5
4
• This appliance shall only be installed by an authorized professional.
• The appliance shall be installed in accordance with the standards of the country
where it will be installed. The installation of this appliance must conform to local
codes and ordinances. In the absence of local codes installation must conform
to American National Standards, National fuel Gas code ANSI Z223.1-Latest
edition/NFPA 54 or B 149.1.
• The appliance, when installed, must be electrically grounded in accordance with
local codes or, in the absence of local codes, with the National Electrical code,
ANSI/NFPA 70.
• In Canada:
Installation must be in accordance with the current The Natural Gas
and Propane Installation code, CAS B149.1. and/or local codes. Electrical
installation must be in accordance with the current CSA C22.1 Canadian
Electrical Codes Part 1 and/or local codes.
• If local codes permit, a flexible metal appliance connections with the new
AGA or CGA certified design, max 5 feet (1.5m) long, is recommended for
connecting this appliance to the gas supply line. DO NOT bend or damage the
flexible connector when moving the appliance.
• This appliance must be used with the pressure regulator provided. The regulator
must be properly installed in order to be accessible when the appliance is
installed in its final location. The pressure regulator must be set for the type of gas
to be used. The pressure regulator has 34˝ female pipe thread. The appropriate
fitting must be determined based on the size of your gas supply line, the flexible
metal connector and the shut-off valve.
• The appliance must be isolated from the gas supply piping system by closing its
individual manual shut-off valve during any pressure testing of the gas supply
piping system at test pressures equal to or less than 34 PSI(13,8w.cpr 3,5kPA).
• All opening holes in the wall and floor, back and under the appliance shall be
sealed before installation of the appliance.
• A manual valve shall be installed in an accessible location in the gas line
external to the appliance for the purpose of turning on and shutting off the gas to
the appliance.
Do not use aerosol sprays in the vicinity of this appliance
while it is hot.
WARNING
BEFORE INSTALLATION
Gas Supply
ROOM VENTILATION
An exhaust fan may be used with the appliance; in each case it shall be installed
in conformity with the appropriate national and local standards. Exhaust hood
operation may affect other vented appliances; in each case it shall be installed in
conformity with the appropriate national and local standards.
TYPE OF GAS
This appliance is shipped from the factory for use with natural gas. For use with
propane LP gas, please follow the conversion procedure described on pg. 18. A step
by step conversion procedure is also included with each set of LP gas nozzles.
GAS PRESSURE
• The maximum inlet gas supply pressure incoming to the gas appliance pressure
regulator is 34PSI (13,8w. cpr 3,5kPA).
• The minimum gas supply pressure for checking the regulator setting shall be
at least 1˝ w.c (249 Pa) above the inlet specified manifold pressure to the
appliance (This operating pressure is 4˝ w.c. (1.00kPa) for Natural gas and 11˝
w.c. (2.75 kPa) for LP gas.
• Gas cooktop requires 1”- 6” side wall spacing above the counter height for
proper combustion. Please review specific model installation instructions for
required dimensions. 30 inches between the cooktop and bottom of the cabinet
above. 0.25 inches for sides below countertop height.
NOTE
: Please consult your local building codes for variations with installation.
A properly grounded and horizontally-mounted electrical receptacle type NEMA 14-
50R should be installed no higher than 3” above the floor, no less than 2” and not
more than 8” from the left side (facing product); refer to electrical connection section.
GAS
An agency-approved, properly-sized manual shut-off valve should be installed no
higher than 3” above the floor and no less than 2” and no more than 8” from the
right side (facing product).
To connect gas between shut-off valve and regulator, use agency-approved,
properly sized flexible or rigid pipe. Check all local code requirements.
BEFORE INSTALLATION
Gas Supply