background image

7

© Copyright 2010 Zoeller Co. All rights reserved.

Once the above has been verifi ed proceed with the following checks:

•  Pump power cables properly connected to panel.
•  Float cables properly connected to panel.
•  Conduit connections to panel are properly sealed.
•  Thermal overload adjustments made in the panel.
•  After installing the pump into the containment area, with adequate 

submergence, open the discharge valve fully. Start the unit using 
manual controls. If fl ow is appreciably less than rated performance, 
pump may be air locked. To expel trapped air, jog the unit several 
times, using the manual controls.

•  Have a qualifi ed electrician take voltage and current measurements 

on the black wire of single phase or all three power wires of three 
phase with the pump running. Record these readings in the space 
provided in the “Owner’s Information” section on page 1 of this 
manual for future reference. 

After the preoperational functional test has been completed, system 
is ready for operation. Zoeller requires completing a Start-up Report 
(ZM1074) whenever a system is started for the fi rst time or after a 
system has had a signifi cant change take place (i.e. pump replacement, 
overhaul, etc..). A copy of the Start-up Report should remain with the 
system for future reference.

Operation 

(continued)

ADJUSTMENT PROCEDURE

Pumps:  No adjustments are required other than assuring correct

  

rotation.

Panels:  The thermal overloads in the panel  must be set to the F.L.A. rat-

ing on the pump nameplate (or refer to pump data sheet).

Floats:   Refer to the system drawing for desired location of each fl oat 

function.

Valves:  Discharge valves should be placed in the fully open position. 

Systems should not be operated for extended periods of time 

with the discharge valves partially closed due to damaging 

the valve.

SHUTDOWN PROCEDURES

If a system is shutdown for more than six months, the following is recom-

mended:

Pumps:  If pit is to remain dry, then the pump can remain in the pit. 

With the pump in the pit, it should be operated for fi ve minutes 

once every three months. If the pit is to remain wet, the pump 

should be removed and stored as noted above.

Panels:  The panel should have all openings sealed to prevent moisture 

and dust from entering the enclosure. Prior to restarting system, 

the panel should be inspected for presence of moisture and any 

loose connections.

Valves:  Consult the valve/actuator supplier for information concerning 

these systems components.

 Repair and service should be performed by a Zoeller 

Pump Company Authorized Service Station only.

SAFETY PROCEDURES

 For your protection, always disconnect pump and panel 

from its power source before handling.

 Never enter the basin until it has been properly vented 

and tested. Any person entering a basin should be wearing a harness 

with safety rope extending to the surface so that they can be pulled out 

in case of asphyxiation. Sewage water gives off methane and hydrogen 

sulfi de gases, both of which can be highly poisonous.

Installation and checking of electrical circuits and hardware should be 

performed by a qualifi ed electrician.

Pump is never to be lifted by power cord.

 Unit must be fl ushed and disinfected, inside and out, 

prior to servicing.

GENERAL SYSTEM INSPECTION

Before the system is placed into operation, a system Start-up Report 

should be conducted by a qualifi ed technician.

 Wiring and grounding must be in accordance with the na-

tional electrical code and all applicable local codes and ordinances.

LUBRICATION PROCEDURES

No lubrication is required.

If pumps are to be stored for more than six months, refer to short term 

storage procedure in the Operation section.

PREVENTIVE MAINTENANCE

Preventive maintenance is recommended to ensure a long service life 

from the product. Provided is a suggested maintenance schedule.

Every month:

•  Check for proper and unobstructed fl oat operation.

•  Listen for proper check valve operation.

•  Duplex Units - Check for even operating times. Uneven times indicate 

a defective unit, fl oat switch or control.

•  Inspect the panel for any presence of moisture in enclosure, loose 

connections, and general component condition. check out location 

and  condition of fl oat switches.

Every year:

•  In addition to the monthly checks, the basin should be inspected 

and cleaned. Any defective components should be replaced. Inspect 

and remove any sand, debris, or mud present in the pump basin 

assembly. 

