Gas Connection

Gas Connection

MANUAL SHUT-OFF VALVE

•  This valve is not shipped with the appliance and must be provided by the 

installer. 

•  The manual shut-off valve must be installed in the gas service line between the 

gas hook-up on the wall and  the appliance inlet, in position where it can be 
reached quickly in the event of an emergency.

•  In Massachusetts:

 A T handle type manual gas shut-off valve must be installed in 

the gas supply line to this appliance. 

FLEXIBLE CONNECTIONS

•  In case of installation with flexible couplings and/or quick-disconnect 

fittings, the installer must use a heavy duty, AGA design-certified commercial 
flexible connector of at least ½˝ (1.3cm) IF NPT (with a suitable strain relief in 
compliance with ANSI Z21.41 and Z21.69 standards. 

•  In Massachusetts:

 The unit must be installed with a 36˝ (3 foot long) flexible gas 

connector. 

•  In Canada:

 Use CAN 1-6. 10-88 metal connectors for gas appliances and 

CAN 1-6.9 M79 quick disconnect device for use with gas fuel. 

PRESSURE TEST POINT STOPPER VALVE

To avoid gas leaks, the pressure test-point stopper valve and gasket supplied with the 
range must be installed on the gas fitting at the back of the range according to the 
diagram below.

INSTALLATION

Gas Connection

Gas pipe

Gasket

Gas connection adaptor 1/2” NPT with
pressure test point 1/8” NPT (to be fixed
toward external side of the appliance)

Pressure test-point stopper

PRESSURE REGULATOR

Since service pressure may fluctuate with local demand, every gas cooking 
appliance must be equipped with a pressure regulator on the incoming service line 
for safe and efficient operation.

•  The pressure regulator shipped with the appliance has two female threads 

34”NPT. The regulator shall be installed properly in order to be accessible when 
the appliance is installed in its final position. 

•  Manifold pressure should be checked with a manometer and comply with the 

values indicated below. 

 

Natural Gas->4.0”W.c.P

 

L P/Propane-> 10.0” W.c.P

•  Incoming line pressure upstream from the regulator must be 1˝ W.C.P. higher 

than the manifold pressure in order to check the regulator. 

•  The regulator used on this range can withstand a maximum input pressure of ½ 

PSI (13.8˝ W.C or 3.5kPa) If the line pressure exceeds that amount, a step down 
regulator is required. 

•  The appliance, its individual shut-off valve, and the pressure regulator must be 

disconnected from the gas line during any pressure testing of that system at 
pressures in excess of ½ PSI (13.8˝ W.c or 3.5kPa).

Pressure Regulator

Before carrying out this operation, disconnect the appliance from gas 
and electricity. 
Gas conversion shall be conducted by a factory-trained professional.

WARNING

INSTALLATION

Gas Connection

Содержание RCBR30

Страница 1: ...Dropins Installation Guide and Users Manual...

Страница 2: ...nd professional features into everyone s homes Because we continually strive to improve our products we may change specifications and designs without prior notice REGISTERING YOUR PRODUCT Please regis...

Страница 3: ...Bath and or our service contract partner Unapproved out of pocket payments for service will not be reimbursed All warranty procedures must be followed to maintain warranty coverage Warranty shall not...

Страница 4: ...ely and carefully Please observe all local state and national codes and ordinances Please ensure the range is properly grounded The installer should leave these instructions with the consumer who shou...

Страница 5: ...nce DO NOT touch any electrical switch DO NOT use any phone in your building DO NOT use any aerosol cans or combustibles Immediately call your gas supplier from a neighbor s phone follow the gas suppl...

Страница 6: ...ssible location in the gas line external to the appliance for the purpose of turning on and shutting off the gas to the appliance Do not use aerosol sprays in the vicinity of this appliance while it i...

Страница 7: ...35 3 8 19 1 2 19 1 8 20 3 8 2 1 2 INSTALLATION INSTALLATION ATTACHING THE DROPIN To prevent liquids from accidentally leaking into the underlying storage space the appliance is equipped with a specia...

Страница 8: ...shipped from the factory for use with natural gas For LP Propane household installation the appliance must be converted by the dealer factory trained professional or qualified licensed plumber or gas...

Страница 9: ...as pipe Gasket Gas connection adaptor 1 2 NPT with pressure test point 1 8 NPT to be fixed toward external side of the appliance Pressure test point stopper PRESSURE REGULATOR Since service pressure m...

Страница 10: ...e is a convertible type pressure regulator for use with Natural Gas at a nominal outlet pressure of 4 w c or LP gas at a nominal outlet pressure of 1 1 w c and it is pre assembled from the factory to...

Страница 11: ...a small size flathead screwdriver locate the choke screw see diagram below and turn to the right or left until the burner flame is adjusted to desired minimum 4 Make sure that the flame does not go ou...

Страница 12: ...of a gas cooking appliance generates heat and humidity in the room where it is installed Proper ventilation in the room is needed Make sure the kitchen is equipped with a range hood of appropriate pow...

Страница 13: ...cte Incorrecte Correcte Incorrecte A B WARNING WARNING Cooktop Cooking OPERATION Be sure to set all worktop oven broiler burner controls to the OFF position after each use of the appliance Maximum tem...

Страница 14: ...ation never move the appliance from its original installation position Never use abrasive cleaners Scratches on the stainless steel surfaces are permanent Do NOT clean the range when hot WARNING RANGE...

Страница 15: ...Installation Guide and User Manual 1 614 777 5004 2 0 0 www zlinekitchen com contact zlinekitchen com...

Отзывы: