

Zonex Systems recommends de-energizing the bypass damper when the
blower fan turns off. If not installed as recommended, when the blower fan
turns off the bypass will fully close. Then when the blower fan turns back
on, there could be excessive air supplied to the calling zone, causing
excessive air noise until the bypass is able to open sufficiently. An
alternative wiring diagram is provided using an additional static pressure
sensor to deenergize the bypass damper.

22

Alternative Wiring

Содержание DigiTract 4-2

Страница 1: ...DigiTract 4 2 Two Stage Heat Cool Comfort Control System Installation Guide Part DT4MAN Rev April 2003 Zoning Systems That s all we do...

Страница 2: ...Heat Pump DTHP4 2 11 Calibration 11 LAS Installation 11 ZONE THERMOSTATS Types 12 Zonex Systems Gas Electric Models 12 Digital SADIGI 12 Digital SADIGI Operation 13 Programmable 101PROG 12 Communicati...

Страница 3: ...he auxiliary heat to maintain a minimum supply air temperature of 88 degrees See Capacity Controller section page 11 for further information The Zone Dampers are air valves placed in the forced air du...

Страница 4: ...BBD diam Rectangular RBB W x H PROGRAMMABLE DIGITAL 101PROG SADIGI OVER 5 TONS ELECTRONIC BYPASS Round STMPD diam Rectangular STCD W x H STATIC PRESSURE CONTROLLER 101ASPC BYPASS TRANSFORMER FIELD SUP...

Страница 5: ...e LAS downstream of the bypass takeoff Ensure wire polarity is correct Refer to CAPACITY CONTROLLER LAS INSTALLATION on P 11 for further information NOTE Shielded conductor provided for installations...

Страница 6: ...er sized and fused for the total number of zone dampers See DAMPER TRANSFORMER on page 23 Emergency heat terminal E Use only if emergency heat source is different from auxiliary heat W2 If used do not...

Страница 7: ...1AMPD 101MRTD 101CD DAMPER RELAY BOARD R C MC RC W W Y RO TB2 TB1 N C N C N C N C N C N C N C N C 101 SERIES DAMPER TO ADDITIONAL 101 SERIES DAMPERS IF APPLICABLE FUSED 24VAC XFMR Transformer and fuse...

Страница 8: ...nating Dampers for the zones not calling for cool are powered closed and the dampers for the zones calling for cool are left open This is indicated by the DPR LEDs If the DPR LED is illuminated on the...

Страница 9: ...o know this number if conferring with technical support F Heat Mode Fan Control Selection Jumper In the A position the blower is energized by the furnace when heat is energized gas furnaces In the B p...

Страница 10: ...e if the System Controller receives a call for the opposite mode the System Controller will continue to run in the current mode for 15 minutes or until all current calls are satisfied Then the System...

Страница 11: ...per is closed STATUS LEDs O B Y1 Y2 G W2 PWR DPR MODE FUNCTION OFF OFF OFF OFF OFF OFF OFF Off Power off OFF OFF OFF OFF OFF ON OFF On Power on blower off all zones satisfied OFF OFF OFF ON OFF ON 0 V...

Страница 12: ...gized G made to R requests that the DTHP4 2 energize the indoor blower fan C Heat pump unit 24V power return C Damper Terminals Connects dampers for up to four zones and damper power supply TR1 TR2 24...

Страница 13: ...rgize Y1 and operate with a minimum run time of 4 minutes regardless of the leaving air temperature At the completion of the minimum run time if the leaving air temperature drops below 45 F Y is deene...

Страница 14: ...n SADIGIRS 101PROG Programmable dual setpoint single stage heat cool electronic non power robbing auto changeover weekday weekend 5 1 1 programmable manual override capable Thermostat includes a larg...

Страница 15: ...n the room temperature drops two degrees below the heat setpoint and after running a minimum of 2 minutes turn off when the temperature has risen to the heat setpoint When in Auto or Cool mode the the...

Страница 16: ...d easy spring open operation A cross pin on the motor shaft provides positive direct drive to the damper blade shaft without a coupling or set screws allowing for a quick and easy motor change if requ...

Страница 17: ...19 21 PART 101AMPD06 101AMPD08 101AMPD10 101AMPD12 101AMPD14 101AMPD16 101AMPD18 6 8 10 12 14 16 18 Nominal CFM Duct Diameter Duct Velocity FPM Damper P WC 10 12 14 16 6 8 7 9 410 660 1450 1000 110 25...

Страница 18: ...ully closed and cycle off when the damper is opening or in the full opened position Since this is a spring open damper in the event of power failure the damper fails to the full open position RECTANGU...

Страница 19: ...MOTOR 48 MAXIMUM WIDTH A Rectangular heavy duty dampers should operate at 1500 FPM E G A 24 x 12 damper 2 square feet 2 square feet X 1500FPM 3000 CFM 4 200 280 390 490 700 1090 1500 2000 2500 3000 36...

Страница 20: ...tic pressure and noise at the diffusers Zonex Systems offers two types of bypass dampers Barometric and Electronic Each is available in round or rectangular configuration Barometric bypass dampers are...

Страница 21: ...or 5 minutes to equalize pressure Then make sure all dampers are open by checking for air flow out of each damper c By moving counter weight up or down the lever arm adjust it so that the damper just...

Страница 22: ...olume is 400 CFM and we have a four ton system Thus the air volume we need to bypass is 400 4 400 which equals 1200 CFM Using the ROUND BYPASS SELECTION TABLE we would select a 12 inch bypass since it...

Страница 23: ...16500 18333 20167 22000 48 12000 14000 16000 18000 20000 22000 24000 8 10 12 14 16 18 20 22 8 667 833 1000 1167 1333 1500 1667 1833 10 833 1042 1250 1458 1667 1875 2083 2292 12 1000 1250 1500 1750 200...

Страница 24: ...ass damper is Closed Bypass dampers using a square motor have a grey release lever on the bottom side of the damper near motor to manually open or close the damper c At 101ASPC Static Pressure Control...

Страница 25: ...ng system go to step 12 2 At System Controller a Disconnect LAS sensor at terminals and place jumper wire between terminals b Turn power switch ON 3 Turn off all thermostats except zone 1 4 At zone 1...

Страница 26: ...ext zone a Verify air is not coming out of register diffuser b At thermostat b 1 Set power switch on b 2 Set to Heat mode b 3 Set Fan switch to Auto mode b 4 Set heat setpoint several degrees above ro...

Страница 27: ...Thermostat has cooling anticipator compensator Remove anticipator Air flow too low over evaporator Isolate and correct air flow problem Bypass damper opening prematurely Adjust bypass damper closed w...

Страница 28: ...Fax 714 898 6802 Visit our Web Site http www hvaccomfort com E mail us at calecon hvaccomfort com PATENTED PRODUCT Zonex Systems reserves the right to discontinue or change at any time specifications...

Отзывы: