ECI0032 Network IO Control Card User Manual V1.5
Frequency
<
8kHz
Voltage level
DC24V
Max output current
+300mA
Max leakage current when off
25μA
Respond time to conduct
12μs
Respond time to close
80μs
Overcurrent protection
Support
Isolation method
optoelectronic isolation
Note:
The times in the form are typical based on the resistive load, and may change
when the load circuit changes.
Due to the leak-type output, the shutdown of the output will be obviously
affected by the external load circuit, and the output frequency should not be set
too high in the application. For low-speed output, it is recommended to be lower
than 8HKz. If there needs higher speed, please contact us to adjust parameter or
custom hardware.
→
Wiring Reference
→
Wiring Note:
⚫
The wiring principle of low-speed digital output OUT (0-15) is shown in the figure
above. The external signal receiving end can be an optocoupler or a relay or solenoid
valve, all can be connected as long as the input current does not exceed 300mA.
Содержание ECI0032
Страница 1: ......