situations as well as when by-pass air is being directed back 
into the return air duct.   
 
The  heating  limit  is  adjustable  from  110

F  to  170

F.    The 

cooling limit is fixed at 45

F.  When the ZPS senses heating 

above  its  set  point,  or  cooling  below  its  set  point,  the  H32 
will drop both all stages of heating or cooling.  The ZPS must 
sense a 10

F fall for heating or rise for cooling before re- 

 
activating the first stages of heating or cooling.  If two stage 
heating or cooling is being used the second stage timer will 
start again once the first stage is re-activated.  

110

120

130

140

150

160

170

HIGH LIMIT

 

The  ZPS  requires  2  wires  from  the  sensor  to  the  ZPS 
terminals on the H32 panel.   

 

LAS
LAS
OAS
OAS

Leaving Air Sensor
In Supply Air Duct

Outdoor Air Sensor  only used with 
Fossil/Dual Fuel Applications

 

 
Outdoor Air Sensor - OAS 

The Outdoor Air Sensor is used only when using a Heat Pump with 
Dual/Fossil Fuel back-up furnaces.  The OAS senses the outdoor air 
temperature  and  switches  the  heating  control  between  the  heat 
pump  and  the  fossil  fuel  furnace.    The  temperature  set  point  for 
this  is  adjustable  on  the  Outdoor  Balance  Point  (OBP)  dial  on  the 
control panel.  It is adjustable from 5°F to 53°F.   
 

5

13

21

29

37

45

53

OBP

 

Stage Timer 

The  H32  has  a  built-in  stage  timer  that  eliminates  the  need  and 
added  cost  of  using  two  stage  thermostats.    On  a  call  for  either 
heating  the  timer  begins.    Setting  the  Stage  Timer  dial  provides  a 
adjustable  time  delay  of  4  to  68  minutes  between  the  first  and 
second stage calls.   

 
 
 
 

PURGE TIME 

The  H32  has  a  built-in  Purge  Time  after  each  call  is  satisfied  and 
provides a minimum off time  before another call is initiated.  The 
Purge Time is set at 2 minutes after all calls for a particular mode 
are satisfied or when the Changeover Timer requires a changeover 
due to opposing calls.   
 
After  all  calls  are  satisfied  or  the  changeover  timer  activates,  the 
Purge Timer begins and the heating or cooling, whichever was on, 
is  deactivated.    Typically  the  fan  may  be  running  during  this  time 

and  the  damper(s)  to  the  last  zone(s)  calling  will  remain  open  to 
purge  the  conditioned  air  only  into  those  zones  that  were  calling 
for the conditioning.  DIP Switch 5 can be set ON to keep the Fan 
running during the Purge mode in order to prevent the fan cycling 
off  and  back  on  between  modes.    In  the  instance  where  the  Fan 
staying  may  create  a  draft,  and  the  frequency  of  opposite  calls  is 
minimal this switch can be kept to OFF.   
 

Minimum On Timer 

The  H32  also  has  a  minimum  on  time  whenever  the  compressor 
operates in order to prevent frequent short cycling.  Once there is a 
call  for  cooling  or  the  compressor  on  a  heat  pump,  the  H32  will 
hold that call for a period of 2 minutes.   

 
CHANGEOVER TIMER 

Whenever  a  call  is  made  for  either  heating  or  cooling,  the 
changeover timer is activated in order to track the amount of time 
heating or cooling is on.  When an opposite call is made after a first 
call is existing the changeover timer calculates the amount of time 
the  unit  has  already  been  supplying  the  first  mode  in  order  to 
determine how long it will hold off the opposite call.  If an opposite 
call is made shortly after the first call, the opposite call may be held 
off for as much as 20 minutes.  If the first call or subsequent calls 
for  the  first  call  mode  has  had  that  mode  operating  for  up  to  20 
minutes  already  and  an  opposite  call  comes  in  after  20  minutes, 
the changeover timer will immediately recognize the opposite call, 
shutting  off  the  current  mode,  enter  the  purge  mode  and 
automatically switch to the opposite mode.   
The  longer  a  call  has  been  running  up  to  20  minutes,  the  shorter 
the  wait  time  will  be  for  an  opposite  call.    If  a  call  is  over  20 
minutes  and  an  opposite  call  is  made  the  changeover  will  be 
immediate  following  the  purge  time.    This  intelligent  changeover 
timing makes the H32 unique to any other zoning system.   
 

CHECKOUT 

The  H32  has  unique  features  that  simplify  the  checkout  of  the 
system  and  has  LED  readouts  that  constantly  indicate  the  system 
operation.  Once 24 Volt Power is applied to the panel  the Green 
Power  LED  will  illuminate.    This  will  stay  illuminated  constantly 
when power is applied.   
 
The  System  LED  will  provide  several  different  indications  based 
upon color and if it is flashing.   
 

First Stage Heat Call   

 

RED

 

Second Stage Heat Call 

 

RED

 Flash 1/Second 

Heat Limit 

 

Red

/

Amber

 Alternate Flashing 

Emergency Heat - 

RED

 Flash 2/second 

First Stage Cool Call   - 

GREEN

 

Second Stage Cool Call 

 

GREEN

 Flash 1/second 

Cool Limit - 

GREEN

/

Amber

 Alternate Flashing 

Fan On - 

Amber

 

Purge - 

Amber

 Flash 

 

Each zone has its own small Green indicator LED next to each zone 
relay.    This  light  is  lit  when  the  specific  zoning  is  calling  for  the 
mode shown on the System LED. 

 
WIRING  

The  H32  is  very  simple  to  wire  and  requires  only  a  minimum 
number of connections.  The  H32 terminal blocks are color coded 
and screw-less for all wires to be easily pushed into their respective 
terminal  by  de-pressing  the  button  for  each  point  and  releasing 
once the wire is seated.  (Solid wire can often just be pushed into 

4

 

37

 

59

 

68

 

  STAGE TIMER

 

15

 