board.  There are 4 key-hole mounting points in each corner 
of the case.  The case has openings in the rear of the case as 
well  as  the  side  for  all  wiring.    Wiring  can  come  from  the 
back as well as the side in order to make a neat installation.   

 
OPERATION 

The  H32  can  be  controlled  by  conventional  single  stage  or 
heat pump thermostats.   Each thermostat can then call for 
heating,  cooling  or  the  fan.      This  panel  can  control  single 
stage gas-oil-electric heating and cooling, two stage heating 
and  cooling  and  most  heat  pumps.    This  panel  can  control 
two stage/speed and dual/fossil fuel heat pumps. 
 
When a call for either heating or cooling is made the panel 
will  open  the  damper(s)  to  the  zone(s)  calling,  close  the 
damper(s)  to  those  zones  not  calling,  activate  the 
appropriate  controls  for  heating  or  cooling,  whichever  is 
being called and not accept any calls for the opposite mode.   
 
Any calls for the opposite mode will be locked out until the 
initial  mode  is  either  satisfied  or  a  period  of  time  has 
elapsed  that  is  sufficient  for  the  first  mode  to  satisfy,  a 
maximum  of  20  minutes.    A  unique  sequence  determines 
the time the unit has been running or needs to continue to 
run  in  order  to  adequately  provide  conditioning  for  each 
mode.  If a  particular  mode  has already been  calling for  20 
minutes or longer and an opposite call comes in the H32 will 
immediately drop the mode, enter the purge mode in order 
to dissipate the conditioned air into the zones calling before 
switching  over  to  provide  the  new  conditioning  call  to  its 
zones.   
 
When  using  the  H32  to  control  two  stage  heating,  the 
second  stage  is  controlled  based  upon  time  after  the  first 
stage  call  from  the  thermostat.    When  any  zone  calls  the 

panel’s built

-in timer begins and after the set period of time 

elapses  the  H32  will  also  activate  the  W2  for  second  stage 
heating.   The Second Stage Timer is adjustable between 4 to 
68 minutes after the first stage calls.  Once the second stage 
is on, it will continue to run until the first stage is satisfied.   
 
Once  all  zone  thermostats  are  satisfied  for  heating  and 
cooling,  the  H32  can  now  accept  Fan  calls  allowing 
Continuous  Air  Circulation  (CAC)  in  those  zones  where  the 

thermostat’s Fan Switch is set  to ON.  These zone dampers 

will be Open while the dampers to the zones where the Fan 
Switch is set to AUTO will be CLOSED.   
 
When  all  zone  thermostats  are  satisfied  for  both  Heating 
and Cooling, and all Fan switches are set to AUTO position, 
the HVAC unit will be off and all zone dampers will return to 
a  normally  open  position.    Once  a  zone  calls  for  heating, 
cooling or fan, the dampers to the calling zones remain open 
and the dampers to the zones not calling will close.   
 

 
 
 

Set-Up for Various HVAC Equipment 

The  H32 is  factory set  for conventional  heating and cooling 
operation.    The  panel  only  needs  to  be  configured  when 
using with an electric furnace or heat pumps.  
 
The panel configuration is done by setting the DIP switches 
in  the  bottom  left  of  the  panel.    Other  functions  come  by 
wiring  for  specific  applications.    Below  is  shown  the  most 
typical settings.  Review each function for you application.     
 

SYSTEM 

  G/E  OR  HP 

This  switch  sets  the  HVAC  Output 

operation.  In G/E the Y1 operates as first stage cooling only.  
In  HP  position  Y1  makes  as  the  compressor  call  for  both 
heating and cooling.   

HP Type 

 CONV or FF 

 This switch is used to determine the 

equipment output when the System switch is set to HP, this 
switch  determines  if  the  output  will  be  for  a  conventional 
heat  pump  with  electric  back-up  heat  or  fossil  (dual)  fuel 
mode.   

FAN IN HEAT 

 YES or NO

 

 This switch will activates the Fan 

on a call for Heat in the Yes position.  In Off, the heating unit 
must activate the fan when the heat is called.  

 

FAN PURGE 

 YES or NO 

 

This switch determines if the Fan 

is kept on during the Purge Mode, after the end of each heat 
or cool call.  

 

STAT  RV 

  O  or  B 

 

When  using  HP  type  thermostats  this 

determines  if  the  O  or  B  terminal  is  wired  to  the  W/OB 
terminal  on  each  thermostat  to  determine  if  the  call  if  for 
Heat (B) or Cool (O).  

  

TSTAT 

 HC-HP 

Switch determines if conventional Heat/Cool 

thermostats  or  Heat  Pump  thermostats  are  being  used  for 
ALL  zones.   A conventional  HC stat  would have  separate  W 
and Y output for heating and cooling calls.  A HP thermostat 
uses Y for both a heat and cool call and the O or B is used to 
determine whether the call is for Cooling (O) or Heating (B).  

EM  HEAT

 

 

This  switch  sets  any  heat  call  to  call  for  the 

Emergency  Heat.    The  Red  EM  HEAT  LED  on  the  panel  will 
light only when this switch is ON.  This is used when there is 
no EH switch on the thermostats.    

TEST 

 

This switch accelerates the panel timings in order to 

provide  a  quick  checkout  of  all  of  the  functions  without 
having to wait the full time for each sequence.    

ZONE STAGING MODE 

 

This switch is used to control how 

the second stage of heating & cooling is determined.  In the 
OFF  position,  the  second  stage  is  controlled  by  the  stage 
timer  setting.  In  the  ON  position,  the  second  stage  is 
brought on based on the number of zones calling. When 2 of 
the  3  zones  are  calling,  the  second  stage  will  activate  for 
both heating and cooling. 

 
Leaving Air and Outdoor Air Sensor  

The Leaving Air Sensor, Model ZPS, is a remote sensor that is 
located  in  the  supply  air  duct  to  sense  the  Leaving  Air 
temperature  of  the  HVAC  Unit.    The  ZPS  is  a  high  limit 
protection for the heating and a low limit protection for the 
cooling.  When zoning, the airflow through the HVAC Unit is 
critical.    The  ZPS  protects  the  equipment  in  low  air  flow 