ENGLISH

  

 

 

Jandy

® 

Pro Series JE Heat Pumps   

|

   Installation and Operation Manual

test

recommended level

Free Chlorine or

1.0 to 3.0 ppm

Bromine

2.0 to 4.0 ppm

pH

7.2 to 7.8 (Ideal ranges being between 7.4 and 7.6)

Total Alkalinity (TA)

80 to 120 ppm

Calcium Hardness (CH)

175 to 400 ppm

Cyanuric Acid

30 to 50 ppm

Total Dissolved Solids (TDS)

1000 to 2000 ppm (Excluding dissolved NaCl from Salt 
Chlorine Generator)

* Concentration levels taken from “Basic Pool and Spa Technology” published by APSP (Association of Pool and 

Spa Professionals).

table 3.  optimal Water Chemistry ranges

checks must be performed.

Check for loose or broken wires and terminal 

connections.

2. 

Verify the pressure switch or flow switch 

operation. Turn the heat pump OFF. Disconnect 

the power to the pump time clock, or turn the 

pump time clock to an OFF position. Turn the heat 

pump back ON. The heat pump must not come on.  

3. 

Inspect the electrical controls, specifically the 

following:

 

a. High and Low Limits

 

b. Pressure Switch or Flow Switch

 

c. Temperature Control

4. 

Inspect the evaporator coil for blockage and clean 

as necessary.

5. 

Check for spider webs or debris in the condensate 

drain; clean if necessary.

6. 

Conduct a normal operating cycle and observe that 

the unit operates properly.

section 7.  professional Maintenance 
and service

7.1 

Heat pump design

The Zodiac

®

 heat pump is one of the most efficient 

ways to heat a pool or spa. The heat pump transfers heat 

from the outside air to the pool or spa water by means 

of an internal heat exchanger. 

When the fan is turned on, warm air is drawn through 

the refrigerant charged evaporator, turning the cold 

liquid refrigerant to a warm gas. The gas then flows 

through the compressor where it is compressed resulting 

in a much higher temperature.

The hot gas enters the heat exchanger where the water 

extracts the heat. The pump pulls in cool pool water, 

which in turn converts the hot gas back into a liquid 

refrigerant and starts the cycle over again.

The JE heat pump and the EE-Ti heat pump uses a 

refrigerant called R-410A. It is a non-ozone depleting 

refrigerant that is accepted by the EPA. R-410A has 

higher operating pressures and cooling capabilities than 

R-22, which is the refrigerant used in the AE-Ti heat 

pump. Therefore, R-410A should NEVER be used in 

any of the AE-Ti heat pumps.

The EPA requires certification to purchase or use 

R-410A. It is recommended that service personnel be 

trained in installation, service, brazing, and maintenance 

procedures. They are similar to what the industry has 

used for the R-22 system, however, they should be 

redefined for the higher operating pressures.

notE

  The maximum heat output and efficiency of 

a heat pump is dependent upon the quality 

and performance of the major components 

used. Equally important are the environmental 

conditions (for example, air temperature, 

humidity, water temperature, and wind).

7.2 

Heat pump Components and 
operation

Evaporator

 - As air passes through the evaporator, the 

refrigerant in the evaporator absorbs heat from the 
ambient air. The warmer the ambient air and the 
larger the surface area of the evaporator the more 
heat it can collect.

Fan

 - The heat pump fan produces high volume airflow. 

Adequate airflow is required to move warm air 

through the large evaporator.

Compressor

 - The compressor compresses the 

refrigerant gas to a higher pressure, increasing the 

temperature.

Heat Exchanger

 - As the final step to the heating 

process, the heat exchanger transfers the heat 

from the hot gas to the water. (Also known as a 

condenser.)

Reversing Valve

 - (For Hybrid Units with Optional 

Chiller and Hot Gas Defrost) The reversing valve 

reverses the flow of the refrigerant, which results 

in transferring cold gas to the water, thus lowering 

the temperature.

Содержание Jandy Pro Series JE1500T

Страница 1: ...on of R410A refrigerant In the event no such state or local requirement exists the installer or maintainer must be a professional with sufficient experience in pool equipment installation and maintena...

Страница 2: ......

Страница 3: ...Spa Connection 3 Wire Connection 16 Figure 11b AquaLink RS or Remote TSTAT Connection 2 Wire Connection 16 Figure 12 AquaLink RS to JE Heat Pump 17 Figure 13 JE Heat Pump Connection to Power Center 1...

Страница 4: ...Page 2 ENGLISH Jandy Pro Series JE Heat Pumps Installation and Operation Manual...

Страница 5: ...rovides installation and operation instructions for the Jandy Pro Series JE models of heat pumps Read these installation and operation instructions completely before proceeding with the installation C...

Страница 6: ...here possible shelter the pool from prevailing winds with well trimmed hedges or other landscaping cabanas or fencing 7 The use of an automatic pool cover if installed provides a valuable safety featu...

Страница 7: ...installation is required to assure safe operation The requirements for Zodiac heat pumps include the following 1 Field assembly if required 2 Appropriate site location and clearances 3 Sufficient air...

Страница 8: ...ing Scroll Scroll Scroll CABINET ABS REFRIGERANT 64 Oz R410A 78 Oz R410A 78 Oz R410A 78 Oz R410A 118 Oz R410A 126 Oz R410A 118 Oz R410A 126 Oz R410A REFRIGERANT HIGH PRESSURE ALARM 600 PSI reset to 46...

Страница 9: ...ed indoors means of condensate disposal must be provided Indoor installation requires factory consultation Lawn Sprinklers Keep lawn sprinkler heads from spraying on the heat pump to prevent corrosion...

Страница 10: ...ater connections are no more than 10 feet below the pool water surface or no more than 5 feet above it See instructions for pressure switch adjustment Section 5 6 in the heat pump start up section of...

Страница 11: ...ng on multiple heat pump installations must be done in parallel see Figures 6 and 7 An equal flow of water to each heat pump is important for optimum operation Note It may be necessary to adjust water...

Страница 12: ...the front cover of the junction box 4 Electrical supply lines must be run through watertight conduit Route the wires and conduit through the knock out designated for high voltage on the right side of...

Страница 13: ...CAL FEEDER TO POOL OR SPA CHECK VALVE OR OPTIONAL CHLORINE GENERATION SYSTEM JANDY AQUAPURE SHOWN MANUAL BYPASS VALVE CHEMICAL LOOP POOL HEATER VENT FOR INDOOR INSTALLATION ONLY HEATER HEAT PUMP FROM...

Страница 14: ...and Operation Manual Figure 6 Two 2 Heat Pump Plumbing Layout Figure 7 Four 4 Heat Pump Plumbing Layout Manual Bypass Valve 2 PVC 3 PVC Optional Isolation Valves From Filter To Pool Manual Bypass Valv...

Страница 15: ...BK BL BK BK BR W BL Y Y BL W BR HIGH REFRIGERANT PRESS SWITCH LOW REFRIGERANT PRESS SWITCH WATER TEMP DEFROST TEMP BK R R L1 L2 Y Y Y Y BK W R R FAN MOTOR BR BR W BK W W W W W R R GROUND GR GR R REVE...

Страница 16: ...GR Y GROUND POWER BOARD COMPRESSOR FAN MOTOR WATER PRESSURE SWITCH USER INTERFACE REVERSING VALVE OPTIONAL HIGH REFRIGERANT PRESSURE SWITCH LOW REFRIGERANT PRESSURE SWITCH CONTACTOR W W W W W L1 L2 L3...

Страница 17: ...a Remote Pool Off Spa Selector 3 Wire Connection Install the Remote Pool Off Spa Selector 1 Turn off the power to both the pool spa control system and the heat pump unit 2 Remove the screws that attac...

Страница 18: ...Setup mode press and hold the MENU POOL and SPA buttons for 5 seconds NOTE The display will revert back to OFF after one minute since the last key press 3 Press the Up or Down button to display REMOTE...

Страница 19: ...trol connected to the heat pump the display on the heat pump will show JANDY REMOTE ONLINE PUSH MENU TO DISABLE When the JE heat pump is online with the RS control all functionality of the control on...

Страница 20: ...re control When that happens the heat pump will automatically shut off but the filter pump will keep running 5 2 Operating the Controller Your new Jandy Pro Series JE heat pump is controlled by an adv...

Страница 21: ...LL will not be displayed if the unit is not provided with chiller You can change the temperature set point by pressing the Up or Down button Repeatedly press the Up or Down button until you reach the...

Страница 22: ...de 2 To enter the User Setup mode press and hold the MENU button for 5 seconds 3 To select spa timer use the Up or Down button to scroll through to display SELECT USER SETUP SPA TIMER Press the MENU b...

Страница 23: ...mum requirement of 30 gpm 114 lpm after the direction fitting or elbow has been installed Make sure the pool filter is clean before making any pressure switch adjustment A dirty filter will restrict t...

Страница 24: ...em which has been under water Zodiac recommends that you inspect your heat pump on a regular basis and especially after abnormal weather conditions The following basic guidelines are suggest ed for yo...

Страница 25: ...t gas enters the heat exchanger where the water extracts the heat The pump pulls in cool pool water which in turn converts the hot gas back into a liquid refrigerant and starts the cycle over again Th...

Страница 26: ...run and control board displays FAULT NO FLOW Verify circulating pump is on and all necessary valves are in the correct positions Verify filter and skimmers are clean Check water level in pool Tempora...

Страница 27: ...sure builds too high the high pressure switch will open causing the heat pump to shut off immediately The control will sense this fault condition and shut off the compressor until the switch re closes...

Страница 28: ...pansion Valve 1500 R0575000 15 Thermal Expansion Valve 2000 2500 R0575100 15 Thermal Expansion Valve 3000 R0575200 16 Air Temperature Sensor All R0575300 17 High Pressure Switch All R0575400 18 Low Pr...

Страница 29: ...mps Installation and Operation Manual 9 3 Zodiac JE 1500 Heat Pumps Exploded View C 1 2 3 4 5 6 7 8 9 10 11 12 20 21 DETAIL C SCALE 1 8 13 14 15 16 17 18 19 33 See Figure 19 for detail Figure 16 Zodia...

Страница 30: ...allation and Operation Manual 9 4 Zodiac JE 2000 JE2500 JE3000 Heat Pumps Exploded View C 1 2 3 4 5 6 7 9 8 10 12 20 11 21 23 DETAIL C SCALE 1 8 15 14 13 17 18 22 19 33 See Figure 20 for detail Figure...

Страница 31: ...ation and Operation Manual 9 5 Zodiac JE Single Phase Electric Box 9 6 Zodiac JE Three Phase Electric Box Figure 18 Zodiac JE Single Phase Electric Box Figure 19 Zodiac JE Three Phase Electric Box 24...

Страница 32: ...acPoolSystems com Zodiac Pool Systems Canada Inc 2115 South Service Road West Unit 3 Oakville ON L6L 5W2 1 888 647 4004 www ZodiacPoolSystems ca ZODIAC is a registered trademark of Zodiac Internationa...

Отзывы: