background image

© Copyright 2014 Zoeller

®

 Co. All rights reserved.

4

IL0413

Figure 2

To size pressure tank properly, match the 

drawdown of the tank to the capacity of the 

pump.
(*)  For manual operation, omit the pressure 

tank and pressure switch.  Wire motor direct to 

fuse box or switch per NEC.

Gate/Ball Valve 

(Normally Open)

Check Valve

Union

Line Strainer 

or Filter 

(Optional)

Street Supply

Union

Gate/Ball Valve 

(Normally Open)

Pressure 

Gauge

Check Valve

Union

Gate/Ball Valve 

(Normally Open)

Pressure Tank

Pressure 

Switch

Main Power Box

Fuse Box 

or Switch

Union

Pressure Switch

Drain

Pressure Gauge

Pressure Relief Valve

Typical Installations

Install a pressure relief valve on 

any installation where pump pressure can exceed 

the pressure tank's maximum working pressure 

or on systems where the discharge line can be 

shut off or obstructed.  Extreme over pressure can 

result in personal injury or property damage.

IL0414

Figure 3

Foot Valve 

with Strainer

Pressure Tank

Pressure 

Switch

Pressure 

Gauge

Main Power Box

Gate/Ball Valve 

(Normally Open)

Fuse Box 

or Switch

Union

Pressure Switch

Drain

Pressure Gauge

Union

Pressure Relief 

Vacuum 

Gauge

Union

Содержание 300 Series

Страница 1: ...ght lock it in the open position and tag it to prevent unexpected application of power Failure to do so could result in fatal electrical shock 7 Unit must be securely and adequately electrically grounded This can be accomplished by wiring the unit to a ground metal clad raceway system or by using a separate ground wire connected to the bare metal of the motor frame or other suitable means 8 Do not...

Страница 2: ...assume for us any other liability in connection with our products Contact Zoeller Pump Company 3649 Cane Run Road Louisville Kentucky 40211 1961 Attention CustomerServiceDepartmenttoobtainanyneededrepair or replacement of part s or additional information pertaining to our warranty ZOELLER PUMP COMPANY EXPRESSLY DISCLAIMS LIABILITY FOR SPECIAL CONSEQUENTIAL OR INCIDENTAL DAMAGES OR BREACH OF EXPRES...

Страница 3: ...3 7 8 2 4 4 5 8 3 11 16 4 13 16 9 3 16 2 1 8 8 1 4 8 1 8 15 5 8 3 7 8 Figure 1 300 Series Single Stage Booster Pump IL0396 H A C J E D F K B G 1 1 4 Discharge 1 1 2 Suction Motor Data Chart B HP PH VOLTS HZ RPM MOTOR VOLTAGE FACTORY CONNECT SERVICE FACTOR MOTOR AMPS SINGLE PHASE LOCKED ROTOR AMPS SINGLE PHASE KVA 115V 230v 115V 230v 1 3 1 115 230 60 3450 115V 8 6 4 3 26 0 13 0 K 1 2 1 115 230 60 3...

Страница 4: ...Open Pressure Tank Pressure Switch Main Power Box Fuse Box or Switch Union Pressure Switch Drain Pressure Gauge Pressure Relief Valve Typical Installations Install a pressure relief valve on any installation where pump pressure can exceed the pressure tank s maximum working pressure or on systems where the discharge line can be shut off or obstructed Extreme over pressure can result in personal in...

Страница 5: ...an that required by the unit PIPING 1 Use galvanized piping rigid plastic or other suitable pipe that will not collapse under suction or rupture due to pressure 2 The diameter of the suction and discharge pipe should be no smaller than the corresponding tappings of the pump see Figure 1 If long runs are encountered larger pipe should be used Smaller pipe will reduce the capacity of the pump 3 All ...

Страница 6: ...perty damage IL0415 Pressure Gauge Rigid Foundation Priming Plug Level Pipe Support Discharge Suction Pipe Installed with Gradual Rise to Pump Inlet Figure 4 ELECTRICAL Ground motor before connecting to electrical power supply Connect the motor frame to equipment grounding conductor by using green screw Do not connect green ground wire to any of the motor leads Do not ground to a gas supply line T...

Страница 7: ...g can be accomplished by any of the following methods 2 When the liquid supply level is above the center line of the pump it is primed by opening the suction and discharge valves The inflowing liquid will displace the air and fill the suction line pump casing and discharge line up to the level of supply 3 Where the pump is operating with suction lift and the suction line is equipped with a foot va...

Страница 8: ...Bent impeller shaft 6 Replace Pump will not start or run 1 Improperly wired 1 Refer to wiring diagram 2 Blown fuse or open circuit breaker 2 Replace fuse or close circuit breaker 3 Loose or broken wiring 3 Tighten connections and replace broken wiring 4 Impeller clogged 4 Clean 5 Motor shorted out 5 Replace Pumps leaks at shaft 1 Worn mechanical seal 1 Replace 2 Bent impeller shaft 2 Replace Place...

Отзывы: