ECI0032 Network IO Control Card User Manual V1.5
Whether the device is subjected to
vibration or shock
Should be within the range of
vibration resistance and
impact resistance
Is the heat dissipation good
Keep good ventilation and
heat dissipation
Installation and
Wiring Status
Whether the basic unit and the
expansion unit are installed firmly
The mounting screws should
be
tightened
without
loosening
Whether the connecting cables of the
basic unit and the expansion unit are
fully inserted
The connection cable cannot
be loosened
Are the screws of the external wiring
loose
Screws should be tightened
without loosening
Whether the cable is damaged, aged,
cracked
The cable must not have any
abnormal appearance
6.2.
Common Problems
Problems
Suggestions
Motor does not rotate.
1.
Check whether the ATYPE of the controller is correct.
2.
Check whether hardware position limit, software
position limit, alarm signal work, and whether axis
states are normal.
3.
Check whether motor is enabled successfully.
4.
Confirm whether pulse amount UNITS and speed
values are suitable. If there is the encoder feedback,
check whether MPOS changes.
5.
Check whether pulse mode and pulse mode of drive
are matched.
6.
Check whether alarm is produced on motion
controller station or drive station.
7.
Check whether the wiring is correct.
8.
Confirm whether controller sends pulses normally.
The position limit signal is 1.
Check whether the limit sensor is working normally,