3. Delay protection function of the compressor
This unit offers restart protection for the compressor. Except that the compressor
may start immediately when the unit is energized for the first time, there is 3-minute
delay start protection after the compressor is shut down.
4.After the compressor operates continuously for 10 minutes, if the pipe temperature
sensor detects that the difference between the pipe temperature and room
temperature is less than 3
℃
for 30 minutes continuously, the unit enters fluorine-free
protection, the compressor and water spraying motor turn off, the fan operates in the
low speed mode and E3 is displayed.
Remote Control
1
2
3
4
5
6
7
C / F
Press the key to switch
℃
and
℉
.
Power key
Press the key to turn ON/OFF the A/C.
Speed key
Press the key to choose high/low speed.
Temperature/ time adjusting key
Press the key at cooling mode
to increase/reduce the setting temperature;
press it at timing mode to adjust timing ON/OFF
time.
Mode key
Press the key to choose cool,fan,dry.
Timer key
Press the key at standby mode to set ON time.
Press this key at ON mode to set OFF time.
Sleep Key
Press the key to choose sleep mode.