Every two years:

•  Check insulating oil in motor and seal chambers. Inspect oil for 

contaminations as follows:

•  Clear oil, no burnt odor - Oil, motor and seals are in satisfactory 

condition.

•  Dark oil, burnt odor - Pump motor has overheated. Check the motor winding 

resistance to ground. Ohm readings of 1 megohm or higher is required. If 

lower readings are present, return the unit to an Zoeller Authorized Service 

Station for service.

• Milky, emulsifi ed oil - Seals have failed. Unit must be returned to an 

authorized service facility for service.

•  Dispose of the motor insulating oil properly if replacement is re-

quired.

•  Inspect power cables for damage or wear. Replace immediately if 

damage or wear is detected.

•  Inspect impeller for damage or wear. Replace as required by a Zoeller 

Authorized Service Station.

DOUBLE SEAL PUMPS

•  Double seal pumps offer extra protection from damage caused by seal 

failure.

•  Oil in a motor housing and lower seal cavity must be checked when 

pump is serviced. If oil from the motor housing contains water or other 

contamination, both seals should be replaced during maintenance. 

Always replace with new factory recommended oil and service parts. 

All repairs must be made by  Zoeller Authorized Service Stations.

Maintenance

Содержание 600 Series

Страница 1: ...mp but also save time and money during installation Reference FM1799 for repair manual on 600 Series Pumps Should further assistance be necessary please call our Technical Service Department at 1 800 928 PUMP 7867 Table of Contents Safety Instructions 1 Limited Warranty 2 Performance Data 2 Preinstallation Information 3 Electrical Data 3 Typical Dewatering Installation 4 Typical Sewage Installatio...

Страница 2: ...ranty for any material or product that has been disassembled without prior approval of Manufacturer subjected to misuse misapplication neglect alteration accident or act of God that has not been installed operated or maintained in accordance with Manufacturer s installation instructions that has been exposed to outside sub stances including but not limited to the following sand gravel cement mud t...

Страница 3: ...tallation a vent hole approx 3 16 must be drilled in the discharge pipe below the check valve and pit cover to purge the unit of trapped air Water stream will be visible from this hole during pump run periods This vent hole should be checkedperiodicallyforcloggingandcleanedasnecessary Trappedairiscaused by agitation and or a dry basin 4 Water hammer creates momentary high pressure surges These sur...

Страница 4: ...ump run periods Also a vent hole is drilled in the pump housing Be sure that this hole is cleared during any servicing 7 Vent gases and odors to the atmosphere through vent pipe per Local and State codes 8 Secure power cord to avoid entanglement with variable level float switch mechanism 9 Do not reduce pump discharge pipe below 3 IPS size 10 Basin must be in accordance with all applicable codes a...

Страница 5: ...ted capacitors and starting relays Your control panel should have provisions for mounting these starting components 2 All pumps require overload protection in panel Use with approved motor control that matches motor input in full load amperes with overload element s selected or adjusted in accordance with control instructions 3 Hazardous Location pumps require panels that offer intrinsically safe ...

Страница 6: ...or seal in plastic bag the terminal ends of wire leads Single Phase Installation All single phase models require start capacitor run capacitor and relay in the circuit to start and operate properly These components can be pur chased separately or prewired in Zoeller control panel For components purchased separately used the diagram for installation and hookup Single phase models are nonautomatic T...

Страница 7: ...has been properly vented and tested Any person entering a basin should be wearing a harness with safety rope extending to the surface so that they can be pulled out incaseofasphyxiation Sewagewatergivesoffmethaneandhydrogen sulfide gases both of which can be highly poisonous Installation and checking of electrical circuits and hardware should be performed by a qualified electrician Pump is never t...

Страница 8: ...fective Pit too small D Pump will not shut off Debris under float switch Float travel obstructed Defective or damaged float switch Magnetic starter contacts shorted Air lock check vent hole E Pump operates but delivers little or no water Check for plugged Pump housing discharge pipe or sticking check valve Vent hole clogged or not drilled Discharge head exceeds pumps capacity Low or incorrect volt...

Отзывы: