12

ZONE THERMOSTATS

Each zone requires a zone thermostat.  The following lists the types of
thermostats to use with each Digitract 4-2 system, information on Zonex

Systems thermostats and how to select a thermostat not manufactured by
Zonex Systems.

Gas/Electric DTGE4-2

– Use 24V ac single stage gas/electric thermostats.

Zonex Systems offers three models:  SADIGI, 101PROG and DIGICOM.
If not using Zonex Systems thermostats, see Thermostat Compatibility
section below.

Heat pump DTHP4-2

– Use 24V ac single stage heat, single stage cool

heat pump thermostats. If emergency heat feature is preferred then the
thermostat for Stat1 must have the emergency heat mode feature. If the
heat pump has the compressor fail flag feature, STAT1 should also have
a compressor fail light. See Thermostat Compatibility section below.

Zonex Systems offers three thermostat models that can be used with the Gas/Electric Digitract 4-2 System
Controller (DTGE4). These models are SADIGI, 101PROG and DIGICOM. 

SADIGI: 

The SADIGI is a single stage gas/electric, hard wired (non-power robbing) thermostat. It can

control one heat, one cool and blower fan. It can run in Heat, Cool, or Auto changeover mode. Setpoint
range is from 55° to 86° Fahrenheit. The mode and setpoints are stored in nonvolatile memory so they
will be remembered even if power is interrupted. It has a bright and easy to read digital display and is
simple to operate. Up and down push buttons select the mode and setpoint(s). Under the cover of the
thermostat there are two mode status lights: one red and one green. The red light is on when the
thermostat is making a heat call. The green light is on when the thermostat is making a cool call. The
dimensions are: 2

7

8

”W x 4

1

2

”H x 1”D, the color is off white. Terminal designations are: R, C, Y, W

and G. Requires 5 conductor thermostat wire. Can be ordered with remote sensor; p/n SADIGIRS.

101PROG:

Programmable, dual setpoint, single stage heat/cool, electronic, non power robbing, auto

changeover, weekday/weekend (5,1,1) programmable, manual override capable. Thermostat includes
a large LCD that displays time, day, program, setpoints and room temperature. Can program up to four
different schedules per day. Battery backup memory. Dimensions are: 6”W x 3

1

2

”H x 1

3

4

”D. Requires

five thermostat wires for installation. Color: White. Can be ordered with remote sensor; p/n 101PROGRS.

DIGICOM/DIGIHP:

The DIGICOM and DIGIHP are auto changeover, communicating thermostats used

exclusively in ZonexCommander thermal management systems. Using a computer and the ZonexCommander
software, all thermostats in the system can be programmed and viewed. The DIGICOM/DIGIHP may
be applied in stand alone unit control, from 1 to 20 split or packaged systems. When used with a
modem, all ZonexCommander software functions can be controlled remotely. The DIGICOM/DIGIHP
requires 24V AC power from either the zone system or HVAC unit transformer, with the addition of a two
conductor, twisted pair cable for communications. Dimensions: 2-7/8” W x 4-1/2” H x 1” D. 

ZONE THERMOSTATS – COMPATIBILITY

The DTGE4-2 gas/electric and DTHP4-2 heat pump controllers are compatible with most thermostats,
offering a wide thermostat selection to the installing contractor. When using other than Zonex Systems
thermostats, please refer to the following guidelines:

Electronic Thermostats:

Digital thermostats requiring 24V AC power must be “Hard wired” with a

separate R and C or common terminal. Power robbing type thermostats are not compatible. All types
of battery operated thermostats may be used with any Digitract 4-2 control system.

Mechanical Thermostats:

When using a mechanical thermostat, ensure the cooling compensator

(anticipator) is removed, and the heating anticipator is shorted or set to its lowest setting. 

Please contact Factory Technical Support for additional thermostat compatibility information.

ZONE THERMOSTATS – TYPES

ZONEX SYSTEMS THERMOSTATS

DIGICOM/DIGIHP

SADIGI

Содержание DigiTract 4-2

Страница 1: ...DigiTract 4 2 Two Stage Heat Cool Comfort Control System Installation Guide Part DT4MAN Rev April 2003 Zoning Systems That s all we do...

Страница 2: ...Heat Pump DTHP4 2 11 Calibration 11 LAS Installation 11 ZONE THERMOSTATS Types 12 Zonex Systems Gas Electric Models 12 Digital SADIGI 12 Digital SADIGI Operation 13 Programmable 101PROG 12 Communicati...

Страница 3: ...he auxiliary heat to maintain a minimum supply air temperature of 88 degrees See Capacity Controller section page 11 for further information The Zone Dampers are air valves placed in the forced air du...

Страница 4: ...BBD diam Rectangular RBB W x H PROGRAMMABLE DIGITAL 101PROG SADIGI OVER 5 TONS ELECTRONIC BYPASS Round STMPD diam Rectangular STCD W x H STATIC PRESSURE CONTROLLER 101ASPC BYPASS TRANSFORMER FIELD SUP...

Страница 5: ...e LAS downstream of the bypass takeoff Ensure wire polarity is correct Refer to CAPACITY CONTROLLER LAS INSTALLATION on P 11 for further information NOTE Shielded conductor provided for installations...

Страница 6: ...er sized and fused for the total number of zone dampers See DAMPER TRANSFORMER on page 23 Emergency heat terminal E Use only if emergency heat source is different from auxiliary heat W2 If used do not...

Страница 7: ...1AMPD 101MRTD 101CD DAMPER RELAY BOARD R C MC RC W W Y RO TB2 TB1 N C N C N C N C N C N C N C N C 101 SERIES DAMPER TO ADDITIONAL 101 SERIES DAMPERS IF APPLICABLE FUSED 24VAC XFMR Transformer and fuse...

Страница 8: ...nating Dampers for the zones not calling for cool are powered closed and the dampers for the zones calling for cool are left open This is indicated by the DPR LEDs If the DPR LED is illuminated on the...

Страница 9: ...o know this number if conferring with technical support F Heat Mode Fan Control Selection Jumper In the A position the blower is energized by the furnace when heat is energized gas furnaces In the B p...

Страница 10: ...e if the System Controller receives a call for the opposite mode the System Controller will continue to run in the current mode for 15 minutes or until all current calls are satisfied Then the System...

Страница 11: ...per is closed STATUS LEDs O B Y1 Y2 G W2 PWR DPR MODE FUNCTION OFF OFF OFF OFF OFF OFF OFF Off Power off OFF OFF OFF OFF OFF ON OFF On Power on blower off all zones satisfied OFF OFF OFF ON OFF ON 0 V...

Страница 12: ...gized G made to R requests that the DTHP4 2 energize the indoor blower fan C Heat pump unit 24V power return C Damper Terminals Connects dampers for up to four zones and damper power supply TR1 TR2 24...

Страница 13: ...rgize Y1 and operate with a minimum run time of 4 minutes regardless of the leaving air temperature At the completion of the minimum run time if the leaving air temperature drops below 45 F Y is deene...

Страница 14: ...n SADIGIRS 101PROG Programmable dual setpoint single stage heat cool electronic non power robbing auto changeover weekday weekend 5 1 1 programmable manual override capable Thermostat includes a larg...

Страница 15: ...n the room temperature drops two degrees below the heat setpoint and after running a minimum of 2 minutes turn off when the temperature has risen to the heat setpoint When in Auto or Cool mode the the...

Страница 16: ...d easy spring open operation A cross pin on the motor shaft provides positive direct drive to the damper blade shaft without a coupling or set screws allowing for a quick and easy motor change if requ...

Страница 17: ...19 21 PART 101AMPD06 101AMPD08 101AMPD10 101AMPD12 101AMPD14 101AMPD16 101AMPD18 6 8 10 12 14 16 18 Nominal CFM Duct Diameter Duct Velocity FPM Damper P WC 10 12 14 16 6 8 7 9 410 660 1450 1000 110 25...

Страница 18: ...ully closed and cycle off when the damper is opening or in the full opened position Since this is a spring open damper in the event of power failure the damper fails to the full open position RECTANGU...

Страница 19: ...MOTOR 48 MAXIMUM WIDTH A Rectangular heavy duty dampers should operate at 1500 FPM E G A 24 x 12 damper 2 square feet 2 square feet X 1500FPM 3000 CFM 4 200 280 390 490 700 1090 1500 2000 2500 3000 36...

Страница 20: ...tic pressure and noise at the diffusers Zonex Systems offers two types of bypass dampers Barometric and Electronic Each is available in round or rectangular configuration Barometric bypass dampers are...

Страница 21: ...or 5 minutes to equalize pressure Then make sure all dampers are open by checking for air flow out of each damper c By moving counter weight up or down the lever arm adjust it so that the damper just...

Страница 22: ...olume is 400 CFM and we have a four ton system Thus the air volume we need to bypass is 400 4 400 which equals 1200 CFM Using the ROUND BYPASS SELECTION TABLE we would select a 12 inch bypass since it...

Страница 23: ...16500 18333 20167 22000 48 12000 14000 16000 18000 20000 22000 24000 8 10 12 14 16 18 20 22 8 667 833 1000 1167 1333 1500 1667 1833 10 833 1042 1250 1458 1667 1875 2083 2292 12 1000 1250 1500 1750 200...

Страница 24: ...ass damper is Closed Bypass dampers using a square motor have a grey release lever on the bottom side of the damper near motor to manually open or close the damper c At 101ASPC Static Pressure Control...

Страница 25: ...ng system go to step 12 2 At System Controller a Disconnect LAS sensor at terminals and place jumper wire between terminals b Turn power switch ON 3 Turn off all thermostats except zone 1 4 At zone 1...

Страница 26: ...ext zone a Verify air is not coming out of register diffuser b At thermostat b 1 Set power switch on b 2 Set to Heat mode b 3 Set Fan switch to Auto mode b 4 Set heat setpoint several degrees above ro...

Страница 27: ...Thermostat has cooling anticipator compensator Remove anticipator Air flow too low over evaporator Isolate and correct air flow problem Bypass damper opening prematurely Adjust bypass damper closed w...

Страница 28: ...Fax 714 898 6802 Visit our Web Site http www hvaccomfort com E mail us at calecon hvaccomfort com PATENTED PRODUCT Zonex Systems reserves the right to discontinue or change at any time specifications...

Отзывы: