Leak detection; pressure test:
- never use oxygen or dry air (risk of fire or explosion)
-
use dry nitrogen or the mixture of nitrogen and refrigerant indicated on the
information plate,
-
the test pressure for both the high and low pressure circuits must not exceed
42 bar (for R410A) in cases where the appliance is equipped with the optional
pressure gauge.
• The high pressure circuit pipes are made of copper and have a diameter equal to or
greater than 1’’5/8. A certificate as indicated in §2.1 in compliance with standard
NF EN 10204 must be requested from the supplier and filed in the installation's
technical file.
•
Technical data relative to the safety requirements of the various applicable directives
are indicated on the information plate. All this information must be recorded in the
appliance's installation manual, which must be kept in its technical file: model,
code, serial number, maximum and minimum OT, OP, year of manufacture, CE
marking, manufacturer’s address, coolant and weight, electrical parameters,
thermo-dynamic and acoustic performance.