15
MOTOR DATA CHART
HP
Phase
Volts Code Letter Max Amps
Locked Rotor
Amps
1/3
1
115
A
3.1
9.5
PERFORMANCE
Item
Number
HP
Ft. of Head Flow (GPM)
Shut Off
Head (Ft.)
Discharge
Size
1104-0082
1/3
0
43
18
1-1/2 in.
5
38
10
30
15
14
SPECIFICATIONS
Problem
Possible Cause
Corrective Action
Capacity or flow
drops after a
period of use.
1. Clogged inlet or discharge pipe.
1. Clean all piping.
2. Check valve clogged or defective.
2. Be sure check valve is installed and
operating properly. Replace check
valve if necessary.
3. Abrasive material or chemicals
damaged impeller or pump housing.
3. Remove base and inspect.
TROUBLESHOOTING