14
2.3 I Electricity supply connections
•
Before any work inside the device, you must cut the electricity supply as there is a risk of
electric shock which may cause material damage, serious injury or even death.
•
Incorrectly tightened terminals may cause the terminal unit to heat up and invalidate the
warranty.
•
Only a qualified and experienced technician is authorised to carry out cabling in the equipment
or to replace the supply cable.
•
The heat pump's electrical supply must be provided through a protection and circuit breaking device (not supplied)
complying with the standards and regulations in force in the country where it is installed,
•
The device is provided for connection to a general power supply with a TT and TN.S neutral regime.
•
Electrical protection: by circuit breaker (D curve) (for calibre, see § “1.2 I Technical specifications”), with a 30 mA
dedicated differential circuit breaker (circuit breaker or switch) at the head of the line.
•
The electricity supply must correspond to the voltage indicated on the device's information plate.
•
The electricity supply cable must be insulated against any cutting or hot elements that may damage or crush it.
•
The equipment must be connected to an earth socket.
•
The electrical connection lines must be fixed.
•
Use the gland to pass the supply cable into the device.
•
Used the supply cable (RO2V type) adapted for outdoor or buried use (or run the cable into a protection duct).
•
We recommend burying the cable at a depth of 50 cl (85 cm under a road or path) in an electrical duct (red ribbed).
•
If this buried cable meets another cable or pipe (gas, water, etc.), there must be more than 20 cm between them.
Depending on the model, there are 2 ways to connect:
Device not equipped with a cable (Z200, PI20 and Power 11M models)
•
Connect the supply cable to the connection terminal unit inside the heat pump.
L: live
N: neutral
PE: earth
Device equipped with a cable with plug (Power models 5M, 7M or 9M)
•
Check that the supply cable is firmly attached to the connection terminal.
•
All use of an extension cord or multisocket connection is prohibited.
•
If the supply cable is not long enough, contact a qualified technician.
•
Connect the supply cable delivered with the appliance to a 16A socket, according to the
country's applicable standards and regulations.